background image

SNS20-28C Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual    

 

 

 

 

Page 18 

 

 

 

NEMA 7 ENCLOSURE, GENERAL: 

In general, operation and maintenance of a NEMA 7 electric actuator is no different than that of a 

NEMA 4 electric actuator.  However, there are some precautions that must be followed. 

 

1. 

DO NOT

 install in ambient temperatures that exceed 

140 degrees F

2. 

DO NOT

 under any circumstances 

remove the actuator cover

 while in a hazardous location 

when the contacts are still live, this could cause ignition of hazardous atmospheres. 

3. 

DO NOT

 under any circumstances 

use a NEMA 7 electric actuator in a hazardous location 

that does not meet the specifications for which the actuator was designed

.  The actuator is 

clearly tagged with the NEMA classification it was designed for. 

4. 

DO NOT

 

mount, test and calibrate actuator on valve in non-hazardous location. 

5. 

When removing the cover care must be taken not to scratch, scar or deform the flame path 

of the cover or base of the actuator, this will negate the NEMA 7 rating of the enclosure. 

6. 

When replacing the cover on actuators rated NEMA 4 and 7 take care that the gasket is in 

place to assure the proper clearance after the cover is secured.  After securing the cover 

screws check the clearance between the cover and the base - a .002” thick by 1/2” wide 

feeler  gauge may not enter between the two mating faces more than .125”. 

7. 

All  electrical  connections  must  be  to  state  and  local  codes  and  in  accordance  with  the 

 

specifications for which the unit is being used. 

8. 

After de-energizing the NEMA 7 actuator, wait at least 45 minutes before removing the  

 

cover to allow the heater to cool. 

 

*After  proper  installation  the  actuator  will  require  little  or  no  maintenance.  In  the  event 
maintenance is required remove it from the hazardous location before attempting to work on it.  If 
the  actuator  is  in  a  critical  application  and  down  time  is  not  permitted  it  is  advisable  to  have  a 
spare actuator in stock. 

 

 

MANUAL REVISIONS 

JUNE  22, 

2018 

CHANGED EXTERNAL INDICATOR WIRING CONNECTIONS SECTION – CURRENT LOAD USED TO 

BE 5A. NEW RELAYS ON BOARD ARE 2A @ 30VDC AND 0.5A @ 125VAC. 

MAY  13, 

2020 

ADDED  ELECTRICAL  SPECIFICATIONS  FOR  AUXILIARY  SWITCHES/CONTACT  CURRENT; 

UPDATED INDELAC LOGO. 

FEB 

3, 

2021 

“R1”  –

  NEWLY  RE-DESIGNED  SNS2000  SERIES  W/SMALLER  BOARDS  AND  BATTERY.  NEW 

BRACKET DESIGNS AND LAYOUT TO FIT ALL INTO SINGLE “L” ACTUATOR ENCLSOURE.

 

 

 

 
 
 
 
 
 

Summary of Contents for SNS20

Page 1: ...including but not limited to models with modulating controls timers speed controllers remote off local controls TELEPHONE 1 859 727 7890 TOLL FREE 1 800 662 9424 FAX 1 859 727 4070 SHIPPING ADDRESS 68...

Page 2: ...Y to file a claim for damages STORAGE If the actuators are scheduled for installation at a later date 1 Store off the floor 2 Store in a climate controlled building 3 Store in a clean and dry area FOR...

Page 3: ...t Terminal Strip Screws 3 16 Wide Flat Head Screwdriver Cam Set Screw 5 64 Allen Wrench Mounting Pad Screws 9 16 Socket SUGGESTED MAXIMUM TORQUE VALUES FOR FASTENERS IN LBS SCREW SIZE LOW CARBON STEEL...

Page 4: ...external power and the battery will begin to re charge automatically The actuator will then return to its last position before the power had failed This unit is available as a Standard OPEN CLOSE Actu...

Page 5: ...Operation Maintenance Manual Page 5 MECHANICAL MOUNTING The Safe Secure Actuator can be direct mounted to any valve using the standard ISO 5211 F10 Output See the drawing below for the actuator outpu...

Page 6: ...your local electrical codes Remove the actuator cover by loosening the cover screws and pulling straight up on the cover to complete the wiring and set up Connect the Main Power to the actuator per t...

Page 7: ...IONS FOR STANDARD OPEN CLOSE WIRING DIAGRAM W200628 200628 DESCRIPTION 24VAC 24VDC SNS2000 ACTUATOR STANDARD OPEN CLOSE OPTIONS SHOWN OPTIONS SHOWN OPTIONS SHOWN 2 AUXILIARY SWITCHES MOTOR BRAKE HEATE...

Page 8: ...OR STANDARD OPEN CLOSE WIRING DIAGRAM W200707 200707 DESCRIPTION 12VDC SNS2000 ACTUATOR STANDARD OPEN CLOSE OPTIONS SHOWN OPTIONS SHOWN OPTIONS SHOWN 2 AUXILIARY SWITCHES MOTOR BRAKE HEATER AND THERMO...

Page 9: ...tion Maintenance Manual Page 9 CUSTOMER ELECTRICAL CONNECTIONS FOR MODULATING OPTION WIRING DIAGRAM W200620 200620 DESCRIPTION 115 230VAC ACTUATOR WITH MODULATING CONTROL OPTIONS SHOWN OPTIONS SHOWN O...

Page 10: ...ion Maintenance Manual Page 10 CUSTOMER ELECTRICAL CONNECTIONS FOR MODULATING OPTION WIRING DIAGRAM W200629 200629 DESCRIPTION 24VAC 24VDC ACTUATOR WITH MODULATING CONTROL OPTIONS SHOWN OPTIONS SHOWN...

Page 11: ...eration Maintenance Manual Page 11 CUSTOMER ELECTRICAL CONNECTIONS FOR MODULATING OPTION WIRING DIAGRAM W200630 630 DESCRIPTION 12VDC ACTUATOR WITH MODULATING CONTROL OPTIONS SHOWN OPTIONS SHOWN OPTIO...

Page 12: ...ACTUATOR WILL MOVE TO THE OPEN POSITION WHEN POWER FAILS CLOSE ACTUATOR WILL MOVE TO THE CLOSE POSITION WHEN POWER FAILS WARNING DO NOT switch the FAIL switch while the actuator is moving or while the...

Page 13: ...the valve is opening and closing fully If not the Open and Close CAMs may be adjusted to allow more or less motion in both directions The CAM set screw needs to be loosened to rotate the CAM Re tighte...

Page 14: ...fails the battery will supply power to the Controller Board and run the motor to the selected FAIL position 2 Set the DIP Switch 3 to ON right 4 to OFF left on the DMC 102 Controller Board This will...

Page 15: ...Secure Board should illuminate indicating that the power from the external source is on When the external power fails the Blue LED will turn off and the Yellow Battery LED will illuminate indicating...

Page 16: ...the Modulating SNS Board There is a battery charge circuit built into the Safe Secure actuator that will charge the battery when the external power is on After a full 8 10 hour full charge the Green b...

Page 17: ...eck the entire system and clear any jams or valve binding prior to restarting the system MECHANICAL OVER LOAD Indelac actuators are all designed to withstand stall conditions It is not recommended to...

Page 18: ...ors rated NEMA 4 and 7 take care that the gasket is in place to assure the proper clearance after the cover is secured After securing the cover screws check the clearance between the cover and the bas...

Page 19: ...minal block screws Bad Brake Remove brake hub try to run Modulating Signal Not Present Connect 4 20mA or 0 10vdc Signal to Actuator ACTUATOR WILL NOT OPEN OR CLOSE COMPLETELY Travel limits set wrong R...

Page 20: ...e the Test Switch again 10 If the Battery Green LED on the Safe and Secure Board illuminates the battery is good and is charged 11 If the Red LED is comes back on or is OFF the battery is bad and need...

Page 21: ..._____________________________________________________ _________________________________________________________________ _________________________________________________________________ ______________...

Page 22: ..._____________________________________________________ _________________________________________________________________ _________________________________________________________________ ______________...

Page 23: ..._____________________________________________________ _________________________________________________________________ _________________________________________________________________ ______________...

Page 24: ...nce Manual Page 24 Contact Information Debbie Voges dvoges indelac com 859 727 7890 ext 100 Matt Robinson mrobinson indelac com 859 727 7890 ext 109 Talbot Caywood tcaywood indelac com 859 727 7890 ex...

Reviews: