5.2 Main setting mode
Character
Name, Function, Setting range
Default value
SV1
•
Sets SV1.
•
Setting range: SV low limit to SV high limit
0
SV2
•
Sets SV2.
•
Available only when the option SM is applied.
•
Setting range: SV low limit to SV high limit
0
5.3 Sub setting mode
Character
Name, Function, Setting range
Default value
AT setting/Auto-reset setting
•
Designates auto-tuning Performance or auto-reset Performance.
•
If the auto-tuning is cancelled during the process, P, I and D
values revert to the former value at which AT is performed.
•
When auto-tuning has not finished after 4 hours, it is cancelled
automatically.
•
Auto-reset is cancelled in approximately 4 minutes.
OUT1 proportional band setting
•
Sets the proportional band for OUT1.
•
OUT1 becomes ON/OFF action when set to 0 or 0.0
•
0 to 1000 (2000 ), 0.0 to 999.9 ( ) or 0.0 to 100.0%
10
OUT2 proportional band setting
•
Sets the proportional band for OUT2.
•
OUT2 becomes ON/OFF action when OUT1 proportional band
is set to 0 or 0.0.
•
Not available if option DT is not added or if OUT1 is ON/OFF action.
•
0.0 to 10.0 times (multiplying factor to OUT1 proportional band)
1.0 times
Integral time setting
•
Sets integral time for OUT1.
•
Setting the value to 0 disables the function.
•
Not available when OUT1 is ON/OFF action.
•
Auto-reset can be performed when PD action (I=0).
•
Setting range: 0 to 1000 seconds
200 seconds
Derivative time setting
•
Sets derivative time for OUT1.
•
Setting the value to 0 disables the function.
•
Not available when OUT1 is ON/OFF action.
•
Setting range: 0 to 300 seconds
50 seconds
ARW setting
•
Sets ARW for OUT1.
•
Available only when PID is the control action.
•
Setting range: 0 to 100%
50%
OUT1 proportional cycle setting
•
Sets proportional cycle for OUT1.
•
Not available for DC current output type or when OUT1 is
ON/OFF action.
•
Setting range: 1 to 120 seconds
30 seconds or
3 seconds
OUT2 proportional cycle setting
•
Sets proportional cycle for OUT2.
•
Not available if the option DT is not applied or when OUT2 is
ON/OFF action.
•
Setting range: 1 to 120 seconds
3 seconds
A1 setting
•
Sets action point for A1 output.
•
Not available if No alarm action is selected in A1 action selection
•
Refer to (Table 5.3-1).
0
A2 setting
•
Sets action point for A2 output.
•
Not available if option A2 is not applied or if No alarm action is
selected in A2 action selection.
•
Refer to (Table 5.3-1).
0
. ,
XX.X
indicated
in turn
Heater burnout alarm setting
•
Sets the heater current value for Heater burnout alarm.
•
Self-holding is not available for the alarm output.
•
Available only when the option W is added.
•
Rating 5A : 0.0 to 5.0A
Rating 10A: 0.0 to 10.0A
Rating 20A: 0.0 to 20.0A Rating 50A: 0.0 to 50.0A
0.0A
7