background image

6

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

1.3  AERATION AND VENTILATION OF 

THE INSTALLATION ROOMS.

The rooms must have one or more permanent 

openings for aeration on external walls. The 

openings used for aeration can be protected 

using metal grills, meshes and/or rain-proof fins 

as long as the net aeration surface is not reduced.

The aeration openings must be realised and 

located in a way to prevent the formation 

of pockets of gas, independently from the 

conformation of the covering.

Aeration for installation in outdoor places.

 The 

minimum free surfaces, in relation to the overall 

heat input must not be below:

a)  above-ground rooms (S ≥ Q x 10)
    S > 755 cm

2

 for every Victrix Pro 80 1 I

    S > 925 cm

2

 for every Victrix Pro 100 1 I

    S > 1145 cm

2

 for every Victrix Pro 120 1 I

    (ex: to install 3 Victrix Pro 80 1 I in cascade, 

the minimum surface is 755 x 3 = 2265 cm

2

)

b)  basements and underground rooms up to a 

height of -5 m from the reference surface (S 

≥ Q x 15).

    S > 1130 cm

2

 for every Victrix Pro 80 1 I

    S > 1385 cm

2

 for every Victrix Pro 100 1 I

    S > 1712 cm

2

 for every Victrix Pro 120 1 I

    (ex: to install 3 Victrix Pro 80 1 I in cascade, 

the minimum surface is 1130 x 3 = 3390 cm

2

)

c)  underground rooms at quota between -5 m 

and -10 m from the reference surface (S ≥ Q 

x 20 with a minimum of 5000 cm

2

).

    S > 5000 cm

2

 for all configurations

In all cases each opening must not have a net 

surface area less than 100 cm

2

.

Attention:

 in the case of installation of appliances 

powered with gas with greater density than 0.8 

(L.P.G.) in outdoor places, above-ground, at least 

2/3 of the aeration surface must be flush with the 

floor, with a minimum height of 0.2 m.

The aeration openings must be at least 2 m for 

heating capacities not exceeding 116 kW and 

4.5 m for higher heating capacities, cavities, 

depressions or openings communicating with 

rooms below the walkway surface or draining 

ducts.

Aeration for installation in buildings also 

destined for other use or in places inserted in 

the volume of the building served.

 The aeration 

surface must not be less than 3000 cm

2

 in the case 

of natural gas and must not be less than 5000 cm

2

 

in the case of L.P.G..
The installation must comply with the 

requirements of all relevant codes and standards.

1.4  OUTDOOR INSTALLATION.

The boiler has an IPX5D electric insulation 

rating and can also be installed outdoors, without 

additional protections.

Attention:

 all optional kits that can be potentially 

connected to the boiler must be protected on the 

basis of their electrical protection rating.

1.5  ANTI-FREEZE PROTECTION.

Minimum temperature -5°C.

 The boiler comes 

standard with an anti-freeze function that 

activates the pump and burner when the system 

water temperature in the boiler falls below 5°C.

The anti-freeze function is only guaranteed if:

- the boiler is correctly connected to gas and 

electricity power supply circuits;

- the boiler is powered constantly;
- Main switch is inserted;
- the boiler is not in no ignition block (Par.
-  the boiler essential components are not faulty.

In these conditions the boiler is protected against 

freezing to an ambient temperature of -5°C.

Minimum temperature -15°C.

 If the boiler is 

installed in a place where the temperature falls 

below -5°C and in the event there is no gas (or 

the boiler goes into failed ignition block), the 

appliance can freeze.

To prevent the risk of freezing follow the 

instructions below:

- protect the central heating circuit from freezing 

by introducing a top quality anti-freeze liquid 

into this circuit, which is not noxious to health. 

The instructions of the manufacturer of this 

liquid must be followed scrupulously regarding 

the percentage necessary with respect to the 

minimum temperature at which the system 

must be kept. An aqueous solution must be 

made with a potential water pollution class 

of 2 (EN 1717).

The materials used for the central heating circuit

 

of Immergas boilers withstand ethylene and 

propylene glycol based antifreeze liquids (if the 

mixtures are prepared perfectly).

For life and possible disposal, follow the supplier’s 

instructions.

- Protect the condensate drain trap and relative 

drain against freezing by using an accessory 

supplied on request (anti-freeze kit) comprising 

two electric resistances, the relevant cables 

and a control thermostat (carefully read the 

installation instructions contained in the 

accessory kit pack).

Boiler anti-freeze protection is thus ensured only if:

- the boiler is correctly connected to electricity 

power supply circuits;

-  Main switch is inserted;
-  the anti-freeze kit components are efficient.
In these conditions the boiler is protected against 

freezing to temperature of -15°C.

The warranty does not cover damage due to 

interruption of the electrical power supply and 

failure to comply with that stated on the previous 

page.

Summary of Contents for Victrix Pro 100 1 I

Page 1: ...VICTRIX PRO 80 100 120 1 I 1 036116ENG IE Instruction and warning book...

Page 2: ......

Page 3: ...ransfer or succession of ownership It must be stored with care and consulted carefully as all of the warnings provide important safety indications for installation use and maintenance stages This inst...

Page 4: ...DEX 2 Use and maintenance instructions 22 2 1 Cleaning and maintenance 22 2 2 Aeration and Ventilation of the installation rooms 22 2 3 General warnings 22 2 4 Control panel 23 2 5 Using the boiler 23...

Page 5: ...adequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In the case of walls made from hollow brick or block partitions with limite...

Page 6: ...tion rating and can also be installed outdoors without additional protections Attention all optional kits that can be potentially connected to the boiler must be protected on the basis of their electr...

Page 7: ...f the fuel Storage tanks in case of supply from LPG depot New LPG storage tanks may contain residual inert gases nitrogen that degrade the mixture delivered to the appliance causing problems with boil...

Page 8: ...on Immergas S p A declines any respon sibility for damage or physical injury caused by failure to connect the boiler to an efficient earth system or failure to comply with the reference standards Also...

Page 9: ...if external probe is present The zone manager is powered directly by the cascade heat adjuster via 2 wires Cascadeandzoneregulatorelectricconnection or On off chrono thermostat Optional Any thermosta...

Page 10: ...sealed chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble the 80 adapter the...

Page 11: ...t 1 3 m Terminal complete with vertical ex haust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric b...

Page 12: ...rder to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to look at on the outside of the b...

Page 13: ...the lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position...

Page 14: ...with this configuration can be extended up to a max measurement of 28 0 m with Victrix Pro 80 1 I 14 0 m with Victrix Pro 100 1 I and 8 5 m with Victrix Pro 120 1 I including the terminal Using the 8...

Page 15: ...plate has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the male side smoo...

Page 16: ...s in particular the declaration of conformity must be compiled at the end of work and on commissioning of the ducted system The instructions in the project or technical report must likewise be followe...

Page 17: ...is recommended to use the pump at maximum speed The circulation pump is already fitted with a capacitor Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew t...

Page 18: ...CHNICIAN Head available to the system Head kPa Head kPa Victrix PRO 100 1I Victrix PRO 120 1I Key A Head available to the system at maximum speed B Head available to the system at second speed Head m...

Page 19: ...9 Condensing module air vent valve 10 Flue probe 11 Condensation module 12 Fumes hood 13 Air intake pipe 14 Igniter 15 16 Heat exchanger safety thermal fuse 17 Ignition electrode 18 Detection electro...

Page 20: ...d block circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collecti...

Page 21: ...tral heating circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety therm...

Page 22: ...down of the boiler is required proceed as follows a drain the heating system if anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on...

Page 23: ...bol 23 Resettable presence of anomalies 24 Pump running 25 Summer mode 2 5 USING THE BOILER Before ignition make sure that the system is full of water checking that the manometer 5 indicates a base va...

Page 24: ...t If a certain amount of time lapses without saving the value the boiler will exit setting mode and maintain the previous setting 2 4 2 5 Stand by mode by pressing buttons A and C at the same time it...

Page 25: ...cts an anomalous difference between the NTC probe flow and return temperatures The error may be caused by a failure in one of the two probes Press the Reset button 1 0A16 Poor thermal flow NTC probe c...

Page 26: ...urn NTC probe temperature detection incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow and return temperatures The error may be caus...

Page 27: ...to the heating system water In systems that are drained frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 12 CASE CLEANING Use damp...

Page 28: ...ucts into the room even during function ing of fans check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices seal the gas flow rate regulation devices...

Page 29: ...not be restored in series with the electric power supply of the gas valve E4 Safety thermostat E13 Safety thermofuse G2 Igniter M1 Boiler circulator pump M20 Fan M30 Three way valve optional S1 Main s...

Page 30: ...radiator valves are not closed and also the functionality of the pump Also check the integrity of the thermofuse and if it has been triggered it will be necessary to check the integrity of the module...

Page 31: ...ion with a storage tank and a separate thermostat this defines the flow temperature during DHW operation 35 90 C 80 C P23 Modulazione sanitario DHW modulation Summed with the Set San P16 parameter thi...

Page 32: ...s After Sales Assistance 3 7 HEAT OUTPUT The boiler heat output is correlated to the length of the air intake and flue exhaust pipes This de creases slightly with the increase of pipe length 3 8 ADJUS...

Page 33: ...deposits are detected in the combustion chamber one must remove them and clean the exchanger coils using nylon or sorghum brushes it is forbidden to use brushes made of metal or other materials that...

Page 34: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Page 35: ...35 3 10 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Page 36: ...03 5580 61 0 52460 6 63 5550 4 87 5420 59 0 50740 6 42 5390 4 71 5250 57 0 49020 6 20 5230 4 55 5090 55 0 47300 5 98 5070 4 39 4930 53 0 45580 5 76 4910 4 23 4770 51 0 43860 5 55 4750 4 07 4610 49 0 4...

Page 37: ...40 6 68 5970 81 0 69660 8 78 5910 6 44 5760 78 0 67080 8 45 5680 6 20 5550 75 0 64500 8 12 5460 5 96 5340 72 0 61920 7 79 5240 5 72 5130 69 0 59340 7 47 5030 5 48 4930 66 0 56760 7 14 4810 5 24 4720 6...

Page 38: ...63 0 54180 6 83 4000 5 01 3900 60 0 51600 6 51 3830 4 78 3730 57 0 49020 6 18 3660 4 54 3560 54 0 46440 5 86 3490 4 30 3390 51 0 43860 5 54 3320 4 06 3230 48 0 41280 5 21 3150 3 83 3060 45 0 38700 4 8...

Page 39: ...mbar mm H2 O 20 204 37 377 Flue flow rate at nominal heat output kg h 146 148 Flue flow rate at min heat output kg h 16 16 CO2 at Q Nom Min 9 45 8 90 10 60 10 00 CO with 0 O2 at Nom Min Q Nom Min ppm...

Page 40: ...7 6 107 2 107 5 Heat loss at casing with burner On Off 80 60 C 0 34 0 80 0 41 0 60 0 28 0 70 Heat loss at flue with burner On Off 80 60 C 0 01 2 2 0 01 1 9 0 01 2 0 Central heating circuit max operati...

Page 41: ...Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type appliance configuration ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn m...

Page 42: ......

Page 43: ......

Page 44: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 036116ENG rev ST 000450 001 09...

Reviews: