background image

16

1

2

3

3

3

4

5

6

7

6 8

9

A

10

11

12

12

A

B

A
C

1-28

1-27

INS

TALL

AT

O

R

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

Kit composition:

Ref.

Qty

Description

1

1

Door adapter Ø100 or Ø125

2

1

Door gasket in neoprene

3

4

Screws 4.2 x 9 AF

4

1

Screw TE M6 x 20

5

1

Flat washer in nylon M6

6

2

Door hole closure steel cap

7

1

Neoprene cap gasket

8

1

Toothed washer M6

9

1

Nut M6

10 1 (kit 80/125) Concentric gasket Ø60/-100
11 1 (kit 80/125) Flanged adapter Ø80/-125
12 4 (kit 80/125) Screws TE M4 x 16 flat head screwdriver

-

1 (kit 80/125) Lubricant talc bag

Supplied separately:

Installation drawings key:

Unmistakeable component identification 

present in the kit
Identification component not supplied with 

this kit

1

A

Ref. Qty Description

A

1

Ducting kit door

Rigid Ø80 

Ducting

  

(A) mm

AIR 

SHAFT

(B) mm

AIR 

SHAFT

(C) mm

86

126

146

Flexible Ø80 

Ducting

  

(A) mm

AIR 

SHAFT

(B) mm

AIR 

SHAFT

(C) mm

90

130

150

Rigid Ø60 

Ducting

  

(A) mm

AIR 

SHAFT

(B) mm

AIR 

SHAFT

(C) mm

66

106

126

1.15 ADAPTER KIT INSTALLATION C9. 

The current kit allows for the installation of one 

Immergas boiler in configuration "C93", carrying 

out the combustion air intake directly from the 

air shaft where the flue exhausts are carried out 

by means of a ducting system.

System composition.

The kit must be combined with the following 

components (sold separately) to be functional 

and complete:

- kit C93 version Ø100 or Ø125
- ducting kit Ø60 or Ø80
- flue exhaust kit Ø60/100 o Ø80/125 

configuration based on the installation and 

the type of boiler.

Kit assembly.

- Assemble the components of kit "C9" on door 

(A) of the ducting system (Fig. 1-28).

-  (Only version Ø125) install the adapter flange 

(11) positioning the concentric gasket (10) on 

the boiler and tighten using the screws in the 

kit (12).

- Carry out the ducting system assembly as 

described in the relative instructions sheet.

- Calculate the distance between the boiler 

exhaust and the ducting system bend.

- Prepare the boiler flue by calculating that the 

internal pipe of the concentric kit must engage 

until the end stop in the ducting system bend 

(quota "X" fig. 1-29).

 N.B.:

 to favour the removal of possible 

condensate forming in the exhaust pipe, tilt 

the pipes towards the boiler with a min. slope 

of 1.5%.

-  Assemble the lid (A) complete with adapter (1) 

and wall plugs (6) and assemble the flue to the 

ducting system.

N.B.:

 (only version Ø125) before assembling 

check that the positioning of the gaskets is 

correct. In the case the components lubrication 

(already carried out by the manufacturer) is not 

sufficient, remove the residual lubricant using a 

dry cloth, then to ease fitting spread the elements 

with common or industrial talc.
Once all the components are assembled correctly 

the flue exhausts will be expelled by the ducting 

systems, for the normal operation of the boiler 

the combustion air will take in the air directly 

from the air shaft (Fig. 1-29).

Technical data.

-  The dimensions of the air shafts must guarantee 

an minimum gap between the external wall of 

the flue pipe and the internal wall of the air 

shaft: 30 mm per circular section air shafts and 

20 mm in the case of squared section air shaft 

(Fig. 1-27).

-  On the vertical section of the flue a maximum 

of 2 changes of direction with a maximum angle 

of incidence of 30° with respect to the vertical.

- The maximum vertical extension using a 

ducting system of Ø60 is 13 m, the maximum 

extension includes 1 bend Ø60/10 at 90°, 1 m 

of pipe 60/100 in horizontal, 1 bend 90° Ø60 

ducted and the roof terminal for ducting.

  For the determination of the flue system C93 in 

different configurations than those previously 

described (Fig. 1-29) it is necessary to consider 

that 1 metre of ducted pipe according to the 

indications described, has a resistance factor 

equal to 4.9.

- The maximum vertical extension using a 

ducting system of Ø80 is 28 m, the maximum 

extension includes 1 adapter from 60/100 to 

80/125, 1 m bend Ø80/125 to 87°, 1 m of pipe 

80/125 in horizontal, 1 bend 90° Ø80 ducted 

and the roof terminal for ducting. 

  For the determination of the flue system C93 in 

different configurations than those previously 

described (Fig. 1-29) it is necessary to consider 

the following head loss:

  - 1 m of pipe Ø1 m concentric duct Ø80/125 

= 1 m of ducted pipe;

  - 1 bend at 87° = 1.4 m of dusted pipe.
  As a consequence it is necessary to subtract the 

equivalent length of the added part to the 28 m 

available.

Summary of Contents for VICTRIX X12-242I

Page 1: ...VICTRIX X 12 24 2 I IE Instruction and Warning book 1 036643ENG...

Page 2: ......

Page 3: ...user also in the case of transfer or succession of ownership It must be stored with care and consulted carefully as all of the warnings provide important safety indications for installation use and m...

Page 4: ...ation pump 19 1 25 Kits available on request 20 1 26 Boiler components 21 2 Instructions for use and maintenance 22 2 1 Cleaning and maintenance 22 2 2 General warnings 22 2 3 Control panel 22 2 4 Usi...

Page 5: ...pliance off immediately and contact a qualified technician e g the Immergas Technical Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair...

Page 6: ...by introducing a top quality anti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percent...

Page 7: ...ional way using the couplings on the boiler template The boiler safety valve outlet must be connected toadrainingfunnel Otherwise themanufacturer declines any responsibility in case of flooding if the...

Page 8: ...i e it must be set to On Off mode CARV2 or chrono thermostat On Off electric connection Optional The operations described below must be performed after having removed the voltage from the appliance T...

Page 9: ...l Kit This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning of the gaskets black for green range flue extraction systems Posit...

Page 10: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust...

Page 11: ...of the straps present in the kit making sure to block the 4 gasket flaps Fit the male side smooth of the exhaust terminal into the the female side of the bend 90 80 making sure that the relevant wall...

Page 12: ...o the external atmosphere The technical regulations in force must be respected Max length of exhaust duct The flue pipe vertical or horizontal can be extended to a max length of 30 straight metres Spa...

Page 13: ...al intake exhaust kit 80 125 Kit assembly Fig 1 18 for the installation of kit 80 125 the flanged adapter kit must be used to be able to install the flue system 80 125 Install the flanged adapter 2 on...

Page 14: ...l 6 and insert the intake exhaust pipe 5 Fit the 60 100 3 concentric terminal pipe with the male end 5 smooth into the flange 2 up to the stop making sure that the wall sealing plate has been fitted 3...

Page 15: ...sent in the lateral hole with respect to the central one according to needs and replace it with the flange 3 positioning the gasket 2 already present in the boiler and tighten using the supplied self...

Page 16: ...emoval of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a min slope of 1 5 Assemble the lid A complete with adapter 1 and wall plugs 6 and assemble the flue to...

Page 17: ...e inside the flue technical slot The max possible length of the 60 flexible ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe...

Page 18: ...nt the circulation pump by loosening the front cap and keeping the motor running Re tighten the cap after the operation 1 21 FILLING THE CONDENSATE TRAP On first lighting of the boiler combustion prod...

Page 19: ...24 CIRCULATION PUMP The Victrix X 12 24 2I series boilers are supplied with a built in circulation pump with 3 position electric speed control The boiler does not operate correctly with the circulatio...

Page 20: ...rmation of lime scale and preserves the original heat exchange and domestic hot water production conditions The boiler is prepared for application of the polyphosphate dispenser kit Relay board on req...

Page 21: ...ondensation module 11 Flue probe 12 Heat exchanger safety thermofuse 13 Manual air vent valve 14 Sample points air A flue gases F 15 Negative signal pressure point 16 Positive signal pressure point 17...

Page 22: ...ic hot water temperature selector switch 6 Central heating water temperature selector switch 7 Boiler manometer 8 DHW production phase functioning active 9 Boiler in block does not require release via...

Page 23: ...ite flame block 20 Return probe anomaly 23 Push button control panel anomaly 24 Block due to flue gas temperature gradient intervention 25 Insufficient circulation 27 Flue probe anomaly 29 Loss of rem...

Page 24: ...signal loss error occurs 6 times consecutively in 8 5 minutes 38 To eliminate the block the Reset button 3 must be pressed If this phenomenon occurs frequently contact a qualified technician for assis...

Page 25: ...TI FREEZE PROTECTION The boiler has an anti freeze function that switches on automatically when the temperature fallsbelow 4 C standardprotectiontominimum temperature of 5 C All information relative t...

Page 26: ...the gas flow rate regulation devices if settings are modified checktheproductionofDHW whentheboiler is connected to an external cylinder unit ensure sealing efficiency of water circuits check ventilat...

Page 27: ...ed for software updating operations 3 3 TROUBLESHOOTING N B maintenance interventions must be carried out by a qualified technician e g Immergas After Sales Technical Assistance Service Smell of gas C...

Page 28: ...eating output ignition power 3 6 ADJUSTMENT OF THE AIR GAS RATIO Important theverificationoperationsoftheCO2 must be carried out with the casing mounted while the gas valve calibration operations must...

Page 29: ...heating demand of the house Therefore the boiler works normally in a variable gas pressure field between minimum and maximum power depending on the system heat load setting fan speed in rpm hundreds...

Page 30: ...ich can be configured 0 Off 1 General alarm 2 CH phase active 3 External gas valve power supply 4 Secondary zone control from TA on relay board contact 5 Heat pump 0 5 0 P5 Relay 3 optional The boiler...

Page 31: ...every new power supply of the boiler by pressing buttons at the same time 2 and 4 Fig 2 1 for 5 seconds with boiler in stand by N B if the boiler is connected to the CARV2 the stand by function is onl...

Page 32: ...osen the two screws 4 present in the lower part of the casing front 3 unhook the central fixing 6 exerting slight pressure in the median zone of the side 5 pull the front casing slightly in the lower...

Page 33: ...sure of 1013 mbar Burner pressure values refer to use of gas at 15 C Victrix X 12 2 I Victrix X 24 2 I METHANE G20 BUTANE G30 PROPANE G31 HEAT OUTPUT HEAT OUTPUT BURNER GAS FLOW RATE BURNER NOZZLES PR...

Page 34: ...at Nom Q Min mg kWh 48 13 185 20 85 25 Flue temperature at nominal output C 56 63 57 Flue temperature at minimum output C 58 64 59 Victrix X 24 2 I Gas nozzle diameter 8205 gas valve mm 5 80 4 10 4 1...

Page 35: ...Nom Min 106 9 102 4 106 7 103 0 Efficiency 40 30 Nom Min 107 0 106 8 108 1 107 1 Heat loss at casing with burner On Off 80 60 C 0 89 0 30 0 41 0 50 Heat loss at flue with burner On Off 80 60 C 0 02 2...

Page 36: ...erial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum heating capacity domestic Qn min Minimum heating capacity heating Qnw max Maximum heating capacity dom...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...mergas com Immergas S p A 42041 Brescello RE Italy T 39 0522 689011 F 39 0522 680617 This instruction booklet is made of ecological paper Cod 1 036643ENG rev ST 000346 000 02 2014 Inglese per IRLANDA...

Reviews: