FIREscape System Installation Manual
Page 20 of 56
9
RS-232 Connectors
9.1
PC Interface, PRG
Figure 18 - PC Interface Cable Connection
9.2
EL-ISOL (RS-232 Isolator)
When connecting the control panel’s RS-232 outputs to devices which are earthed, such as PC/printer, the
connection may cause interference due to earth leakage. This is because the negative (-) pin of the RS-232
connector is usually connected to shield ground.
The connection must be arranged through a local modem or the EL-ISOL unit if the RS-232 device and the
control panel are not connected to the same power supply group. Usually this means the same room. In no
instance should the cable length without local modem exceed 20 m.
PC SERIAL
PORT