Selecting Functions
5-3
5
Min.
Factory
Name
Setting range
unit
setting
F29
FMA and FMP
0: Analog output (FMA)
terminals
1: Pulse output (FMP)1
1
0
X
0
(Select)
F30
FMA
(Voltage adjust)
0 to 200%
1%
100
0
F31
(Function)
0:Output frequency 1 (before slip
compensation)
1:Output frequency 2 (after slip
compensation)
2:Output current
3:Output voltage
1
0
0
4:Output torque
5:Load factor
6:Input power
7:PID feedback value
8:DC link circuit voltage
F33
FMP
(Pulse rate)
300 to 6000p/s (Pulse count at 100%)
1p/s
1440
0
F34
(Voltage adjustment)
0%, 1 to 200%
1%
0
0
F35
(Function)
0 to 8 (Same as F31)
1
0
0
F36
30Ry operation mode 0: Excited when tripping
1: Excited during regular operation
1
0
X
0
F40
Torque limiter 1
20 to 200%
(Driving)
999: Inactive
1%
180
0
F41
(Braking)
0%: Automatic deceleration control
20 to 200%
999: Inactive
1%
150
0
F42
Torque vector
0: Inactive
control 1
1: Active
1
0
X
0
Description of change during operation
: The data changed by the or key takes
effect on the inverter operation. However,
press the key to store the new data.
V
V
Function code
Change during
operation
RS485 Data format
: Press the or key to change the data.
The new data takes effect after the key is
pressed to store the data.
X : The data can be changed only while the
inverter is stopped.
V
V
FUNC
DATA
FUNC
DATA
User setting
Summary of Contents for VXSM150-1
Page 3: ......
Page 41: ...5 12 Selecting Functions 5 Frequency setting block diagram ...
Page 45: ...5 16 Selecting Functions 5 Note The chain line indicates the motor speed ...
Page 71: ...7 1 Troubleshooting 7 7 Troubleshooting 7 1 When Protective Function Activates 1 Overcurrent ...
Page 72: ...Troubleshooting 7 2 7 2 Overvoltage 3 Undervoltage ...