PB-INspektor
®
Commissioning
Page 13
Now make the following entries:
Fig. 6: Network configuration in the PC (Windows XP)
Click OK twice to confirm the open dialog boxes. Your network configuration is
changed.
Start the web browser (Microsoft Internet Explorer Version 6 or above, or
Mozilla Firefox Version 2 or above; Java Script must be enabled) and type in
the following address: http://192.168.212.212. You can now access the
PROFIBUS INspektor's web interface (see Web Interface chapter on page
20
).
Here, you can also change the INspektor's network configuration, if required.
To do this, select Settings -> System -> Network. See also the Network
Settings chapter on page
24
. The user name and password for logon are
factory preset to “config”.
Attention: Enter the new IP address in the relevant field on the ID
plate, which is provided on the right side of the housing. The
PROFIBUS INspektor cannot be accessed without this address.
Commissioning
Manual
Page 14
5.1.1 Case 1 - Local Access Only
In this case, the PROFIBUS INspektor is NOT integrated into an existing
network. You can either continue by using the “Alternate Configuration” set for
the LAN connection in your PC, or assign a different free and available IP
address to the INspektor.
5.1.2 Case 2 - Network Integration
In this case, the PROFIBUS INspektor is integrated into an existing network.
Ask your network administrator for the appropriate manual or automatic
(DHCP) setting of the network configuration. You can then connect the
INspektor via a standard patch cable to an existing switch or hub, and thus
to the LAN.
5.1.3 Other Basic Settings
5.1.3.1 Internal Date and Time
The date and time set in the PROFIBUS INspektor is displayed on the Over-
view startup page. If the time is not correct for your time zone or daylight
saving time, you can adjust it under Settings -> System -> Time/Date.
5.1.3.2 Measuring Location
The measuring location of the currently selected PROFIBUS INspektor is
always shown at the top of the screen. To assign a location name, select
Settings -> Designations and enter the name in the top line of the table.
Assigning location names makes it easier to distinguish multiple INspektors on
the network.
5.1.3.3 Favorites/Bookmarks
Save the INspektor as a favorite or bookmark in your web browser and name
the favorite/bookmark after the measuring location
5.1.3.4 Language
When you start the PROFIBUS INspektor, it opens with the German web inter-
face by default. To start with the English web interface, click the national flag
icon and then bookmark the INspektor or save it as a favorite.
Summary of Contents for PB-INspektor
Page 2: ......
Page 32: ...PB INspektor Notices Page 31 13 Notices...
Page 33: ...PB INspektor Notices Page 32...
Page 34: ...PB INspektor Notices Page 33...
Page 35: ......