www.austin-hughes.com
UM-PPS-02-S-Q421V1
P.2
Part no.
IPD-02-S
< 1.2 > IP Dongle Installation & Meter ( PDU ) Cascade
Vertical IP dongle installation steps :
- slide the IP dongle on the plate above the meter
- plug the RJ-45 connector of IP dongle into the LINK port of the 1st level PDU meter
- use the CAT. 5 / 6 cable to connect IP dongle to network device
IP Dongle Access to 16 PDU Levels
Patented IP Dongle provides IP remote access to the PDUs by a true network IP address chain. Only 1 x IP dongle
allows access to max. 16 PDUs in daisy chain - which is a highly e
ffi
cient application for saving not only the IP re-
mote accessories cost, but also the true IP addresses required on the PDU management.
Hot-Pluggable design facilitates the IP dongle installation. Simply integrate the IP Dongle to the 1st PDU, then the
entire daisy chain group can be remote over IP. Hence, administrator can remotely access all PDUs in the daisy
chain group by one single IP via the IP Dongle.
IP Dongle for vertical PDU & 2U rackmount PDU
- SNMP capability v2 / v3
1st level
PDU meter
3rd level
PDU meter
2nd level
PDU meter
Cat 5 / 6 cable
Up to 20M
Cat 5 / 6 cable
Up to 20M
To LINK port of
the 1st PDU
IP dongle
Network Hub
To LAN port
To LINK port
of next PDU
( Up to 16 levels )
LINK
OUT
TH 1
TH 2
Meter ( PDU ) Cascade
■
The PDU can be cascaded up to 16 levels
■
For IP PDU access simply connect 1 x IP Dongle - IPD-02-S
■
1 x IP Dongle allows access to 16 levels
■
Single & 3 Phase PDU can be inter-cascaded in the single daisy chain