Nemo D4-e
07/17 10783591 WEB E cod.MFD4E06
15
Auxiliary Supply
Terminals 20 and 21
Auxiliary Supply:
electrical power supply in AC or DC necessary for correct device
operation.
Check that the power supply voltage available corresponds to the one indicated on the
instrument data plate
(voltage value and possible frequency)
.
Where a double voltage is indicated
(e.g. 80...265Vac / 100...300Vdc)
the instrument can be
supplied with alternating current 80...265Vac or direct current 100...300Vdc.
20+
and
21-.
F
:
0,5A
gG
2 5 8
1
11
3
6
9
4
7
INPUT
VOLTAGE
CURRENT
15 29
20
AUX.
SUPPLY
21
+
–
33 34 35
RS 485
OUTPUT
OUTPUT
0V
F
+
–
Factory Settings
Password
1000
Customised page
1
Lin1v
Voltage L1
2
Lin2v
Voltage L2
3
Lin3v
Voltage L3
Connection:
3n3E
line 4 wires 3 systems
Average time:
15m
15 minutes
Hour-meter counting:
U
Voltage start
RS485
Address: 255
Speed: 9.600
Parity: none
Transmission delay: 15msec
Pulse output
Energy: active
Pulse weight: 0,01kWh
Pulse duration: 50ms
Password
2001
CT ratio: