background image

14

C82

1-22

C42

C52

1-23

1-25

C82

1-24

4

6

5

1

3

2

7

8

5

9

7

A

S

INS

TALLER

US

ER

 MAINTEN

AN

CE TECHNI

CI

AN

1.12 SEPARATOR KIT INSTALLATION.

Type C configuration, sealed chamber and 

fan assisted.

This kit allows air to come in from outside 

the building and the exhaust to exit from the 

chimney or flue through divided flue exhaust 

and air intake pipes. Combustion products are 

expelled from pipe (S). The required amount of 

air is taken in through pipe (A) for combustion. 

The intake pipe (A) can be installed either on the 

right or left hand side of the central exhaust pipe 

(S). Both ducts can be routed in any direction.

• 

Separator kit Ø 80/80. 

Kit assembly (Fig. 1-22): 

install the flange (4) on the central hole of the 

boiler, interposing the gasket (1) and tighten 

with the flat-tipped hex screws included in the 

kit. Remove the flat flange present in the lateral 

hole with respect to the central one (according 

to needs) and replace it with the flange (3), 

positioning the gasket (2) already present in 

the boiler and tighten using the supplied self-

threading screws. Fit the male end (smooth) to 

the bends (5) in the female end of the flanges 

(3 and 4). Fit the intake terminal (6) with the 

male section (smooth) in the female section of 

the bend (5) up to the stop, ensuring that the 

internal and external wall sealing plates are 

fitted. Fit the exhaust pipe (9) with the male end 

(smooth) to the female end of the bend (5) up 

to the stop; making sure that the internal wall 

sealing plate has been fitted, this will ensure 

sealing and joining of the elements making up 

the kit.

• Installation clearances. Figure 1-23 gives the 

min. installation space dimensions of the 

Ø 80/80 separator terminal kit in limited 

conditions.

• Figure 1-24 shows the configuration with 

vertical exhaust and horizontal intake.

•  Extensions for separator kit Ø 80/80. The max. 

vertical linear length (without bends) usable 

for Ø 80 intake and exhaust pipes is 41 metres 

of which 40 intake and 1 exhaust. This total 

The kit includes:

 N°1  -  Exhaust gasket (1)

 N°1  -  Female intake flange (3)

 N°1  -  Flange gasket (2)

 N°1  -  Female exhaust flange (4)

 N°2  -  90° bend Ø 80 (5)

 N°1  -  Intake terminal Ø 80 (6)

 N°2  -  Internal wall sealing plates (7)

 N°1  -  External wall sealing plate (8)

 N°1  -  Exhaust pipe Ø 80 (9)

Maximum usable lengths

(including intake terminal with grill and two 90° bends) 

NON-INSULATED PIPE

INSULATED PIPE

Drain (metres)

Intake (metres)

Drain (metres)

Intake (metres)

1

36.0*

6

29.5*

2

34.5*

7

28.0*

3

33.0*

8

26.5*

4

32.0*

9

25.5*

5

30.5*

10

24.0*

*  The air intake pipe can be increased to 2.5 metres if the exhaust bend 

is eliminated, 2 metres if the air intake bend is eliminated, 4.5 metres 

eliminating both bends.

11

22.5*

12

21.5*

Attention:

 the boiler is designed to evacuate 

the combustion products up to a maximum 

extension of 27 linear metres from the exhaust, 

with 1 m plus 90° bend at the intake. If the 

installation requests a development of the flue 

to the discharge that exceeds the recommended 

12 m, due consideration must be given to the 

formation of condensate that could take place 

inside the pipe and Immergas insulated “Blue 

Series” flue kits must be used.

Summary of Contents for Mini Eolo 24 3 E

Page 1: ...MINI EOLO 24 3E Instruction and warning book IE 1 038773ENG ...

Page 2: ......

Page 3: ... installing the Immergas kit As for the other issues related to boiler installation e g safety in the work site environment protection injury prevention it is necessary to comply with the provisions specified in the current regulation and technical standards In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by ...

Page 4: ...al warnings 19 2 3 Control panel 19 2 4 Using the boiler 20 2 5 Fault and anomaly signals 20 2 6 Boiler shutdown 21 2 7 Restore heating system pressure 21 2 8 Draining the system 21 2 9 Anti freeze protection 21 2 10 Case cleaning 21 2 11 Decommissioning 21 3 Commissioning the boiler initial check 22 3 1 Hydraulic Diagram 22 3 2 Wiring diagram 23 3 3 Troubleshooting 23 3 4 Information Menu 24 3 5 ...

Page 5: ...s plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safety valve intervenes with obstructed conveying system the safety valve must be conveyed away by a draining funnel or if there are leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appliances For th...

Page 6: ...uit from freezingbyintroducingatopqualityanti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollution class of water 2 The materials used for the...

Page 7: ...fully clean the heating system pipes radiators etc with special pickling or de scaling products to remove any deposits that could compromise correct boiler operation A chemical treatment of the thermal system water is required in compliance with the technical standards in force in order to protect the system and the appliance from deposits e g lime scale slurry or other hazardous deposits Water co...

Page 8: ...or the transmission of data between boiler and chrono thermostat Comando Amico Remoto Remote ControlV2 or On Off chrono thermostat electrical connections Optional The operations described below must be performed after having removed the voltage from the appliance Any thermostat or On Off environment chrono thermostat must be connected to clamps 40 and 41 eliminating jumper X40 Fig 3 2 Make sure th...

Page 9: ...ng and joining of the elements correctly Attention if the exhaust terminal and or extension concentric pipe needs shortening consider that the internal duct must always protrude by 5 mm with respect to the external duct Diaphragm installation Attention based on the boiler model checking which type of fan is installed use appropriate diaphragms For correct functioning of the boiler it is necessary ...

Page 10: ...6 Exhaust m 2 0 Terminal complete with intake exhaust vertical concentric Ø 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Intake exhaust terminal vertical concentric Ø 80 125 Intake and Exhaust 26 5 m 1 6 m 4 4 Intake m 11 5 Exhaust m 8 8 Terminal complete with intake exhaust horizontal concentric Ø 80 125 Intake and Exhaust 39 m 2 3 m 6 5 Intake m 16 9 Exhaust m 13 Intake ...

Page 11: ...al can be extended to a max length of 12 linear metres using insulated pipes Fig 1 28 and limit the length of the Ø 80 normal flue pipe not insulated to just 5 metres Example of installation with direct vertical terminal in partially protected location When the vertical terminal for direct discharge of com bustionfumesisused aminimumgapof300mm mustbeleftbetweentheterminalandthebalcony above The he...

Page 12: ...re Application with side outlet Fig 1 15 Using the horizontal intake exhaust kit without the special extensions enables routing through a wall thickness of 725 mm with the left side outlet and 645 with the right side outlet Extensions for horizontal kit The Ø 60 100 horizontal intake exhaust kit can be extended up to a max horizontal length of 3000 mm includingtheterminalwithgrilleandexcluding the...

Page 13: ...bly Fig 1 20 install the concentric flange 2 on the central hole of the boiler inserting the gasket 1 and tighten using the screws in the kit Fit the male end smooth of the adapter 3 into the female end of the concentric flange 2 Imitationaluminiumtileinstallation Replacethe tile with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position the fixed half shell 7 and insert the ...

Page 14: ...al wall sealing plate has been fitted this will ensure sealing and joining of the elements making up the kit Installation clearances Figure 1 23 gives the min installation space dimensions of the Ø 80 80 separator terminal kit in limited conditions Figure 1 24 shows the configuration with vertical exhaust and horizontal intake Extensions for separator kit Ø 80 80 The max vertical linear length wit...

Page 15: ...tween the pipe and flue Insulation of separator terminal kit Whenever there are flue gas condensate problems in the exhaust pipes or on the external surface of the intake pipes on request Immergas supplies insulated intake exhaust pipes Insulation my be necessary on the exhaust pipe due to excessive loss of temperature of the flue gas on their route Insulation may be necessary on the intake pipe a...

Page 16: ... terminals The exhaust terminals must be installed on external perimeter walls of the building be positioned according to the minimum distances specified in current technical standards Combustion products exhaust of natural or fan assisted appliances in open top closed environments In spaces closed on all sides with open tops ventilation pits courtyards etc direct flue gas exhaust is allowed for n...

Page 17: ...iver turn clockwise and insert the by pass anti clockwise it is excluded 1 21 KITS AVAILABLE ON REQUEST System cut off valves kit The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly This kit is particularly useful for maintenance as it allows the boiler to be drained separately without having to empty the entire syst...

Page 18: ...l pressure point 10 Negative signal pressure point 11 Flue pressure switch 12 Flow probe 13 Flue hood 14 Safety thermostat 15 Primary heat exchanger 16 Ignition and detection electrodes 17 System expansion vessel 18 Burner 19 System pressure switch 1 22 BOILER COMPONENTS 20 Air vent valve 21 Boiler pump 22 Plate heat exchanger 23 3 way valve motorised 24 System draining valve 25 By pass 26 3 bar s...

Page 19: ...an checks efficiency of the ducting or other devices Never clean the appliance or connected parts with easily flammable substances Never leave containers or flammable substances in the same environment as the appliance Attention theuseofcomponentsinvolvinguse of electrical power requires some fundamental rules to be observed do not touch the appliance with wet or moist parts of the body do not tou...

Page 20: ... remote control communication 31 Low power supply voltage 37 Loss of flame signal 38 Block due to loss of continuous flame signal 43 Attention the Anomaly can be reset 5 times consecutively after which the function in inhibited for at least one hour One attempt is gained every hour for a maximum of 5 attempts By switching the appliance on and off the 5 attempts are re acquired Ignition block The b...

Page 21: ...ILER SHUTDOWN For complete boiler switch off press the off button disconnect the onmipolar switch outside of the boiler and close the gas cock upstream from the appliance Never leave the boiler switched on if left unused for prolonged periods 2 7 RESTORE HEATING SYSTEM PRESSURE Periodically check the system water pressure The boiler manometer should read a pressure between 1 and 1 2 bar If the pre...

Page 22: ... intake and or exhaust terminals are not blocked check activation of the no air safety pressure switch ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified ensure production of domestic hot water 3 1 HYDRAULIC DIAGRAM ensure sealing efficiency of water circuits check ventilation and or aeration of the installation room where provided If eve...

Page 23: ...sor software updating operation 3 3 TROUBLESHOOTING N B maintenance interventions must be carried out by a qualified technician e g Immergas After Sales Technical Assistance Service Smell of gas Caused by leakage from gas circuit pipelines Check sealing efficiency of gas intake circuit The fan works but ignition discharge does not occur on the burner ramp The fan may start but the safety air press...

Page 24: ...ndard setting 0 instant boiler 1 Boiler with storage tank 0 Display lighting Establishes the display lighting mode Display lighting P2 Range of values which can be set Standard setting 0 Off 1 Auto 2 On 1 Off the display is always lit with low intensity Auto the display lights up during use and lowers after 15 seconds of inactivity In the case of anomaly the display flashes On the display is alway...

Page 25: ...given in the table Par 3 18 3 21 3 7 CHECKS FOLLOWING CONVERSION TO ANOTHER TYPE OF GAS After making sure that conversion was carried out with a nozzle of suitable diameter for the type of gas used and the settings are made at the correct pressure check that there is no flame in the combustion chamber the burner flame is not too high or low and that it is stable does not detach from burner the pre...

Page 26: ... its activation is signalled by the indication of the flow temperature and the flashing and symbols This function allows the technician to check the combustion parameters Once the function is activated it is possible to select whether to perform the check in CH status regulating the parameters with buttons 5 and 6 or in DHW mode opening any DHW cock and always regulate the parameters with the butt...

Page 27: ...te boiler maintenance the casing can be completely removed as follows Fig 3 4 3 5 1 Unhook the decorative frame a from the relative lower retainers 2 Remove the decorative frame a from the casing c 3 Loosen the 2 front screws b that fix the casing on 4 Loosen the 2 lower screws d that fix the casing on 5 Pull the case towards yourself c 6 Push the case c upwards at the same time to release it from...

Page 28: ...28 3 5 4 4 5 6 6 d d c INSTALLER USER MAINTENANCE TECHNICIAN ...

Page 29: ...ts should therefore be carried out using a differential manometer small U shaped column or digital manometer with the probes inserted in the pressure test gas valve outlet and on the sealed chamber positive pressuretest Thepowerdatainthetablehasbeen obtained with intake exhaust pipe measuring 0 5 m in length Gas flow rates refer to heating power below a temperature of 15 C and at a pressure of 101...

Page 30: ...urner On Off 5 60 0 06 Central heating circuit max operating pressure bar 3 Central heating circuit max operating temperature C 90 Adjustable central heating temperature C 35 85 System expansion vessel total volume l 4 0 Expansion vessel factory set pressure bar 1 Water content in generator l 2 5 Head available with 1000 l h flow rate kPa m H2 O 24 52 2 5 Hot water production useful heat output kW...

Page 31: ...SS NOZZLE BURNER GAS FLOW RATE BURNER PRESS NOZZLE BURNER GAS FLOW RATE BURNER PRESS NOZZLE BURNER kW kcal h m3 h mbar mm H2 O kg h mbar mm H2 O kg h mbar mm H2 O 24 0 20640 2 71 12 51 127 6 2 03 29 01 295 8 1 99 36 80 375 3 23 0 19780 2 60 11 53 117 6 1 94 26 65 271 7 1 91 34 07 347 4 22 5 19353 2 55 11 06 112 8 1 90 25 52 260 2 1 87 32 76 334 0 21 0 18060 2 39 9 70 99 0 1 78 22 29 227 3 1 75 28 ...

Page 32: ...rial Number CHK Check Cod PIN PIN code Type Type of installation Qnw min Minimum heating capacity domestic Qn min Minimum heating capacity heating Qnw max Maximum heating capacity domestic Qn max Maximum heating capacity heating Pn min Minimum heat output Pn max Maximum heat output PMS Maximum pressure system PMW Maximum pressure domestic D Specific flow rate TM Maximum working temperature NOx Cla...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...gas Italia immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038773ENG rev ST 002116 002 12 16 ...

Reviews: