Doc Ref: SL-068 v1.35 pg 9
Module Indications
Connected Status
Each module has two push buttons, labelled up and down and five LED’s. In operation the
LEDs and buttons work together to allow local calibration, change or reading of the base
address or connected status as follows:
LED 1
Lit Green if pellistor option activated
Flashing green see table
LED 5
Lit Green if Relay option activated
Flashing green see table
LED 2
Lit Green if IR-PID-Toxic option activated
Flashing green see table
LED 4
Lit Green if I/O Port 2 option activated
Flashing green see table
LED 3
Lit Green if I/O Port 1 option activated
Flashing green see table
Note the LED flash rate is used to indicate as follows:
LED Flash Rate
ON no Flash
1 per Second
5 per Second
1 per 10 Seconds
Indicates
Option Enabled and Powered But No Communication
Option Enabled Powered and Communication All OK
Line Voltage Low only LED 1 then LED 5
Option Has a Fault Condition
Note: IGD App is used to configure the module PCB to switch devices on and off and set
addresses (see Tocsin 650/750 Manual).