background image

© Copyright 2010 IMS Company. All rights reserved.

An ISO 9001:2008 Registered Quality Company

4

FOREWORD

The intent of this manual is to serve as a guide fo placing your
temperature control unit in service and operating and 
maintaining it properly. This manual is supplemented as
required to accommodate any special items that may have
been provided for a specific application. The written information
contained in this manual, as well as various drawings, are
intended to be general in nature. The schematics included in
this manual are typical only. Actual schematics are included in
the electrical enclosure of the unit and should be referred to for
troubleshooting and servicing of the unit. Additional copies of
drawings are available upon request. We strive to maintain an
accurate record of all equipment during the course of its useful
life. While every effort is made to standardize the design 
features of these units, the various options may make it 
necessary to rearrange some of the components; therefore,
some of the general drawings in this manual may differ from
your specific unit. 

Specific references to current applicable codes, ordinances,
and other local laws pertaining to the use and operation of this
equipment are avoided due to their ever-changing nature. There
is no substitute for common sense and good operating 
practices when placing any mechanical equipment into 
operation. We encourage all personnel to familiarize themselves
with this manual's contents. Failure to do so may unnecessarily
prolong equipment down time.

It is recommended that good piping practices are followed and
that the information in this manual is adhered to. We cannot be
held responsible for liabilities created by substandard piping
methods and installation practices external to the unit. 

We trust your equipment will have a long and useful life. If you
should have any questions, please contact our Tech Service
Department specifying the serial number and model number of
the unit as indicated on the nameplate.

Note: RD and RE Series units are nearly identical in internal
function and design, The RD unit however, features a self
diagnostic temperature control microprocessor panel, while
the RE unit uses a simple plug-in type controller. Applicable
control, operation, and start-up differences are noted within
this manual.

Installation

Receiving Inspection

Each unit is skid mounted and boxed or crated to protect it 
during shipping.  Before accepting delivery, check the box or
crate for visible damage.  If damage is evident, it should be
properly documented on the delivery receipt and the box or
crate should be immediately removed to allow for detailed
inspection of the unit.  Check for broken water lines, damaged

controls, or any other major component torn loose from its
mounting point.  Any sign of damage should be recorded and a
claim filed immediately with the shipping company.  In order to
expedite payment for damages it is important to record and
document damage.  An excellent way to do this is by taking 
pictures.  Our Tech Service Department will provide assistance
with the preparation and filing of your claims, including 
arranging for an estimate and quotation on repairs.

Rigging, Handling, and Locating Equipment

The units have a steel base platform and casters for easy 
positioning. For lifting proper rigging methods must be followed
to prevent damage to components.  Avoid impact loading
caused by sudden jerking when lifting or lowering the unit.  
Use pads where abrasive surface contact is anticipated.

The unit is designed for indoor use.  If it is necessary to store
the unit in an unheated area when not in use, be sure that all
water is drained or that an adequate amount of antifreeze is
added to prevent freeze-up of the unit.  A primary concern when
designing your unit was serviceability, therefore, the unit should
be located in an accessible area.

Electrical Power 

All wiring must comply with local codes and the National Electric
Code.  Minimum circuit ampacities and other unit electrical data
are on the unit nameplate and are shown in the Electrical
Specification section at the back of this manual.  A specific elec-
trical schematic is shipped with the unit.  Measure each leg of
the main power supply voltage at the main power source.
Voltage must be within the voltage utilization range given in
Table 1.

Table 1 - Voltage Utilization Range

              

Rated Voltage                   Utilization Range

230

208 to 254

460

414 to 506

575

516 to 633

If the measured voltage on any leg is not within the specified
range, notify the supplier and correct before operating the unit.
Voltage imbalance must not exceed two percent.  Excessive
voltage imbalance between the phases of a three-phase system
can cause motors to overheat and eventually fail.  Voltage
imbalance is determined using the following calculations:

% Imbalance = (V

avg

– V

x

) x 100 / V

avg

V

avg

= (V

1

+ V

2

+ V

3

) / 3

V

x

= phase with greatest difference from V

avg

Summary of Contents for Hydra Pressurized

Page 1: ...Company Hydra Pressurized Open Loop Mold Temperature Controllers INSTRUCTION MANUAL January 2007 IMS Company 10373 Stafford Road Chagrin Falls OH 44023 5296 Telephone 440 543 1615 Fax 440 543 1069 Email sales imscompany com Website www imscompany com Hydra is a trademark of IMS Company ...

Page 2: ... 8 Purge 8 Alarm Silence 8 Lower Set Point Temperature 8 Raise Set Point Temperature 8 Low Pressure 8 High Temp Safety 8 Pump Motor Overload 8 Over Set Point 9 Under Set Point 9 Pump On 9 Heat 9 Cool 9 Vent 9 Probe Fault 9 Changing Temperature Display Scale 9 Seal Saver 10 Auto Tune 10 Diagnostic Error Codes 11 Table 3 Diagnostic Error Codes 11 CONTROL OPTIONS 12 Return Water Temperature Display 1...

Page 3: ...r Modulating Valve 13 Pressure Switch 13 Pressure Relief Valve 14 STANDARD OPTIONS 14 Stacking Bracket Kit RA RB series 14 Mold Water Purge 14 Crash Cool 14 PREVENTIVE MAINTENANCE 14 Once a Week 15 Once a Month 15 TROUBLESHOOTING 16 CHARTS PUMP CURVES 17 Table 5 Single Zone Unit Electrical Specifications 17 Table 6 Dual Zone Unit Electrical Specifications 18 Figure 1 RA RAD RB RBD Series Pump Curv...

Page 4: ...ing Inspection Each unit is skid mounted and boxed or crated to protect it during shipping Before accepting delivery check the box or crate for visible damage If damage is evident it should be properly documented on the delivery receipt and the box or crate should be immediately removed to allow for detailed inspection of the unit Check for broken water lines damaged controls or any other major co...

Page 5: ...s well as quick disconnect fittings that offer high resistance to water flow When manifolds are required for water distribution they should be installed as close to the point of use as possible The return line should be the same size as the supply line In addition to the process water connections the unit requires a cooling water supply and return connection We recommend shut off valves at each ma...

Page 6: ...5 PSI 1 75 Bar and 50 PSI 3 5 Bar If the supply cooling water pressure is higher than 50 PSI 3 5 Bar a pressure regulating valve should be installed on the supply line to the temperature control unit For assistance in installing a pressure regulating valve please contact our Tech Service Department 6 Turn on the control power by pressing the Power button located on the control panel of the unit Th...

Page 7: ...ol Fault Logic Alarm Manual Remote Fault Alarm Pump Shut Heater Shut Unit Shut Reset Reset Alarm Indication Off Off Off Required 1 Required 2 Activated 3 Low Pressure LED Yes Yes Yes No No Yes High Temperature Safety LED Yes Yes Yes Yes No Yes Pump Motor Overload LED Yes Yes Yes Yes Yes Yes Over Set Point LED No No No No No Yes Under Set Point LED No No No No No Yes Probe Fault LED Yes Yes Yes Yes...

Page 8: ...epressing the Alarm Silence button will open the contact that was closed when the alarm occurred The contact will not close again until the alarm has been reset and a subsequent alarm has been triggered Lower Set Point Temperature Depressing and then releasing the Lower Set Point Temperature button will decrease the set point temperature by 1 F or 1 C If the Lower Set Point Temperature button is h...

Page 9: ...ted while the microprocessor is performing an Auto Vent sequence This sequence is performed each time the Start button is pressed to energize the unit unless the temperature is above 150 F The Auto Vent sequence opens the cooling solenoid or modulating valve for 30 seconds to vent air from the mold circuit Then the valve is kept open and the pump is energized for an additional 30 seconds The Vent ...

Page 10: ...re a particular application may require additional fine tuning of the control parameters To make this procedure as simple as possible this controller has been equipped with an Auto Tune function The Auto Tune function is designed to automatically select the best control parameters based upon the particular system that the unit is connected to At the factory certain parameters have been limited so ...

Page 11: ...tact Manufacturer for repair or replacement configuration change or invalid 111 Fixed parameter associated Controller requires servicing Contact Manufacturer for repair or replacement with range invalid 112 Setpoint out of temperature range Controller requires servicing Contact Manufacturer for repair or replacement 113 RAM hardware failure Controller requires servicing Contact Manufacturer for re...

Page 12: ...connect the controller and the unit All control functions are available to the operator at the location of the remote panel and no control functions are available at the location of the unit SPI Communications This option provides an RS 485 communication port located below the control panel on the front of the unit The serial communications will be multi drop half duplex SPI 3 01 compatible and wi...

Page 13: ...st not be defeated A small pump seal flush line is provided to continuously flush the pump seal of dirt and debris Construction Pump Assembly The centrifugal close coupled pump features a specially designed cast volute to eliminate fittings and provide easy connection to the heater and or mixing tubes The pump volute is constructed of cast iron The through 2 HP pumps have stainless steel impellers...

Page 14: ...ss the Stop button This leaves the unit on but puts the microprocessor in an inactive mode The Power button light should still be illuminated 2 Close the valve on the Cooling Water In line to shut off the supply of water 3 Connect the compressed air supply to the ball valve on the back of the unit 4 Open the ball valve to let the compressed air into the mold circuit 5 Press the Purge button on the...

Page 15: ...ay from the normal operating pressure 3 Check the pump for leaks in the seal area Replace pump seal if necessary Repeat items 1 through 3 listed above and continue with the following Once a Month 4 With the main disconnect shut off check the condition of electrical connections at all contactors starters and con trols Check for loose or frayed wires 5 Check the incoming voltage to make sure it is w...

Page 16: ...ctioning correctly and replace any defective components Microprocessor controller failure Replace controller Failure of thermocouple Replace thermocouple Failure of heater Replace heater Failure of heater contactor Replace heater contactor Unable to cool properly Cooling water supply is not Check to make sure the cooling water supply is of sufficient sufficient temperature volume and pressure for ...

Page 17: ...20 2 9 24 9 22 6 11 3 9 0 1 2 6 6 6 0 3 0 2 4 69 4 63 0 31 8 25 4 RA183A 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA183B 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA1850 2 9 24 9 22 6 11 3 9 0 1 5 16 5 15 0 7 5 6 0 79 3 72 0 36 3 29 0 RA1875 2 9 24 9 22 6 11 3 9 0 1 7 5 24 2 22 0 11 0 8 8 87 0 79 0 39 8 31 8 RA2408 2 9 24 9 22 6 11 3 9 0 1 0 75 3 7 3 4 1 ...

Page 18: ...1810 4 9 24 9 22 6 11 3 9 0 2 1 3 7 3 4 1 7 1 4 132 4 120 3 60 4 48 3 RAD1820 4 9 24 9 22 6 11 3 9 0 2 2 6 6 6 0 3 0 2 4 138 2 125 5 63 0 50 3 RAD183A 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD183B 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD1850 4 9 24 9 22 6 11 3 9 0 2 5 16 5 15 0 7 5 6 0 158 0 143 5 72 0 57 5 RAD1875 4 9 24 9 22 6 11 3 9 0 2 7 5...

Page 19: ...e prepared a custom set of drawings for your unit and placed them inside the control panel prior to shipment Please refer to these drawings when troubleshooting servicing and installing the unit If you cannot find these drawings or wish to have additional copies please contact our Tech Service Department and reference the serial number of your unit ...

Page 20: ... the equipment and or system has been subject to misuse negligence or operation in excess of recommended limits including freezing or which has been altered and or repaired without express factory authorization If equipment is installed in hostile environments unless such conditions were specified at the time of purchase or the serial number has been removed or defaced this warranty shall not appl...

Reviews: