System Installation
NOTE : All units are quality tested at the factory. All units are rated up to 12 bar. Mount your ultraviolet
steriliser horizontally or vertically on a level and firm surface. Do not lay the system on the ground or
where water may puddle. Do not submerge. Install sterilizer equipment in a readily accessible and well
lit location to facilitate inspection and maintenance. On all units allow space to change the UV lamp and
Quartz sleeve (typically leave a maintenance space equal to the overall UV system length) and other
parts.
Installation Instructions
Step 1:
Open the package and check you have all the components:
Reactor Chamber,
UV Lamp,
Quartz Sleeve,
O-ring,
Electronic Ballast and Support.
Step 2:
Ensure the quartz sleeve and UV lamp are thoroughly clean before starting to install.
This can be done with alcohol or a mild detergent. Always wear soft non-abrasive gloves to keep
any finger marks away from them.
Step 3:
Remove the end nut from the Reactor Chamber.
Step 4:
Insert the spring into the quartz sleeve.