7 Parameter setting
Using an IO-Link capable parameter setting tool, the following options are
available:
- Reading current process values�
- Reading, changing and saving current parameter settings and transmitting
them to other units of the same type�
7.1 Adjustable parameters
OU2 Output function for OUT2:
Analogue signal: 4���20 mA [I] or 20���4 mA [Ineg]�
ASP Analogue start value for temperature�
Measured value at which the output signal is 4 mA (20 mA at [OU2] = [Ineg]).
AEP
Analogue end value for temperature�
Measured value at which the output signal is 20 mA (4 mA at [OU2] = [Ineg]).
Minimum distance between ASP (analogue start point) and AEP (analogue end
point) = 5 °C or 9 °F.
COF
Zero-point calibration�
Setting range: ±10 °C in steps of 0.1 °C. The internal measured value "0" is
shifted by this value�
FOU2
Behaviour of output 2 in case of an internal fault�
-
[On] = the analogue signal goes to the upper end stop value (21.0 mA).
-
[OFF] = the analogue signal goes to the lower end stop value (3.5 mA.)