background image

13

INS

TALL

AT

O

R

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

2.5  USING THE BOILER.

Before ignition, make sure the heating system 

is filled with water and that the manometer (7) 

indicates a pressure of 1 ÷ 1.2 bar.

- Open the gas cock upstream from the boiler.
- Press the button (2) until the display switches 

on, after which press the button in sequence 

(2) and take the boiler to the summer (

or winter (

) position.

• 

Summer 

(

)

:

 in this mode the boiler fun-

ctions only to produce the DHW, the tempera-

ture is set via the buttons (3-4) and the relative 

temperature is shown on the display via the 

indicator (16). 

• Winter 

(

)

:

 in this mode the boiler functions 

both for producing domestic hot water and 

heating the environment. The temperature of 

the DHW is always regulated via buttons (3-4), 

the heating temperature is regulated via buttons 

(5-6) and the relative temperature is shown on 

the display via the indicator (16).

From this moment the boiler functions auto-

matically. With no demand for heat (heating 

or domestic hot water production) the boiler 

goes to “standby” function, equivalent to the 

boiler being powered without presence of flame. 

Each time the burner ignites, the relative flame 

present symbol is displayed (10) with relative 

power scale. 

• 

Operation with Comando Amico Remoto 

remote control

V2

 (CAR

V2

) (Optional)

. If the 

CAR

V2

 is connected, the (

) symbol will 

appear on the display. The boiler regulation pa-

rameters can be set via the CAR

V2

 control panel 

and the reset button (1) remains active on the 

boiler control panel, along with the switch-off 

button (2) (“off” mode only) and the display 

where the functioning state is shown.

 

Important:

 if the boiler is put into “off” mode 

on the CAR

V2

 the “CON” connection error 

symbol will appear on the CAR. The CAR

V2

 is 

however powered constantly so as not to loose 

memorised programs.

• 

Functioning with optional external probe 

(

)

.

 In the case of a system with optional 

external probe, the boiler flow temperature for 

room central heating is managed by the exter-

nal probe depending on the external tempera-

ture measured (Par. 1.6). The flow temperature 

can be modified by selecting the functioning 

curve via buttons (5 and 6), selecting a value 

from “0 to 9” (Fig. 1-5).

  With external probe present, the relative 

symbol will appear on the display (12). In the 

central heating phase, if the temperature of the 

water contained in the system is sufficient to 

heat the radiators, the boiler can only function 

with the activation of the pump.

• 

“Stand-by” mode.

 Press button (2) in suc-

cession until the (

) symbol appears. The 

boiler remains active from this moment and the 

anti-freeze function, pump anti-block function 

and 3-way and signalling of any anomalies is 

guaranteed.

 

N.B.:

 in these conditions the boiler is conside-

red still live.

• 

“Off” mode.

 The safety functions are not 

guaranteed in this mode.

 

N.B.:

 in these conditions the boiler is consi-

dered still live even if there are no functions 

active.

• 

Display functioning. 

The display lights up 

during the use of the control panel, after 15 se-

conds inactivity, the brightness drops until just 

the active symbols are displayed. The lighting 

mode can be varied via parameter P2 in the 

circuit board customisation menu.

2.6 TROUBLESHOOTING.

The boiler signals out anomalies by flashing on 

the display and relative error codes, listed on the 

table, are displayed. On any remote controls, the 

error code will be displayed using a numerical 

code preceded or followed by the letter E (e.g. 

CAR

V2

= Exx).

Code dis-

played

(flashing)

Anomaly signalled

Cause

Boiler status / Solution

01

No ignition block:

In the event of request of room central heating or domestic hot 

water production, the boiler does not switch on within the preset 

time. Upon appliance commissioning or after extended downtime, 

it may be necessary to eliminate the block.

Press the Reset button (1).

02

Safety thermostat 

block (over-temper-

ature)

During normal operation, if a fault causes excessive overheating 

internally, the boiler goes into overheating block.

After an appropriate cooling press the Reset 

button (1).

03

Flue safety thermostat 

block

During normal operation, if a fault causes excessive flue gas overheat-

ing, the boiler blocks

After an appropriate cooling press the Reset 

button (1)

The boiler will automatically restart after 30 

minutes if normal conditions resume with-

out having to be reset. After three trippings 

of the flue safety thermostat in less than two 

hours the boiler requires a manual reset to 

restart; press the Reset button (1).

04

General boiler board 

anomaly

The P.C.B. detects a malfunction of the safety thermostat, of the flue 

pressure switch or of the system pressure switch.

Press the Reset button (1).

05

Flow probe anomaly

The board detects an anomaly on the flow NTC probe.

The boiler does not start (1).

06

Domestic hot water 

probe anomaly

The board detects an anomaly on the domestic hot water NTC probe. 

In this case the antifreeze function is also inhibited.

In this case the boiler continues to produce 

domestic hot water but not with optimal 

performance (1)

08

Maximum N° of reset

Number of allowed resets that have already performed.

Attention: 

the anomaly can be reset 5 times 

consecutively, after which the function in 

inhibited for at least one hour. One attempt 

is gained every hour for a maximum of 5 

attempts. By switching the appliance on and 

off again, the 5 attempts are re-acquired.

10

Insufficient system 

pressure

Insufficient water pressure inside the central heating circuit is detected 

to guarantee correct boiler operation.

Check on the boiler pressure gauge (1) that 

the system pressure is between 1÷1.2 bar 

and restore the correct pressure if necessary

15

Configuration error

If the board detects an anomaly or incongruity on the electric wiring, 

the boiler will not start.

If normal conditions are restored the boiler 

restarts without having to be reset. Check 

that the boiler is configured correctly (1).

20

Parasite flame block

This occurs in the event of a leak on the detection circuit or anomaly 

in the flame control unit.

Press the Reset button (1)

(1) If the shutdown or fault persists, contact an authorised company (e.g. Technical After-Sales Service).

Summary of Contents for MINI NIKE 24 4 ERP

Page 1: ... IE 1 038450ENG MINI NIKE 24 4 ERP Instantaneous wall hung boilers with open chamber type B and natural draught The European regulation 813 2013 provides that this boiler can be installed only to replace similar equipment connected to existing branched multiple flues ...

Page 2: ......

Page 3: ...ovisions specified in the current regulation and technical standards In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by an authorised company which has specifi...

Page 4: ...m pressure 14 2 9 System draining 14 2 10 Anti freeze protection 14 2 11 Case cleaning 14 2 12 Decommissioning 14 3 Boiler start up initial check 15 3 1 Hydraulic diagram 15 3 2 Wiring diagram 16 3 3 Troubleshooting 16 3 4 Information menu 17 3 5 Programming the p C B 17 3 6 Converting the boiler to other types of gas 18 3 7 Checks following conversion to another type of gas 18 3 8 Possible adjust...

Page 5: ... there are leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appliances For the aforementioned reasons we recommend not placing furnishings furniture etc under the boiler In the event of malfunctions faults or incorrect operation turn the appliance off immediately and contact a qualified technician e g the Im mer...

Page 6: ...cifications as shown on the boiler data plate Boilers are supplied complete with an X type power cable without plug The power supply cable must be connected to a 230V 10 50Hz mains supply respecting L N polarity and earth connection This network must also have an omnipolar circuit breaker with class III over voltage category When replacing the power supply cable contact a qualified company e g the...

Page 7: ... 3 2 Make sure that the On Off thermostat contact is of the clean type i e independent of the mains supply otherwise the electronic adjustment card would be damaged Any Comando Amico Remoto remote controlV2 must be connected to clamps 40 and 41 elimi nating jumper X40 on the circuit board paying attention not to invert the connections Fig 3 2 Important if the Comando Amico Remoto remote controlV2 ...

Page 8: ...ves only when water es capes from them Closethefillingvalvewhentheboilermanometer indicates approx 1 2 bar N B during these operations start up the cir culation pump at intervals acting on the main switch positioned on the control panel Vent the circulation pump by loosening the front cap and keeping the motor running Tighten the cap after the operation 1 12 GAS SYSTEM START UP To start up the sys...

Page 9: ...by pass turn anti clockwise to open it Display of operation status During normal operation the status LED 2 is on green the four yellow LEDs 3 indicate circulator absorption according to the following table Circulating pump LED Absorption G Y Y Y Y On On Off Off Off 0 25 G Y Y Y Y On On On Off Off 25 50 G Y Y Y Y On On On On Off 50 75 G Y Y Y Y On On On On On 75 100 Selection of operating mode To ...

Page 10: ...thout having to empty the entire system Polyphosphatedispenserkit Thepolyphospha tedispenserreducestheformationoflime scale and preserves the original heat exchange and domestic hot water production conditions The boiler is prepared for application of the polyphosphate dispenser kit The above mentioned kits are supplied complete with instructions for assembly and use Total head available to the sy...

Page 11: ...stic hot water probe 7 System filling valve 8 Flue safety thermostat 9 Flow probe 10 Primary heat exchanger 11 Safety thermostat 12 Combustion chamber 13 Ignition and detection electrodes 14 System expansion vessel 15 Burner 16 Vent valve 17 DHW heat exchanger 18 Three way valve motorised 19 System draining valve 20 By pass 21 3 bar safety valve N B connection group optional ...

Page 12: ...ue to the danger operation is also prohibited in the same room as suction devices or the like at the same time as the boiler unless there are additional openings dimensioned in a way to satisfy the additional requirement for air For the dimensioning of these additional openings refer to an authorised company Important the use of components that employ electrical power requires some fundamental rul...

Page 13: ...nel after 15 se conds inactivity the brightness drops until just the active symbols are displayed The lighting mode can be varied via parameter P2 in the circuit board customisation menu 2 6 TROUBLESHOOTING The boiler signals out anomalies by flashing on the display and relative error codes listed on the table are displayed On any remote controls the error code will be displayed using a numerical ...

Page 14: ...cal After Sales Service 2 7 BOILER SHUTDOWN For complete boiler switch off press the off button disconnect the onmipolar switch outside of the boiler and close the gas cock upstream from the appliance Never leave the boiler switched on if left unused for prolonged periods 2 8 RESTORE CENTRAL HEATING SYSTEM PRESSURE Periodically check the system water pressure The boiler pressure gauge should read ...

Page 15: ...he exit of the appliance combustion products check that there is no backflow of combustion products into the room even during functio ning of fans 3 1 HYDRAULIC DIAGRAM ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified check the production of domestic hot water check sealing efficiency of water circuits check ventilation and or aeration ...

Page 16: ...urner or the boiler lamellar pack Frequent interventions of the over heat ing safety thermostat It can depend on the lack of water in the boiler little water circulation in the system or blocked pump Check on the manometer that the sys tem pressure is within established limits Check that the radiator valves are not closed and also the functionality of the pump The boiler produces condensate This c...

Page 17: ...etting 0 instant boiler 1 boiler with storage tank 0 Illuminazione display Stabilisce la modalità di illuminazione del display Display lighting P2 Range of values which can be set Standard setting 0 Off 1 Auto 2 On 1 Off the display is always lit with low intensity Auto the display lights up during use and low ers after 15 seconds of inactivity In the case of anomaly the display flashes On the dis...

Page 18: ...o convert to another type of gas the following operations are required remove the voltage from the appliance replace the main burner injectors making sure to insert the special seal rings supplied in the kit between the gas manifold and the injectors apply voltage to the appliance use the boiler push button control panel to select the gas parameter type G1 and select Ng in case of Methane supply o...

Page 19: ...tivation is sig nalled by the indication of the flow temperature and the flashing and symbols This function allows the technician to check the combustion parameters Once the function is activated it is possible to select whether to perform the check in CH status regulating the parameters with buttons 5 and 6 or in DHW mode opening any DHW cock and always regu late the parameters with the buttons 5...

Page 20: ...litate boiler maintenance the casing can be completely removed as follows Fig 3 4 3 5 1 Unhook the decorative frame a from the relative lower retainers 2 Remove the decorative frame a from the casing c 3 Loosen the 2 front screws b for fixing the casing 4 Loosen the 2 lower screws d for fixing the casing 5 Pull the case towards yourself c 6 Push the case c upwards at the same time to release it fr...

Page 21: ...21 3 5 4 4 5 6 6 d d c INSTALLATOR USER MAINTENANCE TECHNICIAN ...

Page 22: ...Check that the system static pressure with system cold and after refilling the system by means of the filling valve is between 1 and 1 2 bar Visually check that the safety and control devices have not been tampered with and or shorted in particular temperature safety thermostat water pressure switch flue exhaust control thermostat Check the condition and integrity of the elec trical system and in ...

Page 23: ...al head available with 1000 l h flow rate kPa m H2 O 27 3 2 78 Hot water production useful heat output kW kcal h 23 8 20468 Domestic hot water adjustable temperature C 30 60 Min pressure dynamic domestic hot water circuit bar 0 3 Domestic hot water circuit max working pressure bar 10 Minimum D H W flow rate l min 1 5 Drawing capacity in continuous duty T 30 C l min 11 4 Weight of full boiler kg 28...

Page 24: ...ber CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum heating capacity domestic Qn min Minimum heating capacity heating Qnw max Maximum heating capacity domestic Qn max Maximum heating capacity heating Pn min Minimum heat output Pn max Maximum heat output PMS Maximum pressure system PMW Maximum pressure domestic D Specific flow rate TM Maximum working temperature...

Page 25: ...artial load elmin 0 014 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 003 kW Emissions of nitrogen oxides NOX 135 mg kWh For mixed central heating appliances Stated load profile XL Domestic hot water production efficiency ηWH 76 Daily electrical power consumption Qelec 0 158 kWh Daily gas consumption Qfuel 26 271 kWh Contact information IMMERGAS S p A VIA CISA LIGURE 95...

Page 26: ...lementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C From fiche of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is...

Page 27: ...he energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further factors such as heal loss in the distribution system and the dimensioning of the products in rela tion to building size and characteristics Seasonal space heating energy efficiency of package Seasonal s...

Page 28: ... contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once inst...

Page 29: ...ency under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ____ ____ ____ Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of ...

Page 30: ......

Page 31: ......

Page 32: ...immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038450ENG rev ST 002265 001 07 17 Inglese per IRLANDA IE ...

Reviews: