MAINTEN

AN

CE TECHNI

CI

AN

TYPE OF DUCT

Resistance

Factor

(R)

Equivalent  

length in m of 

concentric pipe 

Ø60/100

Equivalent  

length in metres  

of pipe Ø80

Equivalent  

length in metres  

of pipe Ø60

Equivalent  

length in m of 

concentric pipe 

Ø80/125

Concentric pipe Ø60/100 

m 1

Intake and

Exhaust 6.4

m 1

Intake m 7.3

Exhaust m 1.9

m 3.0

Exhaust m 5.3

Concentric bend 90° 

Ø60/100

Intake and

Exhaust 8.2

m 1.3

Intake m 9.4

Exhaust m 2.5

m 3.9

Exhaust m 6.8

Concentric bend 45° 

Ø60/100

Intake and

Exhaust 6.4

m 1

Intake m 7.3

Exhaust m 1.9

m 3.0

Exhaust m 5.3

Terminal complete with 

concentric horizontal 

intake-exhaust Ø60/100

Intake and

Exhaust 15

m 2.3

Intake m 17.2

Exhaust m 4.5

m 7.1

Exhaust m 12.5

Concentric horizontal 

intake- exhaust terminal 

Ø60/100

Intake and

Exhaust 10

m 1.5

Intake m 11.5

Exhaust m 3.0

m 4.7

Exhaust m 8.3

Terminal complete with 

concentric vertical intake-

exhaust Ø60/100

Intake and

Exhaust 16.3

m 2.5

Intake m 18.7

Exhaust m 4.9

m 7.7

Exhaust m 13.6

Concentric vertical intake-

exhaust terminal Ø60/100

Intake and

Exhaust 9

m 1.4

Intake m 10.3

Exhaust m 2.7

m 4.3

Exhaust m 7.5

Pipe Ø80, 1 m

Intake 0.87

m 0.1

Intake m 1.0

Exhaust m 0.4

m 0.4
m 0.5

Exhaust 1.2

m 0.2

Exhaust m 1.0

Complete intake terminal 

Ø80, 1 m

Intake 3

m 0.5

Intake m 3.4

Exhaust m 0.9

m 1.4

Intake terminal Ø 80

Exhaust terminal Ø 80

Intake 2.2

m 0.35

Intake m 2.5

Exhaust m 0.6

m 1

m 0.9

Exhaust 1.9

m 0.3

Exhaust m 1.6

Bend 90° Ø80

Intake 1.9

m 0.3

Intake m 2.2

Exhaust m 0.8

m 0.9
m 1.2

Exhaust 2.6

m 0.4

Exhaust m 2.1

Bend 45° Ø80

Intake 1.2

m 0.2

Intake m 1.4

Exhaust m 0.5

m 0.5

0.7

Exhaust 1.6

m 0.25

Exhaust m 1.3

Pipe Ø 60 m 1 for ducting

Exhaust 3.3

m 0.5

Intake 3.8

Exhaust m 1.0

m 1.5

Exhaust 2.7

Bend 90° Ø60 for ducting

Exhaust 3.5

m 0.55

Intake 4.0

Exhaust m 1.1

m 1.6

Exhaust 2.9

Reduction Ø 80/60

Intake and

Exhaust 2.6

m 0.4

Intake m 3.0

Exhaust m 0.8

m 1.2

Exhaust m 2.1

Terminal complete with 

exhaust vertical Ø60 for 

ducting

Exhaust 12.2

m 1.9

Intake m 14

Exhaust m 3.7

m 5.8

Exhaust m 10.1

Summary of Contents for VICTRIX X12-242I

Page 1: ...VICTRIX X 12 24 2 I IE Instruction and Warning book 1 036643ENG...

Page 2: ......

Page 3: ...user also in the case of transfer or succession of ownership It must be stored with care and consulted carefully as all of the warnings provide important safety indications for installation use and m...

Page 4: ...ation pump 19 1 25 Kits available on request 20 1 26 Boiler components 21 2 Instructions for use and maintenance 22 2 1 Cleaning and maintenance 22 2 2 General warnings 22 2 3 Control panel 22 2 4 Usi...

Page 5: ...pliance off immediately and contact a qualified technician e g the Immergas Technical Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair...

Page 6: ...by introducing a top quality anti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percent...

Page 7: ...ional way using the couplings on the boiler template The boiler safety valve outlet must be connected toadrainingfunnel Otherwise themanufacturer declines any responsibility in case of flooding if the...

Page 8: ...i e it must be set to On Off mode CARV2 or chrono thermostat On Off electric connection Optional The operations described below must be performed after having removed the voltage from the appliance T...

Page 9: ...l Kit This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning of the gaskets black for green range flue extraction systems Posit...

Page 10: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust...

Page 11: ...of the straps present in the kit making sure to block the 4 gasket flaps Fit the male side smooth of the exhaust terminal into the the female side of the bend 90 80 making sure that the relevant wall...

Page 12: ...o the external atmosphere The technical regulations in force must be respected Max length of exhaust duct The flue pipe vertical or horizontal can be extended to a max length of 30 straight metres Spa...

Page 13: ...al intake exhaust kit 80 125 Kit assembly Fig 1 18 for the installation of kit 80 125 the flanged adapter kit must be used to be able to install the flue system 80 125 Install the flanged adapter 2 on...

Page 14: ...l 6 and insert the intake exhaust pipe 5 Fit the 60 100 3 concentric terminal pipe with the male end 5 smooth into the flange 2 up to the stop making sure that the wall sealing plate has been fitted 3...

Page 15: ...sent in the lateral hole with respect to the central one according to needs and replace it with the flange 3 positioning the gasket 2 already present in the boiler and tighten using the supplied self...

Page 16: ...emoval of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a min slope of 1 5 Assemble the lid A complete with adapter 1 and wall plugs 6 and assemble the flue to...

Page 17: ...e inside the flue technical slot The max possible length of the 60 flexible ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe...

Page 18: ...nt the circulation pump by loosening the front cap and keeping the motor running Re tighten the cap after the operation 1 21 FILLING THE CONDENSATE TRAP On first lighting of the boiler combustion prod...

Page 19: ...24 CIRCULATION PUMP The Victrix X 12 24 2I series boilers are supplied with a built in circulation pump with 3 position electric speed control The boiler does not operate correctly with the circulatio...

Page 20: ...rmation of lime scale and preserves the original heat exchange and domestic hot water production conditions The boiler is prepared for application of the polyphosphate dispenser kit Relay board on req...

Page 21: ...ondensation module 11 Flue probe 12 Heat exchanger safety thermofuse 13 Manual air vent valve 14 Sample points air A flue gases F 15 Negative signal pressure point 16 Positive signal pressure point 17...

Page 22: ...ic hot water temperature selector switch 6 Central heating water temperature selector switch 7 Boiler manometer 8 DHW production phase functioning active 9 Boiler in block does not require release via...

Page 23: ...ite flame block 20 Return probe anomaly 23 Push button control panel anomaly 24 Block due to flue gas temperature gradient intervention 25 Insufficient circulation 27 Flue probe anomaly 29 Loss of rem...

Page 24: ...signal loss error occurs 6 times consecutively in 8 5 minutes 38 To eliminate the block the Reset button 3 must be pressed If this phenomenon occurs frequently contact a qualified technician for assis...

Page 25: ...TI FREEZE PROTECTION The boiler has an anti freeze function that switches on automatically when the temperature fallsbelow 4 C standardprotectiontominimum temperature of 5 C All information relative t...

Page 26: ...the gas flow rate regulation devices if settings are modified checktheproductionofDHW whentheboiler is connected to an external cylinder unit ensure sealing efficiency of water circuits check ventilat...

Page 27: ...ed for software updating operations 3 3 TROUBLESHOOTING N B maintenance interventions must be carried out by a qualified technician e g Immergas After Sales Technical Assistance Service Smell of gas C...

Page 28: ...eating output ignition power 3 6 ADJUSTMENT OF THE AIR GAS RATIO Important theverificationoperationsoftheCO2 must be carried out with the casing mounted while the gas valve calibration operations must...

Page 29: ...heating demand of the house Therefore the boiler works normally in a variable gas pressure field between minimum and maximum power depending on the system heat load setting fan speed in rpm hundreds...

Page 30: ...ich can be configured 0 Off 1 General alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay board contact 5 Heat pump 0 5 0 P5 Relay 3 optional The boiler...

Page 31: ...every new power supply of the boiler by pressing buttons at the same time 2 and 4 Fig 2 1 for 5 seconds with boiler in stand by N B if the boiler is connected to the CARV2 the stand by function is onl...

Page 32: ...osen the two screws 4 present in the lower part of the casing front 3 unhook the central fixing 6 exerting slight pressure in the median zone of the side 5 pull the front casing slightly in the lower...

Page 33: ...sure of 1013 mbar Burner pressure values refer to use of gas at 15 C Victrix X 12 2 I Victrix X 24 2 I METHANE G20 BUTANE G30 PROPANE G31 HEAT OUTPUT HEAT OUTPUT BURNER GAS FLOW RATE BURNER NOZZLES PR...

Page 34: ...at Nom Q Min mg kWh 48 13 185 20 85 25 Flue temperature at nominal output C 56 63 57 Flue temperature at minimum output C 58 64 59 Victrix X 24 2 I Gas nozzle diameter 8205 gas valve mm 5 80 4 10 4 1...