IMO TP40A Instruction Manual Download Page 18

 

For 0 to 20mA DC, 0 to 5V DC and 0 to 10V DC inputs, the PV display   

 

indicates the corresponding value with which 0mA or 0V is inputted. 

[Burnout] 

When the thermocouple or RTD input is burnt out, OUT1 and OUT2 are turned off (for DC curren

output type, OUT1 low limit value, OUT2 low limit value) and PV display blinks “

”. 

 

 

[Self-diagnosis]

The CPU is monitored by a watchdog timer, and when any abnormal status is found on the 

CPU, the controller is switched to warm-up status

[Automatic cold junction temperature compensation] (Only thermocouple input type

This detects the temperature at the connecting terminal between the thermocouple and the instrument

and always keeps it set to the same status as when the reference junction is located at 0  (32 ). 

 

 

 

 

r.

 

 

[Power failure countermeasure]   

The setting data is backed up in the non-volatile IC memory. 

[Warm-up indication]

After the power supply to the instrument is turned on, the sensor input character and temperature 

unit are indicated on the PV display and rated scale high limit value is indicated on the SV display 

for 3 seconds

For DC current and voltage inputs, the scaling high limit value is indicated

Accessories included

: Screw type mounting bracket 1 set, Instruction manual 1 copy

CT (Current transformer) CTL-6S  1 piece(for rating 5A, 10A, 20A) 

CTL-12-S36-10L1    1 piece (for rating 50A) 

9.2 Optional specifications 

Alarm 2 (A2) (Option code: A2

The output terminals will be common when the options [W] and [LA] are added togethe

Action

: ON/OFF action 

Hysteresis : 0.1 to 100.0

 

( ), or 1 to 1000 

Output

: Relay contact    1a 

 

 

 

 

 

 

 

 

 

Control capacity, 3A    250V AC (Resistive load)   

Electrical life, 100,000 times 

Loop break alarm (Option code: LA)

When MV (manipulated variable) is maximum or minimum and when the PV does not change as much 

as the preset span within the Loop break alarm assessment time, the alarm is activated.

This also detects the breaking status on the loop such as heater burnout, sensor burnout or actuator

trouble.

The output terminals will be common if the options [W] and [A2] are applied together. 

Setting range : Loop break alarm action time, 0 to 200minutes 

Loop break alarm action span, 0 to 150 ( ), 0.0 to 150.0 ( ), 0 to 1500 

Output

: Relay contact    1a 

 

 

 

 

 

 

 

 

 

 

 

 

Control capacity, 3A    250V AC (Resistive load) 

Electrical life, 100,000 times 

Heater burnout alarm (including sensor burnout alarm) (Option code: W)

Monitors heater current with CT (current transformer), and detects burnout.

The output terminals will be common if the options [LA] and [A2] are applied with it.

This option cannot be applied to DC current output type.

Rating

: 5A [W(5A)], 10A [W(10A)], 20A [W(20A)], 50A [W(50A)] (Must be specified) 

Setting range

: 5A [W(5A)], 0.0 to 5.0A (Off when set to 0.0) 

10A [W(10A)], 0.0 to 10.0A (Off when set to 0.0) 

20A [W(20A)], 0.0 to 20.0A (Off when set to 0.0) 

50A [W(50A)], 0.0 to 50.0A (Off when set to 0.0) 

Setting accuracy : Within  5% of the rated value 

Action

: ON/OFF action 

 

 

 

 

 

 

 

 

 

Output

: Relay contact    1a 

Control capacity, 3A    250V AC (resistive load) 

Electrical life, 100,000 times 

Heating/Cooling control (Option code: DT) 

The specification of Heating side is the same as that of OUT1.

OUT2 proportional band : 0.0 to 10.0 times OUT1 proportional band (ON/OFF action when set to 0.0) 

OUT2 integral time

: The same as that of OUT1. 

OUT2 derivative time

: The same as that of OUT1. 

OUT2 proportional cycle : 1 to 120 seconds 

Overlap band/Dead band setting range:

Thermocouple, RTD inputs: –100.0 to 100.0

 

( ) 

 

 

 

 

 

DC current, DC voltage inputs: –1000 to 1000 (The placement of the decimal point follows the

 selection) 

Output: Non-contact relay output 0.3A    250V AC

Cooling action mode selection function:

One cooling action can be selected from Air cooling (linear characteristic), Oil cooling (1.5th power o

the linear characteristic) and Water cooling (2nd power of the linear characteristic) by key operation

Serial communication (Option code: C5) 

When this option is added, the option [SM] cannot be added with it.

The following operations can be carried out from the external computer. 

18 

Summary of Contents for TP40A

Page 1: ...it might deform or tarnish the unit As the display section is vulnerable do not strike or scratch it with a hard object Any unauthorized transfer or copying of this document in part or in whole is pr...

Page 2: ...key the setting value or selected value can be registered 14 OUT OFF key The control output ON OFF function or Auto Manual control function can be switched To cancel the control output ON OFF function...

Page 3: ...unting Mount the controller vertically to fulfill the Dust proof Drip proof specification IP66 Mountable panel thickness Within 1 to 15mm Insert the controller from the front side of the panel Attach...

Page 4: ...uilt in power switch circuit breaker or fuse Therefore it is necessary to install them in the circuit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A...

Page 5: ...he input range high limit value is indicated on the SV display for approximately 3 seconds Table 5 1 If any other value is set during the scaling high limit setting the set value is indicated on the S...

Page 6: ...OUT1 high limit setting A1 action delayed timer setting OUT1 proportional cycle setting Data transfer rate selection OUT1 low limit setting A2 action delayed timer setting OUT2 proportional cycle sett...

Page 7: ...Not available when OUT1 is ON OFF action Auto reset can be performed when PD action I 0 Setting range 0 to 1000 seconds 200 seconds Derivative time setting Sets derivative time for OUT1 Setting the va...

Page 8: ...ds on the designation When Lock 1 or Lock 2 is designated PID Auto tuning and Auto reset cannot be carried out Unlock Unlock All setting values can be changed Lock 1 None of the setting values can be...

Page 9: ...0 4 to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 K 320 to 2500 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200...

Page 10: ...to 100 0 or 1 to 1000 0 OUT2 ON OFF action hysteresis setting Sets ON OFF action hysteresis for OUT2 Available only when the option DT is added Setting range 0 1 to 100 0 or 1 to 1000 1 0 A1 action se...

Page 11: ...is overscale or underscale Available only for DC current output type with DC inputs Output OFF Output ON Output OFF OUT OFF key function selection Selects whether OUT OFF key is used for control outp...

Page 12: ...of the unused instrument of the plural units OFF even if the power to the instrument is supplied is indicated on the PV display while the function is working Once the control output OFF function is en...

Page 13: ...dby High Low limit alarm with standby Low limit alarm with standby OFF ON A1 hysteresis OFF ON SV setting OFF ON A1 hysteresis OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Alarm action Alarm action Alarm...

Page 14: ...or OFF unlit Represents Heating control action Represents Cooling control action 7 6 OUT2 Heating Cooling control action When setting Dead band Changes continuously according to deviation Non contact...

Page 15: ...the temperature rises When AT bias is set to 20 fluctuation is applied at the temperature 20 lower than the setting value 15 1 2 3 4 Temperature Setting value 1 Calculating PID constant 2 PID constant...

Page 16: ...reater Allowable input voltage 15V or less Allowable signal source resistance 100 or less OUT1 output Relay contact 1a Control capacity 3A 250V AC resistive load 1A 250V AC inductive load cos 0 4 Elec...

Page 17: ...370 to 1850 370 to 1850 0 to 1760 50 to 1810 50 to 1810 R S 0 to 3200 50 to 3250 50 to 3250 0 to 1820 50 to 1870 50 to 1870 B 0 to 3300 50 to 3350 50 to 3350 200 to 800 250 to 850 250 to 850 E 320 to...

Page 18: ...breaking status on the loop such as heater burnout sensor burnout or actuator trouble The output terminals will be common if the options W and A2 are applied together Setting range Loop break alarm ac...

Page 19: ...e the function is blinking on the PV display Thermocouple RTD or DC voltage 0 to 1V DC is burnt out Change each sensor How to check sensor burnout Thermocouple If the input terminal of the instrument...

Page 20: ...nterference or noise away from the controller The PV display is indicating Internal memory is defective Contact our agency or us 10 2 Key operation Problem Presumed cause and solution Unable to set th...

Reviews: