14
Programming:
OP 12 (tnS F)
sets the
Rotation Rate Threshold
for the first filter. If the synchro rotates
slower than this number of
degrees per second
, the measured positions will be accepted as
valid synchro positions, and immediately displayed. Synchro rotations faster than this rate
will be ignored and assumed to be noise-induced aberrations. When
OP 12 (tnS F)
is set to
zero, this filter will be disabled. The maximum value for this parameter is “3600.0”. The
Serial Command Line protocol for this parameter is: “
TURNSF_nnn.nn”
OP 13 (FLttH)
sets the
Turns Rate Threshold
for the averaging filter. If the synchro rotates
slower than this number of
display counts per second
, the second filter will be active and
will average the position readings. Synchro turns faster than this rate will cause the filter to
temporarily stop averaging. When
OP 13 (FLttH)
is set to zero, the averaging filter will be
active at all times. The maximum value for this parameter is “99999”.
Serial Command Line protocol for this parameter is: “
FLTTH_nnn.nn”
OP 14 (FdPtH)
sets the
Depth
of the averaging filter. The higher this number, the greater
number of position samples will be averaged and the longer it will take for the display to be
updated during a position change. When
OP 14 (FdPtH)
is set to zero, this filter will be
disabled. The maximum value for this parameter is “128.0”
The Serial Command Line protocol for this parameter is “
FDPTH_nnn.nn
”.
Loss of Synchro Signal “FA 25” Error Code Reset
The INCON model 1250B has Synchro Signal Loss detection firmware that freezes all
outputs at their last known good positions, and displays an “FA 25” error code when the
synchro signal is lost. The 1250B has an item in the programming menu which allows the
“automatic reset” portion of this feature to be enabled or disabled.
Programming:
In the programming menu, there will be an item: “
OP 53
”, or its Alpha-Numeric equivalent:
“
AUt25
”. If this menu item is selected, the default value will be “
OFF
”, meaning that the
error condition will not automatically reset (the MENU key will need to be pressed to
manually reset the FA 25 error code). This may be changed to “
On
” by pressing the UP or
DOWN key. With this menu item set to “
On
”, the error code will automatically reset as soon
as the synchro signal is restored. Press the ENTER key to store the selected setting.
The serial commands to program this function are “
AUTO25 ON
” and “
AUTO25 OFF
”.
IMPORTANT NOTICE:
When the synchro signal is lost the 1250B will not detect if
synchro rotation occurs. When the synchro signal is restored,
the 1250B may not be reading
the correct position
. All outputs (Analog, Relays, Serial,) which are driven by the displayed
value may also be incorrect.