background image

 
 

 

 35 

 

 
 
 

AA 
 
 
         

* It shows the UPS is locked.  

 
Turn Off the breaker of Input. Your Setting changes are completed. 
 

7.3. Commissioning   

After all connections and settings have been done, UPS can be started-up in two ways. If the mains 
is in normal condition, you may start-up with the mains. If it is not, you may start-up the UPS from 
the battery.  
 
 

 

 

7.3.1. Start-Up with the Mains 

 

1.

 

Switch the input circuit breaker on the distribution panel to “ON” position.  

2.

 

Switch the circuit breakers on external battery cabinet –if exists- to “ON” position. 

3.

 

Switch the input circuit breaker (F1) to “ON” position.  

 

Green LEDs 

 & 

 light up to show the Utility and Bypass Inputs are normal and the LCD display 

with parallel function will illustrate from drawing A1, drawing A2 to drawing B. Otherwise the LCD 
display will illustrate from drawing A2 to drawing B. 
 
 
 
 
 

A1. 

 

 
 
 
 
 
 

 

 

Even  with  no  connections  have  been  done,  hazardous  voltages  may  exist  on  connection 
terminals and inside the UPS. Do not touch these parts. 

 

 

If you work on terminals; all circuit breakers in the input/bypass distribution panel, and the 
battery circuit breakers in the external battery cabinet should be brought to “0” position. 

 

Summary of Contents for DSP FLEXIPOWER SERIES

Page 1: ...DSP FLEXIPOWER SERIES SINGLE PHASE IN SINGLE PHASE OUT 5 10kVA THREE PHASE IN SINGLE PHASE OUT 10kVA UNINTERRUPTIBLE POWER SYSTEMS U US SE ER R M MA AN NU UA AL L...

Page 2: ...e labeled with a CE mark comply with the Standard EN 62040 1 and EN 62040 2 Read the manual completely before working on this equipment Keep this manual near UPS for easy consultation Reproduction ada...

Page 3: ...eaker Active ON I Closing the Circuit Passive OFF 0 Opening the Circuit Manufacturer INFORM ELEKTRONIK SAN ve TIC A S Emek Mah Ordu Cad No 51 34785 Sancaktepe ISTANBUL Phone 0216 622 58 00 Fax 0216 62...

Page 4: ...packing 6 4 2 Installation Procedures 8 4 2 Installation Procedures 8 4 2 1 PE Connection 11 4 2 2 Input Connection 12 4 2 3 Battery Connection 12 4 2 4 Output Connection 13 4 2 5 Communiation Interfa...

Page 5: ...3 2 Start Up with the Battery Cold Start 38 7 4 Decommissioning 39 7 6 Manual Maintenance Bypass Instructions and Decommissioning 40 7 7 Emergency Power Off EPO 41 8 MAINTENANCE 42 8 1 Batteries 42 8...

Page 6: ...rding to the terms in the manual then the UPS is out of warranty Neglect accident misuse misapplication or incorrect installation Failure due to fortuitous circumstances or force majeure After deliver...

Page 7: ...a vertical position Make sure that the floor can support the weight of the system Connect the PE ground connector before connecting any other cable UPS is designed for indoor use To reduce the risk of...

Page 8: ...bracelets and all metal objects Only use tools with insulated handles Wear rubbers gloves and a rubber apron when handling batteries Do not lay tools or metal parts on top of batteries Eye protection...

Page 9: ...cm at the front and back side of the UPS for ventilation To eliminate any overheating of the UPS keep all ventilation openings free from obstruction and do not store things on top of the UPS Even thou...

Page 10: ...for longer than 6 months they shall be charged periodically Charge period depends on the storage temperature The relationship is as shown below Every 9 months if the temperature is below 20 C Every 6...

Page 11: ...installation If any equipment has been damaged during shipment keep the shipping and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage...

Page 12: ...recommended to store the original UPS packaging for future needs 5 Reload the UPS via wheels 6 Lock the wheels where installed 3 Screw off the stop plates placed at the front of UPS 4 Remove the stop...

Page 13: ...ns Standard UPS circuit breakers and terminal settlements are shown below Terminals and Circuit Breakers for 5 6 8 10kVA 1Phase In 1Phase Out UPS The equipment may only be installed and commissioned b...

Page 14: ...BLE CROSS SECTION INPUT OUTPUT BATTERY NEUTRAL PE PB 5 6KVA 33 A 32 A 32 A 25 A 6 mm 6 mm 6 mm 6 mm 6 mm 8 10KVA 54 3 A 63 A 50 A 41 A 10 mm 10 mm 6 mm 10 mm 10 mm After removing the terminal cover in...

Page 15: ...10 Pass the cables through the glands...

Page 16: ...be grounded via output protective earth terminal PB If there is an external battery cabinet present it shall be grounded via battery protective earth terminal PB of the UPS Connect the PE ground conn...

Page 17: ...e batteries There is no need any further connection so replace the cover Read the Service Manual carefully for External Battery connection If the batteries shall be put in a separate additional batter...

Page 18: ...f the UPS is compatible with many operating systems such as Windows 98 2000 ME NT and XP In the event of an extended period of UPS non operation the batteries must be charged periodically in order to...

Page 19: ...quipped with Serial Communication as standard DSUB 9 female connector with the following pin layout shall be used on the UPS side of the connection cable Pin 3 RS232 Rx Pin 2 RS232 Tx Pin 5 Ground Har...

Page 20: ...on please refer to the User s Manual attached with the card 4 2 5 5 NetAgent II Card It is installed into INTERFACE slot on the rear panel For installation please refer to the User s Manual attached w...

Page 21: ...e function and short pin2 3 to disable it CN2 for RS485 and CN3 for remote power 4 2 5 8 USE USB Card It is installed into INTERFACE slot on the rear panel CN1 for USB Comply with USB version 1 0 1 5M...

Page 22: ...in 10 Shutdown UPS positive signal The shutdown function will be activated after a 6 25Vdc is put between pin9 and pin10 for 5 seconds The capacity of each relay contact is 40Vdc 25mA Installation Pos...

Page 23: ...ergy needed for the load is provided by the battery in UPS or in external battery cabinet s These batteries are charged by an intelligent battery charging circuit during the mains within the limits Ba...

Page 24: ...For the mains limits for Online Operation please see Appendix 2 Technical Specifications The upper limit of mains voltage is independent from the load percentage and it is 270V UPS switches to Battery...

Page 25: ...urn back to within the limits of bypass In case Online Operation norl is set as Operation mode through settings menu 5 3 Bypass Mode If UPS is commissioned through the mains it starts up on Bypass Mod...

Page 26: ...Operation norl it can not switch to Bypass Eco Operation even if a fault occurs If the batteries and the inverter are suitable to supply the loads UPS switches to Battery Operation To return to Eco O...

Page 27: ...ters such as battery type charge discharge cycle and depth of discharge ambient temperature conditions Please look at Appendix 2 Technical Specifications for the ideal environmental conditions for the...

Page 28: ...7 Manual Bypass Mode This feature is useful while performing maintenance or service and shall only be executed by authorized Technical Service Personnel Manual by pass enables the user to isolate the...

Page 29: ...ut UPS and KEYPAD enables the user to access the UPS 6 1 1 Keypad LCD Display Green LED lights up to indicate the UPS has the capability to run under redundancy mode Green LED steadily lights up to in...

Page 30: ...tal Display LCD ENERGY FLOW DIAGRAM is located at the left side and the measurements informations are located at the right of LCD You may find the information of some Symbols on the LCD Display Panel...

Page 31: ...26 Self Test Self Test OK Self Test FAIL Battery Mode Online norl Mode OFF Mode It shows OFF which means UPS pre start is unsuccessfull...

Page 32: ...UPS fails to transfer to bypass Bypass Abnormal at ECO mode 8 Utility Input Abnormal 9 OFF UPS Shutoff 10 LINE OFF UPS Abnormal Lock 11 UPS Flow Chart 12 4 Digits Measurement Display 13 Indicate the...

Page 33: ...r17 Output Parameters Set Error in Parallel System 34 Er21 ID Numbers are in conflict in Parallel System or ID number Error in single unit 35 Er24 Parallel communication error communication wire disco...

Page 34: ...minal Resistor for Parallel function C CAN Bus Connection Port for Parallel System PAR1 CN2 1 PAR2 CN2 2 D Communication Slot E Air Ventilation Hole F Cooling Fan G EPO H Input Output Manual Bypass Ci...

Page 35: ...d to scroll down the screen and check the UPS settings The LCD display will show in consequence between Drawing Q1 buzzer Drawing R1 Self test Drawing S1 Bypass Voltage Windows Drawing T Output Freque...

Page 36: ...31...

Page 37: ...djusted to narrow one S2 It shows bypass voltage is adjusted to wider one T It shows Frequency Window is 3Hz U It shows inverter output voltage V1 It shows the UPS is operated in normal mode V2 It sho...

Page 38: ...operated in CVCF 60Hz mode W It shows Output Voltage Adjustment from 0 to 3 or 0 to 3 X It shows UPS Identification Number Y It shows the UPS is in the No 1st of parallel systems The adjustment of fr...

Page 39: ...c 220Vac 230Vac or 240Vac Drawing V1 V2 V3 and V4 mean the operation modes of the UPS of which alternative is Online Eco Economic mode fixed 50Hz Output or fixed 60Hz Output Drawing W means the adjust...

Page 40: ...xternal battery cabinet if exists to ON position 3 Switch the input circuit breaker F1 to ON position Green LEDs light up to show the Utility and Bypass Inputs are normal and the LCD display with para...

Page 41: ...to charge the batteries 4 Press the UPS On Switch 5 for approx 3 seconds then the Buzzer sounds twice and the LCD display changes from drawing B to drawing C C Then the UPS is under self test mode aga...

Page 42: ...n the screen F It shows 220Vac in Utility Input Your start up operation of the UPS is completely now Make sure the UPS is plugged onto the wall receptacle for charging at least 8 hours and the batteri...

Page 43: ...pprox 5 seconds to awake the UPS and then the buzzer sounds twice The LCD display will illustrate from drawing A to drawing G and keep awake for approx 15 seconds A G G It shows Off which means the UP...

Page 44: ...the output circuit breaker on the distribution panel to OFF position 2 Switch the output circuit breaker F2 to OFF position 3 If exists switch external battery cabinet circuit breakers to OFF position...

Page 45: ...he breakers on external battery cabinets if any to 0 position The loads will be continued to be supplied directly from the mains In order to transfer the loads from Manual Bypass to UPS without interr...

Page 46: ...atched switch can be used as described in below figure When UPS operates in Online Operation the latch switch shall be normally open NO Whenever any emergency occurs you have to make the switch closed...

Page 47: ...horized Technical Personnel 8 2 Fans The life of fans used to cool the power circuits depends on the usage and environmental conditions Please look at Appendix 2 Technical Specifications for detailed...

Page 48: ...hort circuit occurred at the EPO terminal 4 Er11 Er33 Remove the objects blocked onto the ventilation holes 5 Er14 Check the cooling FANs on rear panel are working normally 6 Er15 Make sure the UPS is...

Page 49: ...he Utility is abnormal after the UPS is locked the LED will be extinguished and the LCD will be shown on the LCD screen To release the UPS lock please proceed the followings Check those error messages...

Page 50: ...mbers are in conflict in Parallel System or ID number Error in single unit 10 Er21 Parallel communication error communication wire disconnected or failure to find ID1 UPS in parallel system 11 Er24 CV...

Page 51: ...w Battery Bad Disconnect Overload interrupting during transfer UPS Fault Information on LCD Input Voltage Input Frequency Output Voltage Output Frequency Load Percentage Battery Voltage Inner Temperat...

Page 52: ...us current with a power factor near to 1 from the mains On battery mode it increases the battery voltage level required for the inverter and uses current from the battery with a low ripple ratio thus...

Reviews: