10
Num-
eric
Alpha-numeric
Protocol
Default
Value:
Programmable
Range:
Function:
OP 25 rL Ht
+16
Any valid tap number
Segmented Mode: Sets high relay limit tap
OP 27 S Pt
0
Any valid tap number
Segmented Mode: Sets present tap position
OP 28 L Pt
0
Any valid tap number
Segmented Mode: Loads present tap
position into memory
OP 29 dSPrL
OFF
On or OFF
Enables display of “r” or “L” in Function
Modes 20 and 21
OP 30 CAL E
OFF
On or OFF
Enables analog output Calibration Mode
OP 31 L CAL
LO
Forces the analog output to its lowest signal
output
OP 32 H
CAL
HI
Forces the analog output to its high scale
signal output
OP 33 d
CAL
- -
Forces the analog output to its mid scale
signal outputs
OP 34 t
CAL
LO then HI
Forces the analog output to alternate between
high and low scale signal outputs
OP 40 LED t
Display LED Test: Turns on all LED’s
OP 41 RS t
RS-232 Echo Test: Re-transmits characters
received through the RS-232 serial port
OP 42 InCAL
CAL
Calibrates synchro input circuitry
OP 43 RLY t
LO then HI
Relay Test: UP and DOWN keys toggle
between LO and HI relays
OP 50 DSPbL
OFF
On or OFF
Causes the display to go blank after 60 sec.
OP 51 RS232
0
0 to 4, 6 and 7
RS-232 Mode: 0=Serial Disabled,
1=Data Logger Mode, 2=Polled Mode,
3=Sampled Mode, 4=Serial Command Mode,
5=Reserved, 6=RS485 MODBUS Mode,
7=Remote Display Driver Mode
OP 53 Aut25
OFF
On or OFF
Auto – Reset after “FA 25” Error (Page 13)
OP 60 Add
-99999 to +99999
Scaled Mode: Add a data point pair to the
Non-Linear Conversion Table (Page 15)
OP 61 dEL
Select a data point pair
from the N.L. Table
Scaled Mode: Delete a data point pair from
the Non-Linear Conversion Table
OP 62 EdIt
Select a data point pair
from the N.L. Table
Scaled Mode: Edit a data point pair in the
Non-Linear Conversion Table
OP 63 dISP
Select a data point pair
from the N.L. Table
Scaled Mode: Display a data point pair in the
Non-Linear Conversion Table
OP 64 LEArn
Scaled Mode: Add a learned data point pair to
the Non-Linear Conversion Table
OP 80 POrt
9600
8
n
1
128
2400, 4800, 9600,
14400, 19200,
28800,38400, 57600,
76800
7 or 8
n, E, O
1 or 2
1 to 255
Sets serial port parameters: (press the UP or
Down key to select a value, press the enter key
to advance to the next parameter)
Baud rate
Word length
Parity (n=none, E=even, O=odd)
Stop bits
Address (for RS-485 Multi-drop)
OP 99 to
OP
to OP
Toggles between Numeric and Alphanumeric
menus