Technical documentation
Technical documentation
STEM@ ed 06/01
26
EOLO MAIOR @
SAFETY DEVICES
Circulator antilock
The circulator is run for 150 seconds after:
- 24 hours of inactivity with the SUM/WINT switch in SUMMER position
- 3 hours of inactivity with the SUM/WINT switch in WINTER position (
radiator
antifreeze
)
.
Insufficient circulation
To prevent overheating the water-gas exchanger in case of a pump blockage or bad
circulation in the primary circuit, when the NTC heating sensor (B1) detects a rise in
temperature greater that 5°C per second, the burner is switched off.
The triggering of the safety device is indicated by the lighting up of LED H2 (
red
) and
flashing of LED H1 (
yellow
)
.
Pump post- circulation
To prevent overheating the water/gas exchanger, at the end of each central-heating
(opening
of room thermostat)
or antifreeze request, the circulator is kept running for 150 seconds.
NTC sensors fault
(B1 and B2)
A fault in the d.h.w. sensor (B2) prevents operation in d.h.w. mode.
A fault in the central-heating sensor (B1) prevents operation in both central-heating and
d.h.w. mode.
Breakage is indicated by the flashing of LED H1
(yellow).
INDICATORS
H1
(yellow
LED)
H2
(red LED)
H3
(green
LED)
CAR error
code monitor
(if fitted)
Depending on state, these indicate:
off
off
off
---
- boiler off
(no power)
off
off
on
---
- boiler in stand-by
(boiler powered and burner
not working)
on
off
on
---
- burner working
(gas valve powered)
off
on
on
E01
- no ignition lock engaged
off
flashing
on
E02
- overheating safety device (E4) or flue safety
device (E5) engaged
flashing together
on
E14
- ignition card stalled
(modulaton card-ignition
card connection not OK)
flashing
off
on
E05
- fault of NTC central-heating sensor (B1)
flashing
off
on
E06
- fault of NTC d.h.w. sensor (B2)
flashing aternately
on
E10
- pressure switch engaged due to lack of water
flashing
on
on
E27
- bad circulation safety device engaged
(pump blocked)
on
flashing
on
E31
- remote control not compatible / CAR fault