background image

Ref. IS.MDUINO.58+ 

 

Rev. 0: 30-08-2019 

 

40 

 

 

I/O technical details:  

12

 

Digital Output Waveform: 

 

 

 

 

 

 

 

Digital Out-put Turn-off: 

 

PWM Waveform:  

 

 

Summary of Contents for M-DUINO PLC ARDUINO ETHERNET 58

Page 1: ...M DUINO PLC ARDUINO ETHERNET 58 I Os ANALOG DIGITAL PLUS PLC ARDUINO ETHERNET 58 I Os ANALOG DIGITAL PLUS...

Page 2: ...Ref IS MDUINO 58 Rev 0 30 08 2019 1...

Page 3: ...Ref IS MDUINO 58 Rev 0 30 08 2019 2 Ethernet PLC MDuino 58 PLUS User Guide Revised August 2019...

Page 4: ...g the directive may damage the controller Improper use of this product may severely damage the controller Refer to the controller s User Guide regarding wiring considerations Before using this product...

Page 5: ...ce doit tre effectu e par personnel qualifi familiaris avec la fabrication le fonctionnement et les dangers li s au contr leur La maintenance doit tre effectu e avec l quipement hors service et d conn...

Page 6: ...any codes regulations or standards that apply to the combination of products in the customer s application or use of the product The following are some examples of applications for which particular a...

Page 7: ...ze risks resulting from the handling or manipulation of such products systems and to avoid possible hazards Disclaimers Weights and Dimensions Dimensions and weights are nominal and they are not used...

Page 8: ...s during commissioning operation maintenance and repairs caused by for example Hardware defects and or software errors in the sensors controllers actuators and connection technology Response times of...

Page 9: ...ED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE INDUSTRIAL SHIELDS DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED Limitations of Liability INDUSTRIAL SHIELDS SHALL NO...

Page 10: ...ecautions 18 3 3 1 Arduino Board 18 3 2 Intended Audience 18 3 3 General Precautions 18 Software interface 18 4 How to connect PLC Arduino to PC 21 5 How to connect PLC to power supply 23 6 M Duino 58...

Page 11: ...ernet 35 10 7 RTC 36 10 8 uSD 36 Instructions for interconnection between Industrial Shields controllers 38 11 11 1 RS 232 Communication 38 11 2 RS 485 Communication 38 11 2 2 Full Duplex 38 11 3 Ethe...

Page 12: ...and D the shield from above Having a B and a C in the middle of them The inputs in the zone B are named I0 X being X any number suitable in the Shield Outputs are named as Q0 X and relays as R0 X The...

Page 13: ...Shield 13 Inputs 13 Digital inputs 6 of which can work as Analog Input 8 Outputs 8 Digital Outputs 3 of which can work as Analog Output 13 Inputs 13 Digital inputs 6 of which can work as Analog Input...

Page 14: ...58 Rev 0 30 08 2019 13 1 3 A Zone Features Shield A Zone Communication Shield 1x Ethernet 1x USB 1x I2C 3x TTL 1x RS 232 1x HALF FULL Duplex RS 485 1x SPI external Port 1x RTC 1x uSD Socket 1 4 Mechan...

Page 15: ...a project Cannot be working in a final application An Dig Input 10bit 0 10Vcc 0 to 10Vac Input Impedance 39K Separated PCB ground Rated Voltage 10Vac 7 to 24Vdc I min 2 to 12 mA Galvanic Isolation Rat...

Page 16: ...M Isolated Output 8bit 24Vcc 5 to 24Vdc I max 70 mA Galvanic Isolation Diode Protected for Relay Rated Voltage 24Vdc Expandability I2C 127 elements Serial Port RS232 RS485 By using this type of signal...

Page 17: ...terminal Shock resistance 80m s2 in the X Y and Z direction 2 times each Ambient temperature operating 0 to 60 C Ambient humidity operating 10 to 90 no condensation Ambient environment operating With...

Page 18: ...on equipment 5130 Pulse General To identify the control by which a pulse is started IEC 60417 Graphical symbols for use on equipment 5017 Earth Ground To identify an earth ground terminal in cases wh...

Page 19: ...ve a serious influence on lives and property if used improperly consult your INDUSTRIAL SHIELDS representative Ensure that the rating and performance characteristics of M Duino are sufficient for the...

Page 20: ...go to File Preferences located in the top left corner 2 In Additional Boards Manager URLs write the following http apps industrialshields com main arduino boards package_industrialshields_index json...

Page 21: ...IS MDUINO 58 Rev 0 30 08 2019 20 5 Search for industrialshields on the browser 6 Click install selecting the latest version Following these steps you will be able to see now the Industrial Shields Boa...

Page 22: ...e are some examples of programming in File Examples M Duino Family Furthermore there are some extra libraries that can be found in Industrial Shields github https github com IndustrialShields How to c...

Page 23: ...Ref IS MDUINO 58 Rev 0 30 08 2019 22 Select the correct M Duino Board M Duino 58 Select correct port...

Page 24: ...ories regardless of where use of the device is intended The equipment must be powered from an external power source in accordance with IEC 61010 1 whose output is MBTS and is limited in power accordin...

Page 25: ...3 50 51 52 Reset Vin5 2 I2C SS I2C SS RX0 SS TX0 SS RX1 SS TX1 SS RX2 serial 2 TX2 serial 2 RS485 RS485 RS485 RS485 Arduino Pin SPI SPI SPI SPI 5V Arduino Pin Gnd Gnd Power Supply Base common unit A...

Page 26: ...t Arduino mega has auto reset when using serial communication code Set switch to OFF when using serial communication When uploading code to Arduino Mega set switch to ON Ethernet Arduino Power Connect...

Page 27: ...put GND I0 3 Digital Input GND I0 2 Digital Input GND I0 1 Digital Input GND I0 0 Digital Input B Zone M Duino Connector Arduino Pin Function GND A0 7 1 A0 6 1 A0 5 1 Q Vdc COM Q0 7 1 Q0 6 1 Q0 5 1 Q0...

Page 28: ...put GND I1 3 Digital Input GND I1 2 Digital Input GND I1 1 Digital Input GND I1 0 Digital Input C Zone M Duino Connector Arduino Pin Function GND A1 7 1 A1 6 1 A1 5 1 Q Vdc COM Q1 7 1 Q1 6 1 Q1 5 1 Q1...

Page 29: ...GND I2 3 Digital Input GND I2 2 Digital Input GND I2 1 Digital Input GND I2 0 Digital Input D Zone M Duino Connector Arduino Pin Function GND A2 7 A2 6 1 A2 5 1 Q Vdc COM Q2 7 Q2 6 1 Q2 5 1 Q2 4 Q2 3...

Page 30: ...Choosing between RX1 or the input I1 6 If this switch is ON it enables the I1 6 input and disables the RX1 If this switch is OFF it enables RX1 and disables I1 6 1 TX1 I1 5 Choosing between TX1 or th...

Page 31: ...If this switch is ON it enables the Half Duplex HD option and disables the FD If this switch is OFF it enables Full Duplex FD and disables HD 1 RTC SDA This switch enables the communication to communi...

Page 32: ...hat will provide this digital output is represented with QX X being X any number of the tables above If it is desired to use an Analog Output the pin must be set to OFF and the pin that will provide t...

Page 33: ...uration means that when the pin is at rest nothing connected to it it always reads a HIGH value In this case it reads 5V when nothing is connected The pull up configuration is stablished by default in...

Page 34: ...o correctly work with these pins 9 4 SPI MISO MOSI SCK These pins can only work as a 5V pins if the Ethernet protocol is not going to be used As the Ethernet protocol uses the SPI to communicate with...

Page 35: ...below Function Arduino Pin DI 14 RO 15 RE 11 DE 46 For the RS 485 communication protocol there is only one switch that affects in this communication The RS 485 protocol will be always enabled the only...

Page 36: ...in3 21 20 1 0 19 18 15 14 2 3 Check the switch configuration at section 8 to enable SS pins 10 5 TTL M Duino has two TTL ports RX0 TX0 RX1 TX1 TTL0 is accessed with the function Serial pins 0 and 1 of...

Page 37: ...uSD The micro SD uses the SPI communication to interact with the Arduino Mega The SPI protocol is always enabled as there are no switches that configure it However there is a switch that must be place...

Page 38: ...hine Unexpected operation of a process or machine could result in death or injury to personnel and or property damage Before inserting a memory card always ensure that the CPU is offline and in a safe...

Page 39: ...f IS MDUINO 58 Rev 0 30 08 2019 38 Instructions for interconnection between Industrial Shields 11 controllers 11 1 RS 232 Communication 11 2 RS 485 Communication 11 2 1 1 Half Duplex 11 2 2 Full Duple...

Page 40: ...Ref IS MDUINO 58 Rev 0 30 08 2019 39 11 3 Ethernet For an Ethernet communication between Industrial Shields equipment a SFTP CAT 6 Ethernet crossover cable must be used...

Page 41: ...Ref IS MDUINO 58 Rev 0 30 08 2019 40 I O technical details 12 Digital Output Waveform Digital Out put Turn off PWM Waveform...

Page 42: ...Ref IS MDUINO 58 Rev 0 30 08 2019 41 Analog Out Turn On Analog Out Turn Off Analog Digital input Turn on...

Page 43: ...Ref IS MDUINO 58 Rev 0 30 08 2019 42 Typical Connections 13...

Page 44: ...Ref IS MDUINO 58 Rev 0 30 08 2019 43...

Page 45: ...Ref IS MDUINO 58 Rev 0 30 08 2019 44...

Page 46: ...Ref IS MDUINO 58 Rev 0 30 08 2019 45...

Page 47: ...Ref IS MDUINO 58 Rev 0 30 08 2019 46...

Page 48: ...406 connector from Phoenix contact FK MC 0 5 10 ST 2 5 Connection details Article reference MC 0 5 10 G 2 5 THT Height 8 1mm Pitch 2 5mm Dimension 22 5mm Pin dimensions 0 8x0 8mm Pin spacing 2 50mm Ar...

Page 49: ...chanical Characteristics 15 Dimension M Duino 58 I Os PLUS DIN Rail mounting For optimal operation of the product it must be located in an electrical cabinet with IK08 mechanical protection The minimu...

Page 50: ...witches and contactors in a dedicated electric cabinet and keep the cabinet ventilated If the location has high ambient temperature or heat generating equipment nearby install forced convection device...

Page 51: ...ese systems The means employed for grounding or insulating the equipment from ground should be checked to assure its integrity Accumulations of dust and dirt on all parts including on semiconductor he...

Page 52: ...ning can damage the screws and or the module with the risk of falling short circuits and malfunctions Before handling a module dispose of the electrostatic charge accumulated by the human body by touc...

Page 53: ...Ref IS MDUINO 58 Rev 0 30 08 2019 52 Revision Table 17 Revision Number Date Changes 0 30 08 2019 First implementation...

Page 54: ...08 2019 53 About Industrial Shields Direction F brica del Pont 1 11 Zip Postal Code 08272 City Sant Fruit s de Bages Barcelona Country Spain Telephone 34 938 760 191 34 635 693 611 Mail industrialshie...

Reviews: