background image

Addressing the Assembly

International Gas Detectors

UP

DOWN

PC

P   Y   W

DISPLAY

V+

4-20mA

1  2  3  4  5

In Normal Operation This LED 
is Lit When 24V DC is Applied 
and Will Flash to Indicate 
Communication

The TOC-30 Annunciator is an Addressable Device and Comes 
Equipped With a Simple Interface to Allow the Base Address to 
be Set. 

To Check The Set Address,

Press and Hold the Right Hand Button Labelled ‘DOWN’ For > 2s

Release Button the Light Pattern Will Now Indicate the set Address  as  Shown in the Table Below.

With the Set Address Lit, the UP and DOWN buttons can now be used to alter the address if required

With the Required Address lit, Press and Hold the DOWN Button Until the LED’s go out. Release the 
DOWN button and the new Base Address is Now Set.

Note That the Left  LED Will Now be Flashing if the Annunciator is Communicating With its Control 
Panel.

4100

4108

4116

4124

4101

4109

4117

4125

4102

4110

4118

4126

4103

4111

4119

4127

4104

4112

4120

4128

4105

4113

4121

4129

4106

4114

4122

4130

4107

4115

4123

4131

Setting the base address sets the address for all other components on the annunciator as follows:

For a Base Address Set of 4101:

NOTE: WHEN SETTING ADDRESSES YOU CANNOT HAVE TWO DEVICE ADDRESSES SET THE 
SAME ON THE SAME ADDRESSABLE HIGHWAY.

E-Stop Input = Base Address = 4101

4102 = key Switch
4103 = TOC-10 Digital Input
4104 = Pellistor Input

4201 = Sounder, Display, Digital Output (external Beacon Sounder)
4202 = Sounder, Display, Digital Output (external Beacon Sounder), Relay

S YS T E M   S TAT U S

EDIT
4119

Note when editing
the base address
the display will also
update 

UP

DOWN

1  2  3  4  5

Summary of Contents for TOC-30A-AN1

Page 1: ...d M a n t e n a n c e V 1 0 2 OLIVER IGD CO H S 2 CO2 SO2 NO NO2 CH4 International Gas Detectors Pepper Road Bramhall T echnology Park Stockport SK7 5BW England T el 44 0 161 483 1415 Fax 44 0 161 484...

Page 2: ...he digital inputs to interface with other systems such as fire alarms As with detectors in the TOC 30 series the annunciators will interface with any IGD addressable control panel TOC 30 Annunciators...

Page 3: ...ge Communication Relay Digital Output Digital Input Pellistor Port Sounder Display ABS IP65 using suitable glanding 0 95 RH Non Condensing 0 55 Deg C 12 28V DC RS485 IGD Data Highway 24V 0V A B 4 Core...

Page 4: ...refully unplugging the 10 way ribbon cable DO NOT PLUG OR UNPLUG WHEN POWERED E Stop Option Switch Option Colour LCD 20mm Cable Entries IGD Quick Fit Gland Option PN Pack of 5 Optional Pellistor Port...

Page 5: ...ves boiler shut down interfaces or similar When switching external loads it is important to consider the nature of the load being switched For inductive loads suitable protection from induced back EMF...

Page 6: ...lease the DOWN button and the new Base Address is Now Set Note That the Left LED Will Now be Flashing if the Annunciator is Communicating With its Control Panel 4100 4108 4116 4124 4101 4109 4117 4125...

Page 7: ...l panel then the following alternating message will be displayed SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS Estop add 4101 al2 add...

Page 8: ...RESSES YOU CANNOT HAVE TWO DEVICE ADDRESSES SET THE SAME ON THE SAME ADDRESSABLE HIGHWAY IGD addressable systems use a 4 core cable or highway to connect all system devices Typically an addressable hi...

Page 9: ...the Gas Supply Device Annunciator E Stop Base Address Annunciator Digital Input TOC 10 Annunciator Sounder Display Annunciator Relay TOC 30A PHC Flammable Gas Detector Address 4101 4103 4201 4202 4110...

Reviews: