IMO TP40A Instruction Manual Download Page 7

5.2 Main setting mode 

Character 

Name, Function, Setting range 

Default value 

 

SV1 

• 

Sets SV1. 

 Setting range: SV low limit to SV high limit 

0  

 

SV2 

• 

Sets SV2. 

• 

Available only when the option SM is applied. 

• 

Setting range: SV low limit to SV high limit

 

0  

5.3 Sub setting mode 

Character 

Name, Function, Setting range 

Default value 

 

 

 

AT setting/Auto-reset setting 

 Designates auto-tuning Performance or auto-reset Performance. 

 If the auto-tuning is cancelled during the process, P, I and D   

values revert to the former value at which AT is performed. 

• 

When auto-tuning has not finished after 4 hours, it is cancelled 

automatically. 

 Auto-reset is cancelled in approximately 4 minutes. 

 

 

OUT1 proportional band setting 

 Sets the proportional band for OUT1. 

 OUT1 becomes ON/OFF action when set to 0 or 0.0 

 

0 to 1000 (2000 ), 0.0 to 999.9 ( ) or 0.0 to 100.0% 

10  

 

OUT2 proportional band setting 

 Sets the proportional band for OUT2. 

 OUT2 becomes ON/OFF action when OUT1 proportional band 

is set to 0 or 0.0. 

• 

Not available if option DT is not added or if OUT1 is ON/OFF action. 

 0.0 to 10.0 times (multiplying factor to OUT1 proportional band)   

1.0 times 

 

Integral time setting 

 Sets integral time for OUT1. 

 Setting the value to 0 disables the function. 

• 

Not available when OUT1 is ON/OFF action. 

 Auto-reset can be performed when PD action (I=0). 

 Setting range: 0 to 1000 seconds 

200 seconds 

 

Derivative time setting 

 Sets derivative time for OUT1. 

 Setting the value to 0 disables the function. 

• 

Not available when OUT1 is ON/OFF action. 

 Setting range: 0 to 300 seconds 

50 seconds 

 

ARW setting 

 Sets ARW for OUT1. 

• 

Available only when PID is the control action.   

 Setting range: 0 to 100% 

50% 

     

OUT1 proportional cycle setting 

 Sets proportional cycle for OUT1. 

• 

Not available for DC current output type or when OUT1 is   

ON/OFF action. 

 Setting range: 1 to 120 seconds 

30 seconds or 
3 seconds 

 

OUT2 proportional cycle setting 

 Sets proportional cycle for OUT2. 

• 

Not available if the option DT is not applied or when OUT2 is 

ON/OFF action. 

 

Setting range: 1 to 120 seconds

 

3 seconds 

 

A1 setting 

 Sets action point for A1 output. 

• 

Not available if No alarm action is selected in A1 action selection 

 Refer to (Table 5.3-1). 

0  

 

A2 setting 

• 

Sets action point for A2 output. 

 Not available if option A2 is not applied or if No alarm action is 

  selected in A2 action selection. 

 Refer to (Table 5.3-1). 

0  

. , 

XX.X 

indicated 
in turn 

Heater burnout alarm setting 

 Sets the heater current value for Heater burnout alarm. 

 Self-holding is not available for the alarm output. 

• 

Available only when the option W is added. 

 Rating 5A  : 0.0 to 5.0A 

Rating 10A: 0.0 to 10.0A 

Rating 20A: 0.0 to 20.0A         Rating 50A: 0.0 to 50.0A 

0.0A 

Summary of Contents for TP40A

Page 1: ...it might deform or tarnish the unit As the display section is vulnerable do not strike or scratch it with a hard object Any unauthorized transfer or copying of this document in part or in whole is pr...

Page 2: ...key the setting value or selected value can be registered 14 OUT OFF key The control output ON OFF function or Auto Manual control function can be switched To cancel the control output ON OFF function...

Page 3: ...unting Mount the controller vertically to fulfill the Dust proof Drip proof specification IP66 Mountable panel thickness Within 1 to 15mm Insert the controller from the front side of the panel Attach...

Page 4: ...uilt in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A...

Page 5: ...he input range high limit value is indicated on the SV display for approximately 3 seconds Table 5 1 If any other value is set during the scaling high limit setting the set value is indicated on the S...

Page 6: ...OUT1 high limit setting A1 action delayed timer setting OUT1 proportional cycle setting Data transfer rate selection OUT1 low limit setting A2 action delayed timer setting OUT2 proportional cycle sett...

Page 7: ...Not available when OUT1 is ON OFF action Auto reset can be performed when PD action I 0 Setting range 0 to 1000 seconds 200 seconds Derivative time setting Sets derivative time for OUT1 Setting the va...

Page 8: ...ds on the designation When Lock 1 or Lock 2 is designated PID Auto tuning and Auto reset cannot be carried out Unlock Unlock All setting values can be changed Lock 1 None of the setting values can be...

Page 9: ...0 4 to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200...

Page 10: ...to 100 0 or 1 to 1000 0 OUT2 ON OFF action hysteresis setting Sets ON OFF action hysteresis for OUT2 Available only when the option DT is added Setting range 0 1 to 100 0 or 1 to 1000 1 0 A1 action se...

Page 11: ...is overscale or underscale Available only for DC current output type with DC inputs Output OFF Output ON Output OFF OUT OFF key function selection Selects whether OUT OFF key is used for control outp...

Page 12: ...of the unused instrument of the plural units OFF even if the power to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is en...

Page 13: ...dby High Low limit alarm with standby Low limit alarm with standby OFF ON A1 hysteresis OFF ON SV setting OFF ON A1 hysteresis OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Alarm action Alarm action Alarm...

Page 14: ...or OFF unlit Represents Heating control action Represents Cooling control action 7 6 OUT2 Heating Cooling control action When setting Dead band Changes continuously according to deviation Non contact...

Page 15: ...the temperature rises When AT bias is set to 20 fluctuation is applied at the temperature 20 lower than the setting value 15 1 2 3 4 Temperature Setting value 1 Calculating PID constant 2 PID constant...

Page 16: ...reater Allowable input voltage 15V or less Allowable signal source resistance 100 or less OUT1 output Relay contact 1a Control capacity 3A 250V AC resistive load 1A 250V AC inductive load cos 0 4 Elec...

Page 17: ...370 to 1850 370 to 1850 0 to 1760 50 to 1810 50 to 1810 R S 0 to 3200 50 to 3250 50 to 3250 0 to 1820 50 to 1870 50 to 1870 B 0 to 3300 50 to 3350 50 to 3350 200 to 800 250 to 850 250 to 850 E 320 to...

Page 18: ...breaking status on the loop such as heater burnout sensor burnout or actuator trouble The output terminals will be common if the options W and A2 are applied together Setting range Loop break alarm ac...

Page 19: ...e the function is blinking on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check sensor burnout Thermocouple If the input terminal of the instrument...

Page 20: ...nterference or noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 10 2 Key operation Problem Presumed cause and solution Unable to set th...

Reviews: