Important notices for proper indication of phase

- This function can only be used in TT and TN systems! 

- Hold the instrument in your hand (palm) in a standard way.

- For correct function of phase indication it is necessary that the test tip is

connected to the phase voltage for at least 2! 

- The voltage must be ≥ 190 V / 48 ÷ 52 Hz against the earth, otherwise phase

indication may not work properly!

- Verification of live-circuit shouldn’t be depending on the single-pole phase test

only, but on the voltage measurement (the U function)!

3.4.2. Phase sequence test

This function is intended for testing of phase sequence (rotation).

Press and release the

FUNC

key to select the phase sequence test function.

"1 -

" is displayed.

Connect the test tips between two phases. "1 - 2 " is displayed.

After about 2 seconds, the display shows a moving symbol "1 - 2 _ _ _ 3". 

Disconnect the test tip on the instrument’s case from second phase

conductor and connect it immediately to third phase conductor. The display

shows the phase sequence "1 - 2 - 3" or "1 - 3 - 2" and the symbol of a

rotating wheel in the direction of the expected phase rotation. Displaying is

finished after about 10 seconds after the test tips are disconnected from the

tested mains.

The voltage value is displayed during the test, too.

Important notices for proper indication of phase sequence

- Connect the test tips with tested conductors

thoroughly and steadily

.

- Phase voltage must be 230 ±10% / 48 ÷ 52 Hz.

3.4.3. Function DIGISORT (with DIGIsort optional transmitter only)

The „DIGISORT“ function is intended for distinguishing of up to 12 deenergized

conductors.

Choose one conductor as common conductor, for example cable shielding or

protective conductor.

Ensure by voltage measurement that all conductors are disconnected from

the power supply!

On the opposite end of the bundle of conductors connect the transmitter

DIGIsort. Terminal "GND" connect to dedicated common conductor, terminals

1-12 to other conductors. Turn on the power of DIGIsort.

Select on the DIGOHMpro function "DIGISORT" by the

FUNC

key. In the

upper part of the display there is displayed "DIGISORT" and in the lower part

"- - -".

Summary of Contents for DIGIOHMPro

Page 1: ...USER S MANUAL DIGIOHMpro V 1 2 EN...

Page 2: ...and resistance measurement 8 3 3 1 Function U 8 3 3 2 Function R 9 3 3 3 Function beeper 10 3 4 Phase live conductor test phase sequence test DIGISORT 10 3 4 1 Single pole contactless phase indicatio...

Page 3: ...The instrument cables connectors plugs or accessories exhibits visible damages The instrument was stored under unfavourable conditions for a long period The instrument was exposed to extraordinary str...

Page 4: ...ic field such as watches credit cards with magnetic strips etc Images in this manual are illustrative and may vary slightly from the actual state 1 2 General description of the instrument The DIGIOHMp...

Page 5: ...e hand it to a collection point of secondary raw materials in accordance with local regulations Batteries Please dispose of used batteries in the designated locations in accordance with local regulati...

Page 6: ...e safely hidden Against accidental ejection are both parts secured by non contact magnetic latch Use original accessories only Max allowed voltage between test tip and ground is 300V Max allowed volta...

Page 7: ...ched on off by briefly pressing and releasing The U R key It toggles between measurement of voltage resistance and beeper functions The FUNC key It toggles between one pole phase phase rotation and DI...

Page 8: ...st lead black 2 m P 3011 test tip black P 4011 crocodile clip black P 8060 transmitter DIGIsort enables to distinguish deenergized conductors Note optional accessories P 2011 P 3011 respectively P 201...

Page 9: ...ew fully charged NiMH batteries or the quality alkaline batteries See chapter 4 1 for instructions how to do it If the device measures the voltage and if resistance is not measured check the fuse whic...

Page 10: ...out test lead compensation before measurement After test lead resistance compensation is carried out it is automatically subtracted from all resistance measurements and thus only actual value of meas...

Page 11: ...in range 0 4 If measured value is between 0 4 it is signalized by beeper Follow the same measuring procedure and consider the same warnings that are stated for the resistance function R see chapter 3...

Page 12: ...rd phase conductor The display shows the phase sequence 1 2 3 or 1 3 2 and the symbol of a rotating wheel in the direction of the expected phase rotation Displaying is finished after about 10 seconds...

Page 13: ...ltage 3 6 RESET of the instrument If the device does not operate as described in this manual we recommend RESET disconnect both test tips from tested object and turn off the instrument It the proper f...

Page 14: ...ent uses four AAA either alkaline cells or NiMH accumulators The batteries accumulators are continuously monitored see description in the Chapter 3 2 If batteries accumulators are low it must be repla...

Page 15: ...accumulators should return to normal The above described cycle in stand alone intelligent charger is recommended every few months to make If after several cycles of the above described discharge char...

Page 16: ...ukewarm soap water for plastic case cleaning Do not spill cleaning liquid over the instrument Do not use cleaning liquids based on petrol hydrocarbons etc 4 3 Calibration Measuring instruments should...

Page 17: ...1 3 z MH 10 D 4 z MH 12 D 2 00 43 00 0 01 2 z MH 5 D 3 z MH 7 D 43 0 650 0 0 1 2 z MH 5 D 3 z MH 7 D AC voltage TRMS value Measuring range V Resolution V Reference error Operating error 0 000 2 000 0...

Page 18: ...0 C relative humidity max 85 non condensing mains voltage 190 260 V 48 52 Hz instrument s position arbitrary Storage conditions ambient temperature 10 70 C relative humidity max 90 10 40 C non condens...

Reviews: