Doc Ref: SL-068 v1.35 pg 10

Addressing the Assembly

The TOC-750 Module PCB is an Addressable Device and 
Comes Equipped With a Simple Interface to Allow the Base 
Address to be Set. To Set The Set Address,

Press and hold the Down button for >2s

Release Button the Light Pattern Will Now Indicate the set Address  as  Shown in the Table Below.

With the Set Address Lit, the UP and DOWN buttons can now be used to alter the address if required

With the Required Address lit, Press and Hold the DOWN Button Until the LED’s go out. Release the 
DOWN button and the new Base Address is Now Set.

Note That with the base address set the LED’s revert to showing what options are active and which of 
those options are communicating, see previous section on ‘Module Indications’.

00

08

16

24

01

09

17

25

02

10

18

26

03

11

19

27

04

12

20

28

05

13

21

29

06

14

22

30

07

15

23

31

Setting the base address using the button interface sets the address for all other active options on the 
module as follows:
For a Base Address Set of 01:

NOTE: WHEN SETTING ADDRESSES YOU CANNOT HAVE TWO DEVICE ADDRESSES SET THE 
SAME ON THE SAME ADDRESSABLE HIGHWAY or DEVICE.

Pellistor Input = Base Address = 01

02 = IR/PID/Toxic or Oxygen Sensor
03 = Digital or analogue Input 1
04 = Digital or analogue input 2
05 = E-Stop
06 = Key Switch

101 = Relay & Sounder
102 = Digital Output 1
103 = Digital Output 2
104 = Display Sounder

S YS T E M   S TAT U S

EDIT
 19

Note when editing if an
Annunciator Display is
fitted the base address
display will also update 

UP

DOWN

1  2  3  4  5

UP

DOWN

1  2  3  4  5

 Anything turned off is ignored. Addresses are allocated in the following sequence.

1  2  3  4  5

1  2  3  4  5

Summary of Contents for TOC-750 Series

Page 1: ...a t i o n a n d M a i n t e n a n c e V 1 3 5 Document Ref SL 068 v1 35 Operation Manual TOC 750 Annunciator FS646773 EMS696504 Triton House Crosby Street Stockport SK2 6SH internationalgasdetectors c...

Page 2: ...nce This will usually mean having passed a training competency course International Gas Detectors run training courses for safety survey speci cation installation and service aspects of hazardous gas...

Page 3: ...between the detector or interface and the control panel using IGD s Sentinel 2 Wire protocol A single 2 Wire Highway can support up to 32 devices interfaced using the module PCB Highways can be up to...

Page 4: ...tom Either Side Note TOC 750 AN3 Shown 145 0 126 0 128 5 COVER SECURING SCREW M20 x 1 5 40 0 25 0 7 0 EXTERNAL EARTH MKIII FLAMMABLE GAS DETECTOR SHOWN 40 0 110 128 0 The ATEX version uses IGD s JB3 s...

Page 5: ...ut DVM Test Point DVM Test Point Housing Sealing Environment Temperature Voltage Communication Relay Digital Output Digital Input Analogue I P Pellistor Port Sounder Display Comm Port 1 2 3 4 5 6 7 TO...

Page 6: ...102 103 101 6 Device Address Table Note that one 2 Wire addressable highway running Sentinel protocol can support up to 32 modules Each module can have up to 8 connected devices IGD Con guration softw...

Page 7: ...r performance and or damage to system components 2 WIRE SYSTEMS 2 W i r e G a s D e t e c t i o n S y s t e m I n s t a l l e r s G u i d e V x x OLIVER IGD Triton House Crosby Street Stockport SK2 6S...

Page 8: ...ype Head Head Current Volts MK3 ATEX EXD IIC T6 360mA 2 2V MK6 Safe Area 170mA 2 5V MK7 Safe Area 170mA 2 5V This cable to the pellistor may need to be screened in electrically noisy environments This...

Page 9: ...reen if IR PID Toxic option activated Flashing green see table LED 4 Lit Green if I O Port 2 option activated Flashing green see table LED 3 Lit Green if I O Port 1 option activated Flashing green see...

Page 10: ...cating see previous section on Module Indications 00 08 16 24 01 09 17 25 02 10 18 26 03 11 19 27 04 12 20 28 05 13 21 29 06 14 22 30 07 15 23 31 Setting the base address using the button interface se...

Page 11: ...libration and Zero Gas Bottles 5 4 3 2 1 Notes Diagram indicates a module PCB interfacing to a MK7 Pellistor gas detector Detector could also be an 102 Series ATEX gas detector or TOC 30 Series Safe A...

Page 12: ...using IGD s interface cable as indicated below Apps can be downloaded from the App store Interface Cable PN TOC CBL SET NOTE When undertaking work with a connected tablet ensure the system controller...

Page 13: ...o zero the detector Now apply calibration gas as indicated The graph should show the signal rise as the detector responds to gas and gives a visual indication to show when the reading has stabilised O...

Page 14: ...out 3 Use the UP DOWN buttons to select the left LED for zero mode right LED is CAL mode With the left LED on press and hold the UP button Release when the LED s go out 4 With a zero gas owing allow t...

Page 15: ...post cal reading check the reading is in tolerance 6 Each LED will blink in series to indicate the update and the module will go back to normal operation NOTE There is no ABORT option so before selec...

Page 16: ...icates that the PEllistor I O Port 1 and the Relay are activated When reset the default For software versions 2 5 and earlier will be Pellistor input only for a MK6 7 Pellistor with a default address...