SNS20-28C Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual    

Page 16

For example, if the actuator is moving towards the Open position with the Fail Switch on the SNS 

Board set for CLOSED, the actuator will STOP, and move to the Closed position if the external 

power should fail.

On the Modulating version, the actuator operates the same as the standard version, except the 

FAIL position is set by the DIP Switches on the Modulating Control Board.

On the standard version, when the incoming power fails, the Blue LED on the SNS Board will turn 

OFF and the Yellow Battery LED will turn on.   Also, the battery status LED (Green or Red) will 

illuminate to show the charge level of the battery.  If the Green LED is on, the battery is at full 

power, but if the Red LED is illuminated, the battery power is low and will need to be charged.  If 

neither the Green or Red LED is lit under battery power, the battery is completely dead and will 

need to be replaced.  In this instance, the Yellow LED will not light either.
On the Modulating version, when the incoming power fails, the Blue LED on the SNS Board will 

turn OFF and one of the battery status lights will turn ON (Green or Red).  There is no Yellow LED 

on the Modulating SNS Board.
There is a battery charge circuit built into the Safe & Secure actuator that will charge the battery 

when the external power is on. After a full 8-10 hour full charge, the Green battery status LED will 

illuminate.  If after 8-10 hours of “on board” charging, the Red LED remains on, then the battery 

needs to be replaced.

If the battery is too low, the actuator will FAIL in place.

The Standard SNS unit will indicate direction of operation (OPEN or CLOSE) by lighting the OPEN 

(Green) or CLOSE (Red) LED.  If, for instance, an OPEN signal is delivered to the actuator, the 

OPEN  Green LED  should  turn on and  the actuator  should  move  to  the OPEN position.    If  that 

Green LED turns on and the motor does not move, then the Motor Fuse has blown.
The Modulating version SNS will indicate OPEN and CLOSE motion  by lighting the Red (OPEN) 

and Green (CLOSE) LEDs on the Modulating Control Board, DMC-102.
If  the  Optional  Heater  and  Thermostat  have  been  installed,  the  Heater  will  operate  when  the 

external  power  supply  is  on.    If  the  external  power  supply  should  fail  and  the actuator runs  on 

battery power, the Heater will 

NOT

be operational.

Please  see  the  photos  in  the  previous  pages  of this  manual  for  the  locations  of  the  above 

mentioned boards and LED locations.

WARNING:  DO NOT CHANGE THE FAIL SWITCH SETTING WITH THE POWER ON!! 

POWER OFF FIRST!

WARNING:  DO NOT CHANGE THE DIP SWITCH SETTING WITH THE POWER ON!! 

POWER OFF FIRST!

Summary of Contents for SNS20

Page 1: ...including but not limited to models with modulating controls timers speed controllers remote off local controls TELEPHONE 1 859 727 7890 TOLL FREE 1 800 662 9424 FAX 1 859 727 4070 SHIPPING ADDRESS 68...

Page 2: ...Y to file a claim for damages STORAGE If the actuators are scheduled for installation at a later date 1 Store off the floor 2 Store in a climate controlled building 3 Store in a clean and dry area FOR...

Page 3: ...t Terminal Strip Screws 3 16 Wide Flat Head Screwdriver Cam Set Screw 5 64 Allen Wrench Mounting Pad Screws 9 16 Socket SUGGESTED MAXIMUM TORQUE VALUES FOR FASTENERS IN LBS SCREW SIZE LOW CARBON STEEL...

Page 4: ...external power and the battery will begin to re charge automatically The actuator will then return to its last position before the power had failed This unit is available as a Standard OPEN CLOSE Actu...

Page 5: ...Operation Maintenance Manual Page 5 MECHANICAL MOUNTING The Safe Secure Actuator can be direct mounted to any valve using the standard ISO 5211 F10 Output See the drawing below for the actuator outpu...

Page 6: ...your local electrical codes Remove the actuator cover by loosening the cover screws and pulling straight up on the cover to complete the wiring and set up Connect the Main Power to the actuator per t...

Page 7: ...IONS FOR STANDARD OPEN CLOSE WIRING DIAGRAM W200628 200628 DESCRIPTION 24VAC 24VDC SNS2000 ACTUATOR STANDARD OPEN CLOSE OPTIONS SHOWN OPTIONS SHOWN OPTIONS SHOWN 2 AUXILIARY SWITCHES MOTOR BRAKE HEATE...

Page 8: ...OR STANDARD OPEN CLOSE WIRING DIAGRAM W200707 200707 DESCRIPTION 12VDC SNS2000 ACTUATOR STANDARD OPEN CLOSE OPTIONS SHOWN OPTIONS SHOWN OPTIONS SHOWN 2 AUXILIARY SWITCHES MOTOR BRAKE HEATER AND THERMO...

Page 9: ...tion Maintenance Manual Page 9 CUSTOMER ELECTRICAL CONNECTIONS FOR MODULATING OPTION WIRING DIAGRAM W200620 200620 DESCRIPTION 115 230VAC ACTUATOR WITH MODULATING CONTROL OPTIONS SHOWN OPTIONS SHOWN O...

Page 10: ...ion Maintenance Manual Page 10 CUSTOMER ELECTRICAL CONNECTIONS FOR MODULATING OPTION WIRING DIAGRAM W200629 200629 DESCRIPTION 24VAC 24VDC ACTUATOR WITH MODULATING CONTROL OPTIONS SHOWN OPTIONS SHOWN...

Page 11: ...eration Maintenance Manual Page 11 CUSTOMER ELECTRICAL CONNECTIONS FOR MODULATING OPTION WIRING DIAGRAM W200630 630 DESCRIPTION 12VDC ACTUATOR WITH MODULATING CONTROL OPTIONS SHOWN OPTIONS SHOWN OPTIO...

Page 12: ...ACTUATOR WILL MOVE TO THE OPEN POSITION WHEN POWER FAILS CLOSE ACTUATOR WILL MOVE TO THE CLOSE POSITION WHEN POWER FAILS WARNING DO NOT switch the FAIL switch while the actuator is moving or while the...

Page 13: ...the valve is opening and closing fully If not the Open and Close CAMs may be adjusted to allow more or less motion in both directions The CAM set screw needs to be loosened to rotate the CAM Re tighte...

Page 14: ...fails the battery will supply power to the Controller Board and run the motor to the selected FAIL position 2 Set the DIP Switch 3 to ON right 4 to OFF left on the DMC 102 Controller Board This will...

Page 15: ...Secure Board should illuminate indicating that the power from the external source is on When the external power fails the Blue LED will turn off and the Yellow Battery LED will illuminate indicating...

Page 16: ...the Modulating SNS Board There is a battery charge circuit built into the Safe Secure actuator that will charge the battery when the external power is on After a full 8 10 hour full charge the Green b...

Page 17: ...eck the entire system and clear any jams or valve binding prior to restarting the system MECHANICAL OVER LOAD Indelac actuators are all designed to withstand stall conditions It is not recommended to...

Page 18: ...ors rated NEMA 4 and 7 take care that the gasket is in place to assure the proper clearance after the cover is secured After securing the cover screws check the clearance between the cover and the bas...

Page 19: ...minal block screws Bad Brake Remove brake hub try to run Modulating Signal Not Present Connect 4 20mA or 0 10vdc Signal to Actuator ACTUATOR WILL NOT OPEN OR CLOSE COMPLETELY Travel limits set wrong R...

Page 20: ...e the Test Switch again 10 If the Battery Green LED on the Safe and Secure Board illuminates the battery is good and is charged 11 If the Red LED is comes back on or is OFF the battery is bad and need...

Page 21: ..._____________________________________________________ _________________________________________________________________ _________________________________________________________________ ______________...

Page 22: ..._____________________________________________________ _________________________________________________________________ _________________________________________________________________ ______________...

Page 23: ..._____________________________________________________ _________________________________________________________________ _________________________________________________________________ ______________...

Page 24: ...nce Manual Page 24 Contact Information Debbie Voges dvoges indelac com 859 727 7890 ext 100 Matt Robinson mrobinson indelac com 859 727 7890 ext 109 Talbot Caywood tcaywood indelac com 859 727 7890 ex...

Reviews: