background image

11 / 15 

 

Nemo SX - Multifunction control 
module 

 

Cat. N°: SXM0C1

 

 

 

6. SYSTEM ARCHITECTURES 

6.1 Stand-alone system

 (continued): 

6.1.2 Stand-alone system with remote addressing (through a computer)

 (continued): 

Consequences for the system architecture: 

-

 

for 1 mini configuration module (cat. no SXV01) 

o

 

up to 30 Nemo SX modules (eg. 30 devices grouped per functions with addresses from1 to 30) 

It is possible to assign to several devices the same address with the purpose of grouping different functions, because they are related to the 
same electrical circuit. For example it is possible to assign the same address to a multifunction signalling module (cat. no SXMC02), a 
multifunction control module (cat. no SXM0C1), a measuring module, and so on. In this way on the Nemo SX display or in a supervision system 
the grouped function will be displayed as a unique “device” with all grouped functions.

 [Refer to the schemes here under]

  

 

 

 

Note for the mini configuration module (local display) 
. It is possible to assign it the same address as another Nemo SX 
. The mini configuration module can be placed everywhere in the Nemo SX bus 

6.2 Supervised system (Computer Supervisory System) 

. Supervised system = System to be used through a Computer Supervisory System to remotely read data from the Nemo SX devices and/or do 
operations on these devices (e.g. commands of a motor driven or contactor ...). 

6.2.1 Supervised system with local addressing (through the track wheel) 

Local addressing advantages:  

-

 

No configuration software needed to set-up the installation 

-

 

Installation can be done without the intervention of a System Integrator 

Programming procedure: 

. For Nemo SX modules which need some: mandatory through to lateral DIP-switch of each Nemo SX

 

modules 

(see § ”Module configuration” in the 

technical sheet of each device)

Addressing procedure: 

. For all Nemo SX modules: mandatory through the track wheel located on the top upper face of each Nemo SX

 

modules 

. Marked from 0 to 9 in order to locally define the Modbus address to Nemo SX

 

modules 

In this system the Modbus address of an Nemo SX module device or group of modules (several functions) is obtained considering the address 
of the interface Modbus/Nemo SX Interface as tenth and the address of a device or group of function as unit (e.g. Interface address 1 = 10 

   

address of module n°5 = Modbus address 15) 

 

 

 

 

Technical data sheet: IDP000170EN_02 

Updated: 14/02/2018 

Created: 31/08/2017 

 

 

 

Summary of Contents for Nemo SX SXM0C1

Page 1: ...quipaggiato con micro interruttori sul lato che permettono di configurare lo stato dei contatti contatti NA o NC il tipo di attivazione comando mantenuto o impulsivo Simbolo 2 GAMMA Art SXM0C1 Modulo...

Page 2: ...tra i terminali 3 e 4 Entrambi i rel sono configurabili Vedere il Configurazione del modulo 4 MESSA IN OPERA COLLEGAMENTO continua Configurazione del modulo Sul lato sinistro il modulo Nemo SX dotato...

Page 3: ...nuto Contatti interbloccati Comando a Motore 4 MESSA IN OPERA COLLEGAMENTO continua Collegamento con un dispositivo associato Associazione con Comando a Motore con comandi ON OFF separati I micro inte...

Page 4: ...di comando multifunzione Nemo SX sempre possibile effettuare il comando in locale attraverso i due pulsanti frontali del modulo 4 MESSA IN OPERA COLLEGAMENTO continua Interconnessione tra moduli Nemo...

Page 5: ...eve essere rimossa 4 MESSA IN OPERA COLLEGAMENTO continua Interconnessione tra moduli Nemo SX continua Tramite un mix di cavi di comunicazione e di guide comunicanti in modo da creare un collegamento...

Page 6: ...o del modulo Possibili stati Colore Stato Significato Rosso Lampeggio lento Errore es errore di indirizzamento Lampeggio veloce Nessuna funzione Fisso pressione del tasto multifunzione per pi di 20 se...

Page 7: ...oestinguente Resistenza al calore ed al fuoco secondo la norma IEC EN 60695 2 12 test del filo incandescente a 960 C Classificazione UL 94 IECEN 60695 11 10 V1 Temperature ambiente di funzionamento Mi...

Page 8: ...e di Potenza attiva totale kW sopra il quale la procedura si avvia valore predefinito 100 kW Isteresi valore espresso in della soglia sotto il quale l allarme rientra ed i carichi scollegati vengono r...

Page 9: ...di un Integratore di Sistema Procedura di programmazione Per i moduli Nemo SX che richiedono una programmazione specifica questa deve essere fatta obbligatoriamente tramite i micro interruttori prese...

Page 10: ...dono una programmazione specifica questa deve essere fatta obbligatoriamente tramite i micro interruttori presenti su ciascun modulo vedi Configurazione del Modulo nella scheda tecnica di ciascun disp...

Page 11: ...u essere posizionato ovunque lungo il bus Nemo SX 6 2 Sistema in Supervisione Sistema in Supervisione Sistema utilizzato a distanza tramite un computer con un software BMS Building Management System 6...

Page 12: ...dispositivo con tutte le funzioni raggruppate Fare riferimento allo schema seguente Nota In questa configurazione l indirizzo Modbus di un modulo Nemo SX o gruppo di moduli pi funzioni sotto lo stesso...

Page 13: ...ione specifica questa deve essere fatta obbligatoriamente tramite i micro interruttori presenti su ciascun modulo vedi Configurazione del Modulo nella scheda tecnica di ciascun dispositivo Nota attrav...

Page 14: ...a 30 moduli Nemo SX es 30 dispositivi raggruppati per funzione con indirizzi da 1 a 30 possibile assegnare a diversi dispositivi lo stesso indirizzo con lo scopo di raggruppare funzioni diverse dal mo...

Page 15: ...bando di sostanze pericolose come piombo mercurio cadmio cromo esavalente ritardanti di fiamma bromurati bifenili polibromurati PBB ed eteri di difenile polibromurati PBDE Conformit al regolamento REA...

Page 16: ...devices e g MCCBs Equipped with DIP switches on the side allowing product configuration of contacts type NO or NC contacts working method maintained or momentary contact Symbol 2 RANGE Cat n SXM0C1 U...

Page 17: ...on R2 controls the relay between terminals 3 and 4 Both relays are configurable Refer to Module Configuration 4 PREPARATION CONNECTION continued Module configuration On the left side the Nemo SX modul...

Page 18: ...tained command Contacts interlocked Motor Driven control module 4 PREPARATION CONNECTION continued Connection with an associated device Association with Motor Driven Control module with ON OFF separat...

Page 19: ...on command module local command of the module is still possible pushing on the 2 button on the front face of the module 4 PREPARATION CONNECTION continued Data connection Nemo SX modules inter connect...

Page 20: ...ide communication ports on the Nemo SX module must be removed 4 PREPARATION CONNECTION continued Data connection Nemo SX modules inter connection continued Via a mix between specific communication pat...

Page 21: ...unctions Give information about the operating state on the module Possible states Led color State Meaning red Slow blinking Error e g addressing error Fast blinking No function Steady pressing the mul...

Page 22: ...extinguishing polycarbonate Heat and fire resistant according to IEC EN 60695 2 12 glow wire test at 960 C Classification UL 94 IECEN 60695 11 10 V1 Ambient operating temperature Min 25 C Max 70 C Am...

Page 23: ...the Measurement module Threshold value of Total active power kW above which procedure starts default value 100 kW Hysteresis value expressed in of the threshold under which the alarm is over and the...

Page 24: ...e done without the intervention of a System Integrator Programming procedure For Nemo SX modules which need some mandatory through to lateral DIP switch of each Nemo SX modules see Module configuratio...

Page 25: ...atory through to lateral DIP switch of each Nemo SX modules see Module configuration in the technical sheet of each device Addressing procedure It is not necessary to address the Nemo SX modules The t...

Page 26: ...bus 6 2 Supervised system Computer Supervisory System Supervised system System to be used through a Computer Supervisory System to remotely read data from the Nemo SX devices and or do operations on...

Page 27: ...function will be displayed as a unique device with all grouped functions Refer to the scheme hereunder Note In this configuration the Modbus address of an Nemo SX module device or group of modules sev...

Page 28: ...IP switch of each Nemo SX modules see Module configuration in the technical sheet of each device Note via the configuration software it is possible to assign all the functions and characteristics of e...

Page 29: ...5 o up to 30 Nemo SX modules or grouped modules e g 30 devices grouped per functions with addresses from1 to 30 It is possible to assign to several devices the same address with the purpose of groupin...

Page 30: ...HS 2 on the restriction of the use of certain hazardous substances in electrical and electronic equipment Compliance with REACH regulation at the date of the publication of this document no substance...

Page 31: ...urs diff rentiels interrupteurs sectionneurs d clenchement ou de puissance associ es des boitiers moul s boitiers ouverts Equip s de micro switch sur le c t gauche permettant de r gler le type de cont...

Page 32: ...et 2 Bouton R2 commande locale du relais R2 via les bornes 3 et 4 Les 2 relais sont configurables Cf Configuration du module 4 MISE EN SITUATION RACCORDEMENT suite Configuration du module Equip s de m...

Page 33: ...nt Ferm NC Bistable accrochage Contacts li s Commande motoris e 4 MISE EN SITUATION RACCORDEMENT suite Raccordement avec le produit associ Association avec une Commande motoris e pour une commande ON...

Page 34: ...onn e au Module de commande multifonction Nemo SX il est toujours possible de piloter en local le module de commande via les 2 boutons en face avant du Module 4 MISE EN SITUATION RACCORDEMENT suite Tr...

Page 35: ...configuration le cache plastique pr sent l arri re de tous les modules NEMO SX doit tre enlev afin que la transmission des donn es puisse se faire 4 MISE EN SITUATION RACCORDEMENT suite Transmission d...

Page 36: ...module Diff rents tats couleurs possibles Couleur Etat Signification rouge Clignote lentement Erreur ex erreur d adressage Clignote rapidement Non applicable Fixe suite une pression de plus de 20 sec...

Page 37: ...5 1 Mati res plastiques Polycarbonate auto extinguible Tenue l preuve du fil incandescent 960 C selon la norme IEC EN 60695 2 12 Classification UL 94 IECEN 60695 11 10 V1 Temp rature ambiante de fonc...

Page 38: ...doit se d clencher valeur par d faut 100 kW Hyst r sis valeur en du seuil au dessous de laquelle l alarme doit s arr ter et le circuit doit retourner l tat initial ouvert ou ferm valeur par d faut 5 D...

Page 39: ...ces de communication n est n cessaire L installation peut tre r alis e sans l intervention d un Syst me Int grateur Proc dure de programmation Pour les modules NEMO SX concern s elle doit obligatoirem...

Page 40: ...tion du module dans la fiche technique de chaque dispositif Proc dure d adressage Il n est pas n cessaire d adresser physiquement les modules NEMO SX via la molette Laisser toutes les molettes en posi...

Page 41: ...te o sur le bus Nemo SX 6 2 Syst me Supervis utilisation d une GTC Syst me Supervis Syst me qui est utilis distance via une GTC Gestion Technique Centralis e sur ordinateur 6 2 1 Syst me Supervis avec...

Page 42: ...temps car relatives au m me circuit voir sch ma ci dessous Note Dans ce cas l adresse Modbus du module NEMO SX ou groupes de modules plusieurs fonctions sous une m me adresse se fait en prenant en co...

Page 43: ...e faire via les micro switch Cf Configuration du module dans la fiche technique de chaque dispositif Proc dure d adressage Il n est pas n cessaire d adresser physiquement les modules NEMO SX via la mo...

Page 44: ...jusqu 30 modules ou groupes de modules NEMO SX ex 30 modules group s par fonctions avec une adresse de1 30 Il est possible de donner la m me adresse plusieurs modules NEMO SX afin de regrouper plusie...

Page 45: ...rmit la directive 2011 65 UE dite RoHS 2 sur la restriction de l utilisation de certaines substances dangereuses dans les quipements lectriques et lectroniques Conformit au r glement REACH la date de...

Reviews: