2

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Vertical

Rise

SV4.5E90

Elbow

Horizontal / Inclined Run

SV4.5HTSS

Termination

Shown

*Ceiling

Firestop/Spacer

(SV4.5VF)

SV4.5L6/12/24/36/48

Vent Sections

Support Bracket Spacing

Every 5 ft (1.52 m)

Support

Brackets

Building

Support

Framing

Ceiling

Fireplace

Exterior

Wall

Exterior

Wall

TYPICAL HORIZONTAL VENT INSTALLATION

Firestop/Spacer

SV4.5HTSS

Termination

Shown

Fireplace

*When using Secure Flex use

 Firestop/Spacer (SF4.5VF)

Note:  Adaptor SV4.5RCH or

SV4.5RCHA must be used to

attach the termination to the

venting system.  See Steps J

and K.

Figure 2

H. Change vent direction  -

 At transition from or 

to a horizontal/inclined run, install the SV4.5E45 

and SV4.5E90 elbows in the same manner as 

the straight vent sections.  The elbows feature 

a twist section to allow them to be routed about 

the center axis of their initial collar section to 

align with the required direction of the next 

vent run element. 

Twist elbow sections in a 

clockwise direction only so as to avoid the 

possibility of unlocking any of the previously 

connected vent sections.

I.

 

Continue installation of horizontal/inclined 

sections -

  Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step E

. Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined 

vent runs using conventional plumber’s tape. 

See 

Figure 2. 

 

It is very important that the 

horizontal/inclined run be maintained in a 

straight (no dips) and recommended to be in 

a slightly elevated plane, in a direction away 

from the fireplace of 

1/4" rise per foot (20 mm 

per meter) which is ideal, though rise per foot 

run ratios that are smaller are acceptable all the 

way down to at or near level. Use a carpenter’s 

level to measure from a constant surface and 

adjust the support straps as necessary.

It is important to maintain the required clear-

ances to combustibles: 1" (26 mm) at all sides 

for all vertical runs; and 3" (77 mm) at the 

top, 1" (26 mm) at sides, and 1" (26 mm) at 

the bottom for all horizontal/inclined runs.

J. Assemble vent run to exterior wall - 

If not 

previously measured, locate the center of the 

vent at the exterior wall. Prepare an opening as 

described in

 Step B.

Square Horizontal Termination- (SV4.5 HTSS) 

Assemble the venting system to a point where 

the terminus of the last section is within 6" 

(152mm) to 9" (228mm) inboard of the exterior 

surface to which the termination is to be at-

tached, see 

Figure 4

.  Attach Adaptor SV4.5RCH 

as shown in 

Figure 3

.

NOTE:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner as 

you would a vent section. 

E.  Attach vent components to each other -

 

Other vent sections may be added to the previ-

ously installed section in accordance with the 

requirements of the vent tables.  To add another 

vent component to a length of vent run, align 

the dimpled end of the component over the 

inclined channel end of the previously installed 

section, adjusting the radial alignment until the 

four locking dimples are aligned with the inlets 

of the four incline channels of the previous 

section.  Push the vent component against the 

previous section until it fully engages, then twist 

the component clockwise running the dimples 

down and along the incline channels until they 

seat at the end of the channels.

F.

  

Install firestop/spacer at ceiling - 

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure 

Flex, use SF4.5VF firestop/spacer.  If there is 

living space above the ceiling level, the firestop/ 

spacer must be installed on the bottom side of 

the ceiling. If attic space is above the ceiling, 

the firestop/ spacer must be installed on the 

top side of the joist. Route the vent sections 

through the framed opening and secure the 

firestop/spacer with 8d nails or other appropriate 

fasteners at each corner.

Remember to maintain 1" (26 mm) clearance 

to combustibles, framing members, and attic 

or ceiling insulation when running vertical 

chimney sections

.

G.

 

Support the vertical run sections - 

On the vertical run, support the venting sys-

tem every 8 feet (2.4m) above the fireplace 

vent outlet with field provided support straps 

(Plumber's tape).  Attach the straps to the vent 

pipe and secure to the framing members with 

nails or screws.

HORIZONTAL (OUTSIDE WALL) 

TERMINATION SYSTEM

Figure 2

, and  

Figures 7 to 13 

 and their associated 

Horizontal Vent Tables, illustrate the various hori-

zontal venting configurations that are possible 

for use with these appliances. 

Secure Vent

 pipe 

applications are shown in these figures; 

Secure 

Flex

 pipe may also be used. A Horizontal Vent 

Table summarizes each system’s minimum and 

maximum vertical and horizontal length values 

that can be used to design and install the vent 

components in a variety of applications. Both 

of these horizontal vent systems terminate 

through an outside wall. Building Codes limit 

or prohibit terminating in specific areas. Refer 

to the instructions provided with the fireplace.

Secure Vent

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connection.

A.

 

Plan the vent run -

 

Analyze the vent routing and determine the 

types  and  quantities  of  sections  required       

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" 

(572 mm), 34-1/2" (877 mm) and 46-1/2" 

(1181 mm) net section lengths are available. 

Make allowances for elbows as indicated in 

the instructions provided with the fireplace. 

Maintain a minimum 1" (26 mm) clearance 

to combustibles on the vertical sections. 

Clearances for the horizontal runs are; 3" (77 

mm) on top, 1" (26 mm) on sides, and 1" (26 

mm) at the bottom.

B.

 

Frame exterior wall opening -

 

Locate the center of the vent outlet on the 

exterior wall. Cut and/or frame an opening, 

10-1/2" x 12-1/8" (267 mm x  308mm) inside 

dimensions, about this center.

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 

the center above the appliance. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center.

D. Attach vent components to appliance - 

To 

attach a vent component to the appliance 

collar, align the dimpled end over the collar, 

adjusting the radial alignment until the four 

locking dimples are aligned with the inlets of 

the four incline channels on the collar.  Push 

the vent component against the collar until 

it fully engages, then twist the component 

clockwise, running the dimples down and 

along the incline channels until they seat at 

the end of the channels.  The unitized design 

of the 

Secure Vent

 components will engage 

and seal both the inner and outer pipe elements 

with the same procedure.

Sealant and securing screws are not required.

f i r e - p a r t s . c o m

Summary of Contents for SF-HTSS Series

Page 1: ...os35ST PF Gemini40 45 Libra40 ST PF CR CL Scorpio 35 40 45 ScorpioCD 35 40 45 MHD40 MPD Pro MPD40 45 MPD4035 4540 MPD35ST PF Rhapsody 54 Sirius54 Spectra EDV ELDV and EDVST PF CR CL series gas fireplaces The terminations covered by this document seamlessly integrate with all the other components of the above mentioned fireplaces approved for use with these terminations and when installed in accord...

Page 2: ...ples down and along the incline channels until they seat at the end of the channels F Install firestop spacer at ceiling WhenusingSecureVent useSV4 5VFfirestop spacer at ceiling joists when using Secure Flex use SF4 5VF firestop spacer If there is livingspaceabovetheceilinglevel thefirestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop ...

Page 3: ... in catching the mating pipe when inserting the termination L Install Firestop Spacer at exterior wall When using either of the square termina tions installSV4 5HF SecureVent orSF4 5HF Secure Flex firestop spacer over the opening at the exterior side of the framing long side up withthe3 spacerclearanceatthetopasshown in Figure 3 and nail into place The Firestop Spacer may be installed over the ope...

Page 4: ... When using Secure flex use Firestop Spacer SF4 5HF NOTE To prevent water infiltration in wet environments we recommend the use of a silicone sealant between the termination and the wall Refer to Figure 4 and Figure 5 Venting Components Required for Various exterior Wall Thicknesses When Using the Small Square Termination SV4 5HTSS Vent Components Required Exterior Wall Thickness inches mm Termina...

Page 5: ...4 5HF A E L B A T w o b l e e e r g e d 0 9 e n 0 V x a M m 4 1 9 0 t e e f 3 H E L B A T B m u m i n i M V m u m i x a M H t e e f m t e e f m 1 5 0 3 0 5 2 5 1 2 1 6 0 0 1 1 3 3 4 1 9 0 5 1 5 6 4 4 2 2 1 0 2 2 6 x a M m 4 2 1 t e e f 0 4 H V x a M m 2 6 t e e f 0 2 H H V Wall Firestop Spacer SV4 5HF Ceiling Firestop Spacer SV4 5VF When using Secure Flex use Wall Firestop Spacer SF4 5HF When usin...

Page 6: ...e f 8 H H H 1 H 2 x a M m 2 6 t e e f 0 2 V H Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Wall Firestop Spacer SF4 5HF When using Secure Flex use Ceiling Firestop Spacer SF4 5VF H2 H1 F E L B A T V M M U M I N I H m u m i x a M t e e f m t e e f m 1 5 0 3 0 5 2 5 1 2 0 1 6 0 0 1 1 3 3 4 1 9 0 5 1 5 6 4 4 2 2 1 0 2 2 6 H H 1 x a M m 2 6 t e e f 0 2 V V 1 ...

Page 7: ...mewithanincludedadaptor that can be fitted to the appliance collar or the inclined channel end of the last Secure Vent SV4 5 vent section in a rigid system in the exact same fashion as any other Secure Vent section Align the dimpled end of the adaptor overthepreviouslyinstalledsectionorappliance collar adjusting the radial alignment until the four locking dimples of the adaptor are aligned with th...

Page 8: ...P reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1769 East Lawrence Street Russellville AL 35654 fire parts com ...