background image

MOUNTING DETAILS AND DIMENSIONS 

TECHNICAL

172
158

76

48

43

86

98

18

5

20mm Entries Top, Bottom & Either Side 

Part Numbers & Features

Part Number

TOC-30A-ANN

TOC-30A-AN1

TOC-30A-AN2

TOC-30A-AN3

Description

Base Unit

With E-Stop

With Key Switch

With Key Switch & E-Stop

1

1

1

1

1

1

1

1

  Sounder  Display E-Stop Key Switch

Housing
Sealing
Environment
Temperature
Voltage
Communication
Relay
Digital Output
Digital Input
Pellistor Port
Sounder
Display

ABS, 
IP65 (using suitable glanding)
0 -95% RH Non Condensing
0-55 Deg C
12-28V DC
RS485 IGD Data Highway 24V, 0V, A, B  4 Core Screened Cable
5A Non Inductive Loads 230V AC
24V DC 100mA (Typically for LED Beacon Sounders
Suitable for use with TOC-10 Link Function
Option if fitted to Interface to MK6 or MK7 Pellistors
85dB
2 x 8 Programmable LCD with RGB Backlight 

Note TOC-30A-AN3 Shown

International Gas Detectors

Single Pole 

Relay

Digital

Output

Pellistor

Interface

Digital

Input

Summary of Contents for TOC-30A-AN1

Page 1: ...d M a n t e n a n c e V 1 0 2 OLIVER IGD CO H S 2 CO2 SO2 NO NO2 CH4 International Gas Detectors Pepper Road Bramhall T echnology Park Stockport SK7 5BW England T el 44 0 161 483 1415 Fax 44 0 161 484...

Page 2: ...he digital inputs to interface with other systems such as fire alarms As with detectors in the TOC 30 series the annunciators will interface with any IGD addressable control panel TOC 30 Annunciators...

Page 3: ...ge Communication Relay Digital Output Digital Input Pellistor Port Sounder Display ABS IP65 using suitable glanding 0 95 RH Non Condensing 0 55 Deg C 12 28V DC RS485 IGD Data Highway 24V 0V A B 4 Core...

Page 4: ...refully unplugging the 10 way ribbon cable DO NOT PLUG OR UNPLUG WHEN POWERED E Stop Option Switch Option Colour LCD 20mm Cable Entries IGD Quick Fit Gland Option PN Pack of 5 Optional Pellistor Port...

Page 5: ...ves boiler shut down interfaces or similar When switching external loads it is important to consider the nature of the load being switched For inductive loads suitable protection from induced back EMF...

Page 6: ...lease the DOWN button and the new Base Address is Now Set Note That the Left LED Will Now be Flashing if the Annunciator is Communicating With its Control Panel 4100 4108 4116 4124 4101 4109 4117 4125...

Page 7: ...l panel then the following alternating message will be displayed SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS Estop add 4101 al2 add...

Page 8: ...RESSES YOU CANNOT HAVE TWO DEVICE ADDRESSES SET THE SAME ON THE SAME ADDRESSABLE HIGHWAY IGD addressable systems use a 4 core cable or highway to connect all system devices Typically an addressable hi...

Page 9: ...the Gas Supply Device Annunciator E Stop Base Address Annunciator Digital Input TOC 10 Annunciator Sounder Display Annunciator Relay TOC 30A PHC Flammable Gas Detector Address 4101 4103 4201 4202 4110...