Instruction manual | IKI Pro electric heater
Page 5
Connecting the heater to electricity
The heater is connected to the electric supply with a H07RN-F, or similar, rubber cable. The use of PVC-
insulated cables is forbidden due to poor heat resistance.
The electrical installation must be performed by
a licenced electrician and must adhere to current legislation.
The connecting cable must be installed safely
away from mechanical strain and heat radiation. If the rubber cable runs inside wall panelling 1000 mm
above the floor, it needs to be heat resistant up to 170 degrees Celsius (e.g. SSJ).
Control unit
For installation, refer to the separate installation instructions specific to the control unit.
Sauna’s temperature sensor and overheating protector
Sensor location:
INSTALLATION TO THE CEILING:
- 10-30 cm from the outer casing of the heater.
INSTALLATION TO THE WALL:
- 10 cm from the ceiling
- 10-30 cm from the outer casing of the heater.
NOTE!
Make sure the temperature sensor is not located less than 1000 mm distance from an undirected air inlet
vent, or less than 500 mm from a vent that is directing air away from the sensor.
Temperature limiter will switch off the power from the heater, if the temperature in the sauna raises
dangerously high (139) due to a malfunction.