background image

PB-INspektor

®

 

Commissioning

 

Page 17 

Not all diagnostics are relevant to PROFIBUS device faults. Which of them are 

depends on the device type and its configuration in the PLC program, so that 

this decision also has to be made on a case to case basis. In the Extended 

View  of  the  Alarms/Snapshots  settings,  you  can  set  the  Internal  Diagnostics 

and/or External Diagnostics threshold to a value greater than “1” for a specific 

device only, or disable it for that device by entering “0”. 

 

5.2.5  Troubleshooting   

The best approach when looking for the cause of communication faults, such 

as error frames or retransmission, is to start by ignoring the diagnostics for all 

PROFIBUS devices. This is done by entering “0” for the threshold settings of 

each device.  

 

To find the cause of device faults, on the other hand, it is the diagnostics that 

are relevant. 

 

If  you  are  uncertain  how  to  evaluate  the  measurement  results,  you  should 

have  your  network  tested by  a  PROFIBUS  specialist. The  specialist  will  find 

and  correct  any  existing  faults,  and  set  the  appropriate  threshold  values  for 

your system. 

Quality Parameters

 

Manual 

Page 18 

6  Quality Parameters 

6.1  Drop-outs 

The PROFIBUS INspektor detects drop-outs in two different ways: 

 

1. Detection of parameter frames 

 

A PROFIBUS device receives a parameter frame from the bus master 

when it needs to be newly added to the bus (restart) or when the de-

vice  has  transmitted  a  diagnostic  frame  requesting  parameterization. 

In all three cases, the PROFIBUS device cannot exchange user data 

any longer and is thus considered dropped.  

 

2. No reply from PROFIBUS device 

 

PROFIBUS devices are only parameterized when they are started or 

restarted  (after  drop-out).  Even  if  no  parameter  frame  occurs  during 

monitoring,  the  PROFIBUS  INspektor  can  still  determine  a  device  

failure from the missing reply.  

 

6.2  Diagnostics 

If a fault or exception condition occurs in a PROFIBUS device, the master is 

informed by one of the following three frame types: 

 

x

  DH response, regular diagnostic message that occurs when an error 

state  has  newly  occurred,  changed  or  gone  away  during  cyclic  data 

exchange; e.g. if a wire of an external sensor breaks at an analog 4-

20 mA  input  –  the  INspektor  interprets  this  frame  as  “External  

Diagnostics” 

x

  RS  response  when  a  service  request  received  previously  from  the 

master  cannot  be  executed  because  of  an  error  (in  that  case  DP 

slaves are usually no longer in cyclic data exchange); e.g. in case of 

an internal fault in a remote I/O module, causing incomplete or no data 

to  be  supplied  –  the  INspektor  interprets  this  frame  as  “Internal  

Diagnostics” 

x

  RR response in the case of a dynamic overload that prevents saving 

and  processing  the  frame  received  previously  from the  master  –  the 

INspektor interprets this frame as “Internal Diagnostics” 

 

The  devices' responses regarding  the  diagnostics  vary  from  manufacturer  to 

manufacturer; there is no standardization in that respect. Some devices do not 

distinguish between external and internal diagnostics and only report one type. 

Summary of Contents for PB-INspektor

Page 1: ...4491 5818 99 E Mail info indu sol com www indu sol com Your partner and specialist for Fieldbus Industrial Ethernet and PROFInet Indu Sol GmbH Indu Sol GmbH Blumenstrasse 3 04626 Schmoelln Blumenstras...

Page 2: ......

Page 3: ...ns of this documen tation no claims can be made Any duplication processing and translation of this document as well as excerpts from it require the written allowance by Indu Sol GmbH All rights after...

Page 4: ...12 5 1 First Connection to the Network 12 5 1 1 Case 1 Local Access Only 14 5 1 2 Case 2 Network Integration 14 5 1 3 Other Basic Settings 14 5 1 3 1 Internal Date and Time 14 5 1 3 2 Measuring Locat...

Page 5: ...7 4 System Information 22 7 5 Settings 23 7 5 1 Tresholds Alarms 23 7 5 2 Last Cycle 23 7 5 3 Device Designations 23 7 5 4 System 24 7 5 4 1 Network 24 7 5 4 2 SNMP LLDP 24 7 5 4 3 Time Date 24 7 5 4...

Page 6: ...OFIBUS without interfering with its operation Using the active PROFIBUS connection cable optional accessory not included in scope of delivery it can be inte grated into the fieldbus anytime without un...

Page 7: ...rew connector for power supply x Screw connector for control signals x Manual x CD ROM with protocol analysis software as snapshot viewer incl PDF documentation The protocol analyzer option additional...

Page 8: ...isplays 3 1 Connectors Fig 1 Connectors 3 2 Status LEDs LED Colour Meaning PWR green Power supply OK LAN green Network connected ERR red Device initialization or error RUN yellow Baud rate detection f...

Page 9: ...ssembly Attention To ensure proper cooling please provide sufficient space to neighboring components x On the left and right 20 mm x On all other sides 50 mm 4 2 Measuring Location You can basically c...

Page 10: ...ery simple way to connect the PROFIBUS INspektor to the fieldbus on a live PROFIBUS anytime and without undesirable side effects by using a spur This method is also very useful if you want to connect...

Page 11: ...hut down the PLC and all the devices connected to the PROFIBUS in other words you need to shut down the whole plant Connect the INspektor with a piece of PROFIBUS DP cable at least one me ter long for...

Page 12: ...to shut down the PLC and all the devices connected to the PROFIBUS in other words you need to shut down the whole plant Connect the INspektor with a piece of PROFIBUS DP cable at least one me ter long...

Page 13: ...have to change the default setting How this is done is described below using Windows XP as an example Connect the PROFIBUS INspektor to your PC or notebook by using a standard crossover patch cable n...

Page 14: ...following address http 192 168 212 212 You can now access the PROFIBUS INspektor s web interface see Web Interface chapter on page 20 Here you can also change the INspektor s network configuration if...

Page 15: ...ime set in the PROFIBUS INspektor is displayed on the Over view startup page If the time is not correct for your time zone or daylight saving time you can adjust it under Settings System Time Date 5 1...

Page 16: ...ektor automatically restarts the segment detection after approx 2 minutes 5 2 2 Factory Preset Alarm Defaults The Alarm Alarm Contact and Snapshot functions are enabled by default The quality paramete...

Page 17: ...the error in the Alarm List and displays a trace log under Snapshots 5 2 4 Evaluation Threshold Adjustment and Troubleshooting All the information regarding error events and the status of each device...

Page 18: ...isable it for that device by entering 0 5 2 5 Troubleshooting The best approach when looking for the cause of communication faults such as error frames or retransmission is to start by ignoring the di...

Page 19: ...three frame types x DH response regular diagnostic message that occurs when an error state has newly occurred changed or gone away during cyclic data exchange e g if a wire of an external sensor brea...

Page 20: ...set in the master When analyzing the PROFIBUS the INspektor distinguishes between two retry types x Max Retries per Bus Cycle x Total Retries When determining the Max Retries per Bus Cycle the PROFIB...

Page 21: ...ea With the two icons below it you can toggle between the English and German interface languages The measuring location is given at the top of the screen This is particularly useful when you are using...

Page 22: ...larm list as well as the baud rate and the INspektor s internal temperature and time of day 7 1 2 Device Overview Here all the PROFIBUS devices detected by the INspektor are sorted by address and disp...

Page 23: ...snapshot is a trace log containing max 500 frames captured from the entire bus communi cation the trace starts shortly before and ends shortly after an error event You can download snapshots to a not...

Page 24: ...IBUS INspektor can record up to 500 frames in the period surround ing an error event 7 5 2 Last Cycle The Overview startup page provides three overlapping time periods for which the error events are s...

Page 25: ...ess of a time server to have the date and time updated automatically 7 5 4 4 Password Here you can change the user name and password for logon The default setting for both fields is config 7 5 4 5 Lic...

Page 26: ...8 Snapshot Analysis For snapshot display the supplied telegram monitor PROFI TM is used To interpret a snapshot do the following If needed pursuing analysis to the recognized PROFIBUS event can be mad...

Page 27: ...Snapshot Analysis Manual Page 26 Fig 10 Telegram mode in PROFI TM For this additional software there is an integrated help function as well as manual in PDF format...

Page 28: ...R LED are both not lit permanently Possible cause x IP address conflict with a device on the connected network Remedy x Remove the INspektor from the network and reconfigure the INspektor s IP address...

Page 29: ...roubleshooting Manual Page 28 Problem Causes and remedies Web interface is not displayed properly Possible cause x Java Script has been disabled Remedy x Enable Java Script in your web browser setting...

Page 30: ...of protection IP 20 Operating temperature 5 C to 55 C Storage temperature 20 C to 70 C Certifications CE FCC VCCI 11 GPL Information The PB INspektor uses the following components under GNU General Pu...

Page 31: ...andard industrial environments A Declaration of Conformity in compliance with the above standards has been made and can be inspected at Softing AG on request NOTE For compliance with the legal EMC req...

Page 32: ...PB INspektor Notices Page 31 13 Notices...

Page 33: ...PB INspektor Notices Page 32...

Page 34: ...PB INspektor Notices Page 33...

Page 35: ......

Page 36: ...er and specialist for Fieldbus Industrial Ethernet and PROFInet Indu Sol GmbH Blumenstrasse 3 04626 Schmoelln Germany Telephone 49 34491 5818 0 Telefax 49 34491 5818 99 E Mail info indu sol com www in...

Reviews: