17 EL-2 Technical Specifications
17.1 Control Panel
Control panel model
EL-2
Operating environment[°C]
5 - 40
Operating temperature [°C]*
1
5 - 40
Dimensions (h x w x d) [mm]
347 x 276 x 76
Weight [kg] (includes 7 Ah battery)
8
Luminaire lines
2
Luminaires per line [pcs]
127
Maximum number of luminaires [pcs]
254
Areas
32
Mains transformer
220 VA/35 VAC
Mains AC in minimum 230 VAC -15% [VAC]
195.5
Mains AC in maximum 230 VAC +10% [VAC]
253
Maximum battery capacity [Ah]
7
Battery charge current [A]
0.4
Battery charge voltage [V] @20°C
13.8
Voltage outputs [V]
Minimum voltage
10.0
Maximum voltage
14.5
Normal ripple (from nominal voltage) [mV]
50
Maximum ripple (from nominal voltage) [mV]
50
+12 VDC F3 [A]
0.5
+12 VDC F4 [A]
0.5
Total [A]
0.6
Current consumption motherboard [mA]
60
Standby time [h]
72.5
Outputs
Relay outputs [1A]
2
Serial Ports
PRG
RS232
PRN
RS232
CPN (for keypads)
RS485
SER1+SER2*
2
RS232/485
1
Indoors, 5
–40°C.
2
Requires the EL-EXP serial port expander
Summary of Contents for FIREscape
Page 1: ...Emergency Lighting System INSTALLATION MANUAL ...
Page 22: ...FIREscape System Installation Manual Page 24 of 56 Figure 6 An example of a spur arrangement ...
Page 37: ...FIREscape System Installation Manual Page 39 of 56 Figure 20 EL EXP Connection ...
Page 47: ...FIREscape System Installation Manual Page 49 of 56 Minimum Operating Voltage 7 5 V Figure 28 ...
Page 48: ...Page 50 of 56 FIREscape System Installation Manual Minimum Operating Voltage 8 5 V Figure 29 ...
Page 50: ...Page 52 of 56 FIREscape System Installation Manual Minimum Operating Voltage 7 5 V Figure 31 ...
Page 51: ...FIREscape System Installation Manual Page 53 of 56 Minimum Operating Voltage 8 5 V Figure 32 ...