9-5
Specifications
9
Item
Detail specifications
PID control
This function can control flowrate, pressure, etc. with analog feedback signal|
The reference and feedback values are displayed in %.
Reference signal
Keypad operation key and key.: 0.0 to 100%
Voltage input (Terminal 12)
: 0 to 10Vdc
Current input (Terminal C1)
: 4 to 20mAdc
Multistep frequency setting
: Setting freq./Max. freq.x100%
RS485
: Setting freq./Max. freq.x100%
Feedback signal
Terminal 12 (0 to +10Vdc or +10 to 0Vdc)
Terminal C1(4 to 20mAdc or 20 to 4mAdc)
Second motor’s
The V/f pattern of the second motor can be internally set for selection by means
setting
of an external signal.
The constant of the second motor can be internally set for selection by means of
an external signal.
The electronic thermal overload relay of the second motor can be internally set
for selection by means of an external signal.
Energy saving
Weak magnetic flux can be set for small loads for operation with an increased
operation
motor efficiency.
During
The keypad panel can be extended. (Optional 2m extension cable is available.)
operation/stop
7-segment LED display items
• Set frequency
• Output frequency
• PID setting/feedback value
• Output current
• Motor r/min
• Output voltage
• Line speed
(A soft filter is provided to attenuate the fluctuation in the displayed value.)
A charge lamp indicates power supply.
When setting
The function code and data code are displayed.
When tripping
[The cause of tripping is displayed.]
• OC1 (overcurrent: during acceleration)
• OC2 (overcurrent: during deceleration)
• OC3 (overcurrent: during constant speed operation)
• OU1 (overvoltage: during acceleration)
• OU2 (overvoltage: during deceleration)
• OU3 (overvoltage: during constant speed operation)
• LU (undervoltage)
• Lin (input phase loss) (for 3-phase inverter)
• dbH (external damping resistor overheat (thermal overload relay))
• OH1 (overheat: heat sink)
• OH2 (overheat: external thermal overload relay)
• OL1 (overload: motor 1)
• OL2 (overload: motor 2)
• OLU (overload: inverter)
• Er1 (memory error)
• Er2 (keypad panel communication error)
• Er3 (CPU error)
• Er4 (option error)
• Er5 (option error)
• Er7 (output wiring error) (impedance imbalance)
• Er8 (RS485 communication error)
During operation,
The latest four records of trip history are stored and displayed.
when tripping
Control
Display
V
V
Summary of Contents for VXSM150-1
Page 3: ......
Page 41: ...5 12 Selecting Functions 5 Frequency setting block diagram ...
Page 45: ...5 16 Selecting Functions 5 Note The chain line indicates the motor speed ...
Page 71: ...7 1 Troubleshooting 7 7 Troubleshooting 7 1 When Protective Function Activates 1 Overcurrent ...
Page 72: ...Troubleshooting 7 2 7 2 Overvoltage 3 Undervoltage ...