![IMC Cansas - SCI8 Getting Started Download Page 24](http://html1.mh-extra.com/html/imc/cansas-sci8/cansas-sci8_getting-started_2045717024.webp)
24
Pin configuration and power supply
imc CANSAS Getting Started - Doc. Version 1.9 - 05.12.2014
© 2014 imc Meßsysteme GmbH
PIN
Signal
CiA -description
Use in imc CANSAS
1
+CAN_SUPPLY
imc CANSAS-specific: + imc CANSAS voltage supply. The
module can be supplied via this connector (and Pin 5).
2
CAN_L
dominant low bus line connected as per CiA
3
CAN_GND
CAN Ground
connected as per CiA . CAN-Bus reference ground.
4
CAN_RST_STECK
imc CANSAS-specific: imc CANSAS Reset ( for startup with
Reset Connector). The Reset plug has a shortcut to PIN 3
(GND).
5
-CAN_SUPPLY
imc CANSAS-specific: - imc CANSAS voltage supply (Negative
pole of supply respectively. 0V).
6
GND
CAN Ground
connected to Pin 3, as per CiA
7
CAN_H
dominant high bus
line
connected as per CiA
8
CAN_SYNC
imc CANSAS-specific: Additional line for a sync signal (1 Hz).
Generally 5 V to CAN Ground.
9
1Wire EEPROM
imc CANSAS-specific: EEPROM information about mounting
position (when used in a rack)
Exists only at female CAN-OUT plug P212. Pin 9 at male CAN-
In plug is "not connected".
Pin 9 is the positive pin of the EPROM. The corresponding
minus-pole must be connected to the chassis/shield (10/11)
of the DSUB-plug.
The EPROM is not inside the module, but can be connected
external.
The two 9-pin plugs are connected to each other 1:1; thus, all connections can be fed through to the next
imc CANSAS module, but not Pin 9.