FIREscape System Installation Manual
Page 40 of 56
15 TCH-B200 Address Programming
Device
T
he address of the FIREscape devices is programmed with the TCH-B200 hand held device programmer. The
programmer requires a 9V battery.
Programming Lead
Socket
BLUE button
Battery Cover
Left GREY button
Right GREY button
Figure 21 - TCH-B200 Device Programmer
15.1 Button Functions
LEFT (grey): Start device, increment address (by 10)
RIGHT (grey): Increment address (by 1), turn off device after programming
RED / BLUE: Program/set address
15.2 Programming
Connect the FIREscape device to the programmer by placing the device onto the
programmer’s metal
terminals.
The FIREscape device has an alignment ‘rib’ – this should be at approximately 6 on a clock- face.
Twist the FIREscape device clockwise until it locks in place.
Press t
he left button on the programmer. The programmer reads the FIREscape device’s address and
this is displayed on the numeric LEDs. The factory preset address is 127.
Set the address with the left (10s) and right (units) buttons.
Set the displayed address into the FIREscape device by pressing the red button. When programming is
successful, the numeric LEDs will blink.
The programmer can be turned off with the right button.
NOTE: The programmer will turn off by itself approximately 15s after last key press.
NOTE: The FIREscape device is set to power save mode after programming. The load of a full battery will last
for approximately 2 months. The unit wakes up from the power save mode when line voltage is
connected or the battery is removed and reinserted.
Summary of Contents for FIREscape
Page 1: ...Emergency Lighting System INSTALLATION MANUAL ...
Page 22: ...FIREscape System Installation Manual Page 24 of 56 Figure 6 An example of a spur arrangement ...
Page 37: ...FIREscape System Installation Manual Page 39 of 56 Figure 20 EL EXP Connection ...
Page 47: ...FIREscape System Installation Manual Page 49 of 56 Minimum Operating Voltage 7 5 V Figure 28 ...
Page 48: ...Page 50 of 56 FIREscape System Installation Manual Minimum Operating Voltage 8 5 V Figure 29 ...
Page 50: ...Page 52 of 56 FIREscape System Installation Manual Minimum Operating Voltage 7 5 V Figure 31 ...
Page 51: ...FIREscape System Installation Manual Page 53 of 56 Minimum Operating Voltage 8 5 V Figure 32 ...