8 Operation
After power on, the unit is in the Run mode (= normal operating mode).
Response of the analogue output in case of a fault:
Value below the set measuring
range
-
The output signal falls to min. 3.8 mA (at [OU2] = [I]),
-
rises to max. 20.5 mA (at [OU2] = [Ineg]).
Value above the set measuring
range
-
The output signal rises to max. 20.5 mA (at [OU2] = [I]),
-
falls to min. 3.8 mA (at [OU2] = [Ineg]).
Value below or above the
detection zone of the sensor
Analogue signal acc� to setting [FOU2]�
9 Technical data and scale drawing
Technical data and scale drawing at www�ifm�com�
10 Factory setting
Factory setting
User setting
TP3231 TP3232 TP3233 TP3237
OU2
I
I
I
I
ASP
-50
-50
0
0
AEP
150
300
300
100
COF
0.0
0.0
0.0
0.0
FOU2
OFF
OFF
OFF
OFF