8
INS
TALL
AT
O
R
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
1.9 EVACUATION OF COMBUSTION
PRODUCTS: FLUE DUCT AND
BRANCHED MULTIPLE FLUES
The European regulation 813/2013 provides that
this boiler can be installed only to replace simi-
lar equipment connected to existing branched
multiple flues.
Connection to branched multiple flues.
Fitting the appliances to a branched multiple flues
takes place by means of flue ducts.
In the event of fittings with pre-existing flues,
these must be in safe and efficient status and per-
fectly clean because the detachment of any waste
from the walls during functioning, could block
the passage of flue gases, thus causing extremely
dangerous situations for the user.
The flue ducts must be connected to the chimney
or flue in the same room in which the appliance
is installed or, at most, in the adjoining room and
must comply with the requirements indicated by
the current technical regulations.
1.10 FLUE EXHAUST CONTROL DEVICE
Important:
it is prohibited to put the fumes
exhaust control device out of order voluntarily.
Every piece of this device must be replaced using
original spare parts if they have deteriorated. In
the case of repeated interventions of the fumes
exhaust control device, check the fumes exhaust
flue and the ventilation of the room in which the
boiler is located.
1.11 SYSTEM FILLING.
Once the boiler is connected, fill the system via
the filling valve (Fig. 2-2). Filling is performed
at low speed to ensure release of air bubbles in
the water via the boiler and heating system vents.
The boiler has a built-in automatic venting valve
on the circulator. Open the radiator vent valves.
Close radiator vent valves only when water es-
capes from them.
Close the filling valve when the boiler manometer
indicates approx. 1.2 bar.
N.B.:
during these operations start up the cir-
culation pump at intervals, acting on the main
switch positioned on the control panel.
Vent the
circulation pump by loosening the front cap and
keeping the motor running.
Tighten the cap after the operation.
1.12 GAS SYSTEM START-UP.
To start up the system, make reference to the
Standard.
In particular, for new gas systems:
- open windows and doors;
- avoid presence of sparks or naked flames;
- bleed all air from pipelines;
- check that the internal system is properly sealed
according to the specifications set forth by
technical regulations in force.
1.13 BOILER START UP (IGNITION).
To commission the boiler (the operations listed
below must only be performed by a qualified firm
and without any unauthorised persons):
- check that the internal system is properly sealed
according to the specifications set forth by
technical regulations in force;
- make sure that the type of gas used corresponds
to boiler settings;
- check that there are no external factors that
may cause the formation of fuel pockets;
- switch the boiler on and check correct ignition;
- make sure that the gas flow rate and relevant
pressure values comply with those given in the
manual (par. 3.18);
- check the correct ventilation of the rooms;
- check the existing draught during normal
functioning of the appliance, e.g. a draught
gauge positioned at the exit of the appliance
combustion products;
- check that there is no backflow of combustion
products into the room, even during function-
ing of fans;
- ensure that the safety device is engaged in the
event of gas supply failure and check activation
time;
- check activation of the main switch located
upstream from the boiler.
The boiler must not be started up even if only
one of the checks should be negative.
Summary of Contents for MINI NIKE 24 4 ERP
Page 2: ......
Page 21: ...21 3 5 4 4 5 6 6 d d c INSTALLATOR USER MAINTENANCE TECHNICIAN ...
Page 30: ......
Page 31: ......