26
INS
TALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
Error
Code
Anomaly signalled
Cause
Solution
0E2
Parasite flame block
This occurs during the power-on phase in the event of a leak on the
detection circuit or anomaly in the flame control unit.
(2) (1)
0E8
Flame circuit anomaly
During the ignition phase an anomaly was detected on the electronic
flame control circuit and the boiler switches off.
(2) (1)
0E21
P.C.B. error
An error is detected on the P.C.B. and the boiler does not start up
(2) (1)
0E25
P.C.B. error
An error is detected on the P.C.B. and the boiler does not start up
(2) (1)
0E32
DHW NTC probe in
short circuit
The board detects a short circuit on the DHW NTC probe
(2) (1)
0E33
DHW NTC probe
outside the operating
range
The board detects an open contact on the DHW NTC probe.
(2) (1)
0E34
Low power supply
voltage
This occurs when the power supply voltage is lower than the allowed
limits for the correct boiler operation.
(2) (1)
0E37
Insufficient system
pressure
If the system pressure is too low the boiler switches off.
Check on the boiler pressure gauge (1)
that the system pressure is between 1÷1.2
bar and restore the correct pressure if
necessary.
(2) (1)
0E45
Flue NTC probe in
short circuit
The board detects a short circuit on the flue NTC probe.
(2) (1)
0E46
Flue NTC probe
outside the operating
range
The board detects an open contact on the flue NTC probe.
(2) (1)
0E81
Flow and return NTC
probe temperature
detection incorrect (in
stand-by)
With the boiler in stand-by, the board detects an anomalous difference
between the NTC probe flow and return temperatures. The error may
be caused by a failure in one of the two probes
(2) (1)
(1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical After-Sales Service).
(2) If normal operating conditions are restored, the boiler re-starts without having to be reset.
Error
Code
Anomaly signalled
Cause
Solution
FE90
The P.C.B. is not com-
patible
An incompatibility between the boiler's P.C.B. and the display board
has been detected.
Check the P.C.B.s. (2) (1)
FE94
Display board anomaly
An error is detected on the display's P.C.B..
(2) (1)
FE95
Flow NTC probe
short-circuited or out
of range
The board detects an incorrect value on the flow NTC probe.
(2) (1)
FE96
External probe
anomaly
An anomaly is detected on the external probe.
Check the boiler configuration, check
the external probe (2) (1)
FE97
Configuration error
P.C.B. configuration error.
This may happen when the P.C.B. is changed.
Check the configuration parameters
(when the P.C.B. is reconfigured, press
and hold the “-” (fig. 2-1 ref. 2) button
down until "AUTO" appears, then press
"RESET" until “bu 1” appears). (2) (1)
FE99
Internal communica-
tion anomaly
A communication error has been detected between the display board
and the boiler's P.C.B..
(2) (1)
(1) If the block or anomaly persists, contact an authorised company (e.g. Immergas Technical After-Sales Service).
(2) If normal operating conditions are restored, the boiler re-starts without having to be reset.
Summary of Contents for Victrix Pro 100 1 I