background image

16

B23

1-23

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

1.22 GAS SYSTEM START-UP.

To start up the system, refer to the technical 

standard in force: This divides the systems and 

therefore the start-up operations into three 

categories: new systems, modified systems, 

re-activated systems.

In particular, for new gas systems:

-  open windows and doors;
-  avoid presence of sparks or open flames;
-  bleed all air from the pipelines;
-  check the seal of the internal system by follow-

ing the instructions provided by the technical 

regulations in force (refer to the pertaining lo-

cal regulations for the "sealing test" on systems 

served by single or cascade generators with a 

nominal thermal capacity greater than 35 kW.

1.23 BOILER START UP (IGNITION).

In order to issue the Declaration of Conformity 

required by the regulations in force, one must 

fulfil the following requirements to commission 

the boiler (the operations listed below must only 

be performed by qualified personnel and in the 

presence of staff only):

-  check that the internal system is properly sealed 

according to the specifications set forth by 

regulations in force; Up to operating pressures 

of 40 mbar it is also possible to use the testing 

method adopted by the technical regulations 

in force for systems served by single appliances 

(or in cascade set-up), with nominal thermal 

capacities greater than 35 kW. For greater pres-

sure levels you will need to refer to legislation 

in force and/or other effectively tried and tested 

methods;

-  make sure that the type of gas used corresponds 

to boiler settings;

- check that there are external factors that may 

cause the formation of fuel pockets;

-   switch the boiler on and check correct ignition;
-  make sure the fan rpm matches the value pro-

vided in the book (Par. 3.17);

- ensure that the safety device intervenes in the 

event of gas supply failure and check the relative 
intervention time;

- check activation of the main switch located 

upstream from the boiler and in the boiler;

- check that the intake/exhaust concentric ter-

minal (if fitted) is not blocked.

The boiler must not be started up even if only 

one of the checks should be negative.

N.B.: 

the preliminary boiler check must be carried 

out by an authorised company. The standard boiler 

warranty is valid from the date of inspection.

The test certificate and warranty is issued to the 

user.

1.18 FLUE DUCT SYSTEMS FOR VOIDS 

AND CHIMNEYS.

Flue ducts may be installed in suitable voids or 

chimneys provided that the relevant building 

regulations permit this.  Flue ducting systems 

must be installed in strict accordance with the 

manufacturers instructions.

Immergas ducting system 80 Ø.

 The "Green 

Series" 80 Ø flexible ducting system must only be 

used with Immergas condensing boilers.

In any case, ducting operations must respect 

the provisions contained in the standard and in 

current technical regulations; in particular, the 

declaration of conformity must be compiled at 

the end of work and on commissioning of the 

ducted system. The instructions in the project 

or technical report must likewise be followed, in 

cases provided for by the standard and current 

technical regulations. The system or components 

of the system have a technical life complying with 

current standards, provided that:

- it is used in average atmospheric and envi-

ronmental conditions, according to current 

regulations (in particular, by the standards 

regarding: absence of combustion products, 

dusts or gases that can alter the normal ther-

mophysical or chemical conditions; existence 

of temperatures coming within the standard 

range of daily variation, etc.).

- Installation and maintenance must be per-

formed according to the indications supplied 

by the manufacturer and in compliance with 

the provisions in force.

- The max. possible length of the 80 Ø flexible 

ducting vertical section 

is equal to 28.0 m for 

Victrix Pro 80 1 I, 14.0 m for Victrix Pro 100 1 

I and 8.5 m for Victrix Pro 120 1 I

. This length 

is obtained considering the complete exhaust 

terminal, 1m of 80 Ø pipe in exhaust, two 90° 

80 Ø bends at the boiler outlet to connect to 

the ducting system and two direction changes 

of the flexible tube inside the flue/technical slot.

1.19 

FLUE EXHAUST WITH BOILERS IN 

CASCADE.

The boilers installed in cascade composed of 

any number between 2 and 5 boilers, can be 

manifolded to a unique flue exhaust pipe, which 

flows into a flue.

Immergas supplied an appropriate and original 

flue exhaust system separately to the boilers.

1.20 SYSTEM FILLING.

When the boiler has been connected, fill the sys-

tem. Filling is performed at low speed to ensure 

release of air bubbles in the water via the boiler 

and heating system vents.

The boiler incorporates two automatic vent 

valves fitted on the circulator pump and on the 

condensing module. Check if the cap is loose. 

Open the radiator vent valves. Close radiator 

vent valves when only water escapes from them. 

N.B.:

 during these operations start up the cir-

culation pump at intervals, acting on the main 

switch positioned on the control panel.

 Vent the 

circulation pump by loosening the front cap and 

keeping the motor running

. Tighten the cap after 

the operation.

Attention:

 this boiler is 

not

 equipped with an 

expansion vessel on the system. It is mandatory 

to install a closed expansion vessel to guarantee 

correct boiler operation. The expansion vessel 

must comply with the European Standards in 

force. The dimensions of the expansion vessel 

depend on the data relative to the central heating 

system. Install a vessel whose capacity responds 

to the requisites of the Standards in force (''R'' 

collection).

1.21 CONDENSATE TRAP FILLING.

On first lighting of the boiler combustion prod-

ucts may come out the condensate drain; after a 

few minutes’ operation check that this no longer 

occurs. This means that the trap is filled with 

condensate to the correct level preventing the 

passage of combustion products.

Exhaust

Exhaust

Summary of Contents for Victrix Pro 100 1 I

Page 1: ...VICTRIX PRO 80 100 120 1 I 1 036116ENG IE Instruction and warning book...

Page 2: ......

Page 3: ...ransfer or succession of ownership It must be stored with care and consulted carefully as all of the warnings provide important safety indications for installation use and maintenance stages This inst...

Page 4: ...DEX 2 Use and maintenance instructions 22 2 1 Cleaning and maintenance 22 2 2 Aeration and Ventilation of the installation rooms 22 2 3 General warnings 22 2 4 Control panel 23 2 5 Using the boiler 23...

Page 5: ...adequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In the case of walls made from hollow brick or block partitions with limite...

Page 6: ...tion rating and can also be installed outdoors without additional protections Attention all optional kits that can be potentially connected to the boiler must be protected on the basis of their electr...

Page 7: ...f the fuel Storage tanks in case of supply from LPG depot New LPG storage tanks may contain residual inert gases nitrogen that degrade the mixture delivered to the appliance causing problems with boil...

Page 8: ...on Immergas S p A declines any respon sibility for damage or physical injury caused by failure to connect the boiler to an efficient earth system or failure to comply with the reference standards Also...

Page 9: ...if external probe is present The zone manager is powered directly by the cascade heat adjuster via 2 wires Cascadeandzoneregulatorelectricconnection or On off chrono thermostat Optional Any thermosta...

Page 10: ...sealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble the 80 adapter the...

Page 11: ...t 1 3 m Terminal complete with vertical ex haust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric b...

Page 12: ...rder to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to look at on the outside of the b...

Page 13: ...the lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position...

Page 14: ...with this configuration can be extended up to a max measurement of 28 0 m with Victrix Pro 80 1 I 14 0 m with Victrix Pro 100 1 I and 8 5 m with Victrix Pro 120 1 I including the terminal Using the 8...

Page 15: ...plate has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the male side smoo...

Page 16: ...s in particular the declaration of conformity must be compiled at the end of work and on commissioning of the ducted system The instructions in the project or technical report must likewise be followe...

Page 17: ...is recommended to use the pump at maximum speed The circulation pump is already fitted with a capacitor Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew t...

Page 18: ...CHNICIAN Head available to the system Head kPa Head kPa Victrix PRO 100 1I Victrix PRO 120 1I Key A Head available to the system at maximum speed B Head available to the system at second speed Head m...

Page 19: ...9 Condensing module air vent valve 10 Flue probe 11 Condensation module 12 Fumes hood 13 Air intake pipe 14 Igniter 15 16 Heat exchanger safety thermal fuse 17 Ignition electrode 18 Detection electro...

Page 20: ...d block circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collecti...

Page 21: ...tral heating circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety therm...

Page 22: ...down of the boiler is required proceed as follows a drain the heating system if anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on...

Page 23: ...bol 23 Resettable presence of anomalies 24 Pump running 25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base va...

Page 24: ...t If a certain amount of time lapses without saving the value the boiler will exit setting mode and maintain the previous setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it...

Page 25: ...cts an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one of the two probes Press the Reset button 1 0A16 Poor thermal flow NTC probe c...

Page 26: ...urn NTC probe temperature detection incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caus...

Page 27: ...to the heating system water In systems that are drained frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp...

Page 28: ...ucts into the room even during function ing of fans check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices seal the gas flow rate regulation devices...

Page 29: ...not be restored in series with the electric power supply of the gas valve E4 Safety thermostat E13 Safety thermofuse G2 Igniter M1 Boiler circulator pump M20 Fan M30 Three way valve optional S1 Main s...

Page 30: ...radiator valves are not closed and also the functionality of the pump Also check the integrity of the thermofuse and if it has been triggered it will be necessary to check the integrity of the module...

Page 31: ...ion with a storage tank and a separate thermostat this defines the flow temperature during DHW operation 35 90 C 80 C P23 Modulazione sanitario DHW modulation Summed with the Set San P16 parameter thi...

Page 32: ...s After Sales Assistance 3 7 HEAT OUTPUT The boiler heat output is correlated to the length of the air intake and flue exhaust pipes This de creases slightly with the increase of pipe length 3 8 ADJUS...

Page 33: ...deposits are detected in the combustion chamber one must remove them and clean the exchanger coils using nylon or sorghum brushes it is forbidden to use brushes made of metal or other materials that...

Page 34: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Page 35: ...35 3 10 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Page 36: ...03 5580 61 0 52460 6 63 5550 4 87 5420 59 0 50740 6 42 5390 4 71 5250 57 0 49020 6 20 5230 4 55 5090 55 0 47300 5 98 5070 4 39 4930 53 0 45580 5 76 4910 4 23 4770 51 0 43860 5 55 4750 4 07 4610 49 0 4...

Page 37: ...40 6 68 5970 81 0 69660 8 78 5910 6 44 5760 78 0 67080 8 45 5680 6 20 5550 75 0 64500 8 12 5460 5 96 5340 72 0 61920 7 79 5240 5 72 5130 69 0 59340 7 47 5030 5 48 4930 66 0 56760 7 14 4810 5 24 4720 6...

Page 38: ...63 0 54180 6 83 4000 5 01 3900 60 0 51600 6 51 3830 4 78 3730 57 0 49020 6 18 3660 4 54 3560 54 0 46440 5 86 3490 4 30 3390 51 0 43860 5 54 3320 4 06 3230 48 0 41280 5 21 3150 3 83 3060 45 0 38700 4 8...

Page 39: ...mbar mm H2 O 20 204 37 377 Flue flow rate at nominal heat output kg h 146 148 Flue flow rate at min heat output kg h 16 16 CO2 at Q Nom Min 9 45 8 90 10 60 10 00 CO with 0 O2 at Nom Min Q Nom Min ppm...

Page 40: ...7 6 107 2 107 5 Heat loss at casing with burner On Off 80 60 C 0 34 0 80 0 41 0 60 0 28 0 70 Heat loss at flue with burner On Off 80 60 C 0 01 2 2 0 01 1 9 0 01 2 0 Central heating circuit max operati...

Page 41: ...Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type appliance configuration ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn m...

Page 42: ......

Page 43: ......

Page 44: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 036116ENG rev ST 000450 001 09...

Reviews: