background image

32

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

Programming menu

Menu item

Description

Adjustment range

Default Value

Customised 

Value

P01 Heating Set Temp

This defines the boiler's flow temperature during heating

20 ÷ P02 °C

85

P02 Max Heating Set Temp This defines the maximum settable flow temperature during heating

20 ÷ 95 °C

85

P03 Heating Hysteresis

This defines the power-off hysteresis during the heating phase

2 ÷ 10 °C

5

P04 Heating Anti-Cycle 

Time

This is used to set a waiting time to avoid the boiler from switching on 

multiple times and frequently during CH mode

0 ÷ 15 minutes

3 minutes

P05 Burner Stabilization 

Time

This is the amount of time that the boiler needs to stabilise, when the burner 

runs at minimum power for the set amount of time

3 ÷ 10 minutes

3 minutes

P06 Heating Temp Rise

The amount of time that the boiler takes to reach the required temperature, 

number of degrees per minute (0 means no ramp)

0 ÷ 60 °C/minute

4 °C/minute

P07 Heating Pump 

Overrun Time 

The amount of CH post circulation once the CH phase is fnished

1 ÷ 30 minutes

3 minutes

P08

Boiler Power Used 

During Max Heating 

Mode

This defines the maximum power percentage to be used during the set CH 

phase 

P09 ÷ 100%

100%

P09

Boiler Power Used 

During Min Heating 

Mode 

This defines the minimum power percentage to be used during the set CH 

phase 

0 ÷ P08%

0%

P10 Minimum system 

flow rate

This defines the minimum system flow rate required to power-on the boiler

Attention:

 do not change this parameter

÷

 47 l/minutes

14 l/minutes

P11 Electrode Anti-

Humidity Fan Speed

This defines fan speed and operating mode, to avoid humidity inside 

the condensing module, which could otherwise cause the electrodes to 

malfunction (0 = disabled function, recommended value = 40) (RPM speed is 

calculated by multiplying the value displayed by 50)

P26 

÷

120

0

P12 Boiler’s modulation 

ratio

It defines the boiler’s modulation ratio (Do not modify)

0 ÷ 100 %

10%

P13 Boiler power

Used to calculate the boiler power in the event of simple cascade.

÷

 255 kW

50

P14 External probe curve

This is used to select the external probe operating curve (optional) (0 = 

disabled probe)

÷

 10

0

P15 External probe offset

This defines the CH offset in relation to the selected external probe curve

20 

÷

 70 °C

30 °C

P16 DHW Set Temp

This defines the DHW temperature

20 ÷ 65 °C

65 °C

P17 DHW Configuration

-    With a single boiler it controls an external 3-way. 

-    With single boiler and common flow probe, it lets you choose between an 

      external D.H.W pump and a 3-way one.

-    With a simple cascade, it manages a D.H.W. pump (downstream an 

hydraulic separator).

0 = 3 Ways

1 = D.H.W. pump

0

P18 DHW Hysteresis

This defines the DHW power-on hysteresis during CH

2 ÷ 10 °C

5 °C

P19 DHW Pump Overrun 

Time

This is the post circulation time during DHW once DHW production is 

finished

÷

 180 seconds

60 seconds

P20

Boiler Power Used 

During Max DHW 

Mode

This defines the maximum power percentage to be used during the set DHW 

phase 

P21 

÷

 100 %

50 %

P21

Boiler Power Used 

During Min DHW 

Mode

This defines the minimum power percentage to be used during the set DHW 

phase 

÷

 P20 %

0 %

P22 Flow Delivery Temp 

During DHW Mode

In combination with a storage tank and a separate thermostat, this defines the 

flow temperature during DHW operation

35 

÷

 90 °C

80 °C

P23 DHW Modulation

Summed with the “Set San” (P16) parameter, this defines the flow 

temperature set that the boiler has to modulate the power on during DHW

÷

 30 °C

15 °C

P24 DHW Off Increment

This defines the time that the boiler allows the burner to switch off during 

DHW, by an increment of 5 °C on top of the flow temperature

÷

 255 seconds

60 seconds

P25 Max Fan Speed

This defines the max fan speed and therefore the maximum relative boiler 

operating power

P26 

÷

 255

Met. 131

LPG 129

Summary of Contents for VICTRIX PRO 55 1 A

Page 1: ...VICTRIX PRO 55 1 A Wall mounted heating only boiler User Installation Instruction Manual AU...

Page 2: ......

Page 3: ...rder to install the product correctly Maintenance must be carried out by Authorised Service Personal The appliance must only be destined for the use for which it has been expressly declared Any other...

Page 4: ...ting 24 2 7 Info menu 26 2 8 Boiler shutdown 26 2 9 Restoring central heating system pressure 26 2 10 System drainage 26 2 11Anti freeze protection 26 2 12Case cleaning 26 2 13Decommissioning 26 3 Boi...

Page 5: ...ell as their eventual replacement withappliancesand or equivalent components Installation must be carried out according to regulation standards AS NZS 5601 or Local Authority laws Attention these boil...

Page 6: ...ove ground at least 2 3 of the aeration surface must be flush with the floor with a minimum height of 0 2 m The aeration openings must be at least 2 m for heating capacities not exceeding 116 kW and 4...

Page 7: ...in case of supply from LPG depot New LPG storage tanks may contain residual inert gases nitrogen that degrade the mixture delivered to the appliance causing problems with boiler operation Due to the...

Page 8: ...t Heating decline any responsibility for damage or physical injury caused by failure to connect the boiler to an efficient earth system or failure to comply with the reference standards Also ensure th...

Page 9: ...heat adjuster via 2 wires Thermostat electrical connection Fig 1 5 Thermoregulation electrical connections must be carried out on the boiler terminal board eliminating jumper X40 Thermostat or On Off...

Page 10: ...on Type C configuration sealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disasse...

Page 11: ...t 1 3 m Terminal complete with vertical exhaust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric be...

Page 12: ...ent space to carry out the tests required by law upon commissioning The intake exhaust terminal if properly in stalled is pleasant to look at on the outside of the building Make sure that the external...

Page 13: ...er 1 up to the relevant groove Fix it to the lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it t...

Page 14: ...m length MAX L Fig 1 16 The kit with this configuration can be extended up to a max measurement of 30 0 m with Victrix Pro 55 1A including the terminal Using the 80 vertical terminal for direct dis ch...

Page 15: ...and external 4 wall sealing plate has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 22 install the 80 be...

Page 16: ...em refer to the technical standard in force This divides the systems and therefore the start up operations into three categories new systems modified systems re activated systems In particular for new...

Page 17: ...of 18 C between flow and return During DHW mode the pump always runs at the maximum speed Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew the front cap...

Page 18: ...densation module cover 12 Igniter 13 Ignition electrode 14 Flue probe 15 Condensing module air vent valve 16 Fumes hood 17 Sample points air A flue gas F 18 Heat exchanger safety thermal fuse 19 Manua...

Page 19: ...circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collection Whene...

Page 20: ...ng circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety thermostat CMI...

Page 21: ...the heating system if anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on the boiler that lead to the closure of one or both system...

Page 22: ...24 Pump running 25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base value at which the system has been design...

Page 23: ...maintain the previous setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it is possible to place the boiler in stand by In this mode the boiler is considered powered on but no...

Page 24: ...re The error may be caused by a poor thermal probe contact or a system with excessive thermal inertia Press the Reset button 1 0A17 Poor thermal return NTC probe contact During boiler operation the bo...

Page 25: ...on incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one of the two...

Page 26: ...ned frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp cloths and neutral detergent to clean the boiler casi...

Page 27: ...ified check sealing efficiency of water circuits check ventilation and or aeration of the instal lation room where provided ensure the gas inlet working pressure is correct 1 1 Kpa Natural Gas 2 75 Kp...

Page 28: ...Fan M30 Three way valve optional Configure the corresponding parameters when connecting in simple cascade or when con necting in system side flow probe or D H W pump S1 Main switch Y1 Gas valve 1 Exte...

Page 29: ...10 Flue probe B25 System flow meter E4 Safety thermostat E5 Heat exchanger safety thermostat manual reset E13 Flue safety thermofuse M1 Boiler circulator pump M20 Fan S5 Absolute pressure switch S20 O...

Page 30: ...inlet Clean contact Max 230 Vac 1 A Key B1 System flow probe NTC B2 Domestic hot water probe NTC B4 External probe M2 Plant CH pump M30 3 way valve Note probe B1 B2 B4 Connection cable diameter 3 7 m...

Page 31: ...ve is open Incorrect adjustment of the gas valve check the correct calibration of the gas valve Irregular combustion or noisiness It may be caused by a dirty burner incorrect combustion parameters int...

Page 32: ...d by multiplying the value displayed by 50 P26 120 0 P12 Boiler s modulation ratio It defines the boiler s modulation ratio Do not modify 0 100 10 P13 Boiler power Used to calculate the boiler power i...

Page 33: ...46 P31 Unit of measurement This defines the unit of measure on the display whether metric or Imperial 0 127 C kW 128 256 F kBTu h 0 P32 Min Heating Set Temp Limits the minimum value of the heating se...

Page 34: ...e turn the adjustment screw 3 in a clockwise direction and vice versa to decrease it Calibration of maximum CO2 When you finish the minimum CO2 adjustment turn the boiler on and start the chimney swee...

Page 35: ...obe must be connected to terminals S1 and S2 and parameter P38 must be set up whereas the pump must be connected to termi nals C and D If there is a DHW circuit it can be connected via an external 3 w...

Page 36: ...e replaced at least every two years regardless of their state of wear Check that the burner is intact that it has no deformations or cuts and that it is properly fixed to the combustion chamber lid ot...

Page 37: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Page 38: ...38 3 15 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Page 39: ...43 6550 3 98 6450 49 0 223 1 5 32 6430 3 91 6330 47 0 213 4 5 09 6170 3 74 6060 45 0 204 0 4 87 5910 3 57 5810 43 0 194 6 4 64 5660 3 41 5550 41 0 185 4 4 42 5410 3 25 5300 39 0 176 3 4 21 5160 3 09 5...

Page 40: ...06 8 99 7 Efficiency 40 30 Nom Min 107 4 103 5 Heat loss at casing with burner Off On 80 60 C 0 30 0 90 Heat loss at flue with burner Off On 80 60 C 0 03 1 80 Central heating circuit max operating pre...

Page 41: ...41 INSTALLER USER MAINTENANCE TECHNICIAN 3 27 EXPLODED BOILER DIAGRAM 17 05 17 3 024493 5647076 SERIAL NUMBER START OF SERIES VICTRIX PRO 55 1 A 82D...

Page 42: ...r 10x5 2x1 90 1 8599 Washer 4 3x12 91 3 023387 Flue hood group 92 1 025278 Plug for flange with sample points 93 1 036108 Flue exhaust pipe d 80 94 1 020368 Lip gasket d 80 95 1 034463 Frame 96 1 0352...

Page 43: ...inhibitor was used Quantity Litres Has a system filter been installed Yes No HEATING MODE measure and record Burner inlet gas working pressure at maximum rate Kpa OR gas inlet pressure Kpa Central he...

Page 44: ...lights and heats the water Check gas flame is the correct colour and for gas and water leaks as the system heats up 11 Check that heat is circulating to all radiators through the manual or thermostat...

Page 45: ...ame Telephone No Plumbing Licence No Record At max rate CO ppm CO CO CO Ratio At mim rate CO ppm CO CO CO Ratio Comments Signature SERVICE 02 Date Engineer name Company name Telephone No Plumbing Lice...

Page 46: ...one No Plumbing Licence No Record At max rate CO ppm CO CO CO Ratio At mim rate CO ppm CO CO CO Ratio Comments Signature SERVICE 10 Date Engineer name Company name Telephone No Plumbing Licence No Rec...

Page 47: ......

Page 48: ...This instruction booklet is made of ecological paper Cod 1 039823 rev ST 002925 001 03 18 AS NZS 5263 1 2 Cert SAI 400090 SAI Global...

Reviews: