FIREscape System Installation Manual
after approximately 5 s. After the blink, the line has been tested for that address. Remove the safety light and
move to the next base and repeat the above process for each luminaire base.
19.3.3 Double Address Detection
If the EL-KP key pad reports a double address, it means that more than one device is using the same
address.
The luminaires are supplied already set to address 127. You need to program the luminaires with unique
addresses before installing. Failure to do this will result in a double-address situation.
Luminaires with a double address can be located, for example by setting them active or blinking etc. In a
double address situation one address is also missing, for example, has the same address as another unit.