background image

11. Open the control panel and switch DIP switch #3 to the off

position and close control panel.

12. Reconnect main power.

The unit is now set and will remain set with the selected 
temperature scale until the above steps are repeated.

Seal Saver™ 

Each unit has a Seal Saver program built into the controller that
can be activated when turning off the unit. This software is
designed to reduce water temperature before the unit shuts off
to extend the life of the seal. Here is how to activate this feature:

1. Press the Start button and while holding in the Start button,

momentarily press the Stop button. Both keys can then be
released.

2. The solenoid valve will remain open, bringing cool water to

the unit. This will continue until either the temperature of the
water reaches 90°F (32°C) or for 120 seconds, whichever
occurs first. 

3. Once activated, the Stop LED will flash and the Set Point 

display will toggle between the actual set point and the 90°F
(32°C) Seal Saver cool down value. The actual set point can
be changed at this time if desired.

4. When the water reaches 90°F (32°C) or 120 seconds have

elapsed, the control will enter the normal stop mode. The
Stop LED will discontinue flashing and the Set Point display
will revert to the actual set point value.

5. Seal Saver will not activate if the Process Temperature is less

than 90°F (32°C). If the Stop button is pressed at any point
during Seal Saver operation, the unit will stop all operation. If
the Start button is pressed at any point during Seal Saver
operation, the unit will return to normal running operation, at
the original set point.

6. Seal Saver will not activate under the following circum-

stances: Auto Tune is running, the first 60 seconds of 
operation, or if the set point is under 90°F (32°C).

This process must be repeated every time you wish to activate
Seal Saver. To deactivate Seal Saver, change the configuration
DIP switch #2 to the "Off" position. 

Auto Tune

In most cases, the standard program entered into the 
microprocessor controller at the factory provides excellent 
temperature control; however, there are occasions where a 
particular application may require additional fine-tuning of the
control parameters. To make this procedure as simple as 
possible, this controller has been equipped with an Auto Tune
function. 

The Auto Tune function is designed to automatically select the
best control parameters based upon the particular system that
the unit is connected to. At the factory, certain parameters have
been limited so that the Auto Tune program cannot select val-
ues that could cause damage to certain components. The fol-
lowing procedure should be followed if there is a need for the
Auto Tune program to be run. 

Note: Do not use the Auto Tune function until it is verified
that the unit is operating normally and there is not a failure
of a component. Make sure that the lines are properly sized
and there is sufficient incoming water pressure. If the 
application is for heating, other changes are needed and
you should contact our Tech Service Department. 

1. Make sure that the flow and pressure through the process are

set at the proper levels for that particular installation. Poor
temperature control accuracy is often caused by low coolant
flow through the process.

2. The Auto Tune program must be run with no heat load being

added by the process. The program may take up to 30 
minutes to run.

3. To activate Auto Tune, change DIP switch #8 to the "On" 

position.

4. The unit must be in the stop mode and the process 

temperature must be at ambient.

5. Hold the Start button down for 7 seconds.

6. The Auto Tune program will abort under these conditions:

a.

Pressing the Stop button while Auto Tune is in progress.

b.

If the temperature difference between the process value
and the set point is less than 8°F (4.5°C ) after the vent 
sequence.

c.

The software is unable to obtain a good approximation 
of the PID parameters after 30 minutes has elapsed. 
This condition can occur if the control loop was dis
turbed by external elements or if the control elements 
are faulty. 

If any of the above conditions occur, the previous control 
parameters will be restored. 

7. To abort the Auto Tune program at any time, press the Stop

button, and the previous control parameters will be restored.

© Copyright 2010 IMS Company. All rights reserved.

An ISO 9001:2008 Registered Quality Company

10

Seal Saver™ 

is a trademark of Thermal Care

Summary of Contents for Hydra Pressurized

Page 1: ...Company Hydra Pressurized Open Loop Mold Temperature Controllers INSTRUCTION MANUAL January 2007 IMS Company 10373 Stafford Road Chagrin Falls OH 44023 5296 Telephone 440 543 1615 Fax 440 543 1069 Email sales imscompany com Website www imscompany com Hydra is a trademark of IMS Company ...

Page 2: ... 8 Purge 8 Alarm Silence 8 Lower Set Point Temperature 8 Raise Set Point Temperature 8 Low Pressure 8 High Temp Safety 8 Pump Motor Overload 8 Over Set Point 9 Under Set Point 9 Pump On 9 Heat 9 Cool 9 Vent 9 Probe Fault 9 Changing Temperature Display Scale 9 Seal Saver 10 Auto Tune 10 Diagnostic Error Codes 11 Table 3 Diagnostic Error Codes 11 CONTROL OPTIONS 12 Return Water Temperature Display 1...

Page 3: ...r Modulating Valve 13 Pressure Switch 13 Pressure Relief Valve 14 STANDARD OPTIONS 14 Stacking Bracket Kit RA RB series 14 Mold Water Purge 14 Crash Cool 14 PREVENTIVE MAINTENANCE 14 Once a Week 15 Once a Month 15 TROUBLESHOOTING 16 CHARTS PUMP CURVES 17 Table 5 Single Zone Unit Electrical Specifications 17 Table 6 Dual Zone Unit Electrical Specifications 18 Figure 1 RA RAD RB RBD Series Pump Curv...

Page 4: ...ing Inspection Each unit is skid mounted and boxed or crated to protect it during shipping Before accepting delivery check the box or crate for visible damage If damage is evident it should be properly documented on the delivery receipt and the box or crate should be immediately removed to allow for detailed inspection of the unit Check for broken water lines damaged controls or any other major co...

Page 5: ...s well as quick disconnect fittings that offer high resistance to water flow When manifolds are required for water distribution they should be installed as close to the point of use as possible The return line should be the same size as the supply line In addition to the process water connections the unit requires a cooling water supply and return connection We recommend shut off valves at each ma...

Page 6: ...5 PSI 1 75 Bar and 50 PSI 3 5 Bar If the supply cooling water pressure is higher than 50 PSI 3 5 Bar a pressure regulating valve should be installed on the supply line to the temperature control unit For assistance in installing a pressure regulating valve please contact our Tech Service Department 6 Turn on the control power by pressing the Power button located on the control panel of the unit Th...

Page 7: ...ol Fault Logic Alarm Manual Remote Fault Alarm Pump Shut Heater Shut Unit Shut Reset Reset Alarm Indication Off Off Off Required 1 Required 2 Activated 3 Low Pressure LED Yes Yes Yes No No Yes High Temperature Safety LED Yes Yes Yes Yes No Yes Pump Motor Overload LED Yes Yes Yes Yes Yes Yes Over Set Point LED No No No No No Yes Under Set Point LED No No No No No Yes Probe Fault LED Yes Yes Yes Yes...

Page 8: ...epressing the Alarm Silence button will open the contact that was closed when the alarm occurred The contact will not close again until the alarm has been reset and a subsequent alarm has been triggered Lower Set Point Temperature Depressing and then releasing the Lower Set Point Temperature button will decrease the set point temperature by 1 F or 1 C If the Lower Set Point Temperature button is h...

Page 9: ...ted while the microprocessor is performing an Auto Vent sequence This sequence is performed each time the Start button is pressed to energize the unit unless the temperature is above 150 F The Auto Vent sequence opens the cooling solenoid or modulating valve for 30 seconds to vent air from the mold circuit Then the valve is kept open and the pump is energized for an additional 30 seconds The Vent ...

Page 10: ...re a particular application may require additional fine tuning of the control parameters To make this procedure as simple as possible this controller has been equipped with an Auto Tune function The Auto Tune function is designed to automatically select the best control parameters based upon the particular system that the unit is connected to At the factory certain parameters have been limited so ...

Page 11: ...tact Manufacturer for repair or replacement configuration change or invalid 111 Fixed parameter associated Controller requires servicing Contact Manufacturer for repair or replacement with range invalid 112 Setpoint out of temperature range Controller requires servicing Contact Manufacturer for repair or replacement 113 RAM hardware failure Controller requires servicing Contact Manufacturer for re...

Page 12: ...connect the controller and the unit All control functions are available to the operator at the location of the remote panel and no control functions are available at the location of the unit SPI Communications This option provides an RS 485 communication port located below the control panel on the front of the unit The serial communications will be multi drop half duplex SPI 3 01 compatible and wi...

Page 13: ...st not be defeated A small pump seal flush line is provided to continuously flush the pump seal of dirt and debris Construction Pump Assembly The centrifugal close coupled pump features a specially designed cast volute to eliminate fittings and provide easy connection to the heater and or mixing tubes The pump volute is constructed of cast iron The through 2 HP pumps have stainless steel impellers...

Page 14: ...ss the Stop button This leaves the unit on but puts the microprocessor in an inactive mode The Power button light should still be illuminated 2 Close the valve on the Cooling Water In line to shut off the supply of water 3 Connect the compressed air supply to the ball valve on the back of the unit 4 Open the ball valve to let the compressed air into the mold circuit 5 Press the Purge button on the...

Page 15: ...ay from the normal operating pressure 3 Check the pump for leaks in the seal area Replace pump seal if necessary Repeat items 1 through 3 listed above and continue with the following Once a Month 4 With the main disconnect shut off check the condition of electrical connections at all contactors starters and con trols Check for loose or frayed wires 5 Check the incoming voltage to make sure it is w...

Page 16: ...ctioning correctly and replace any defective components Microprocessor controller failure Replace controller Failure of thermocouple Replace thermocouple Failure of heater Replace heater Failure of heater contactor Replace heater contactor Unable to cool properly Cooling water supply is not Check to make sure the cooling water supply is of sufficient sufficient temperature volume and pressure for ...

Page 17: ...20 2 9 24 9 22 6 11 3 9 0 1 2 6 6 6 0 3 0 2 4 69 4 63 0 31 8 25 4 RA183A 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA183B 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA1850 2 9 24 9 22 6 11 3 9 0 1 5 16 5 15 0 7 5 6 0 79 3 72 0 36 3 29 0 RA1875 2 9 24 9 22 6 11 3 9 0 1 7 5 24 2 22 0 11 0 8 8 87 0 79 0 39 8 31 8 RA2408 2 9 24 9 22 6 11 3 9 0 1 0 75 3 7 3 4 1 ...

Page 18: ...1810 4 9 24 9 22 6 11 3 9 0 2 1 3 7 3 4 1 7 1 4 132 4 120 3 60 4 48 3 RAD1820 4 9 24 9 22 6 11 3 9 0 2 2 6 6 6 0 3 0 2 4 138 2 125 5 63 0 50 3 RAD183A 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD183B 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD1850 4 9 24 9 22 6 11 3 9 0 2 5 16 5 15 0 7 5 6 0 158 0 143 5 72 0 57 5 RAD1875 4 9 24 9 22 6 11 3 9 0 2 7 5...

Page 19: ...e prepared a custom set of drawings for your unit and placed them inside the control panel prior to shipment Please refer to these drawings when troubleshooting servicing and installing the unit If you cannot find these drawings or wish to have additional copies please contact our Tech Service Department and reference the serial number of your unit ...

Page 20: ... the equipment and or system has been subject to misuse negligence or operation in excess of recommended limits including freezing or which has been altered and or repaired without express factory authorization If equipment is installed in hostile environments unless such conditions were specified at the time of purchase or the serial number has been removed or defaced this warranty shall not appl...

Reviews: