3

UK

2  Safety instructions

•  The device described is a subcomponent for integration into a system�

 -The manufacturer of the system is responsible for the safety of the system�
 -The system manufacturer undertakes to perform a risk assessment and to 

create a documentation in accordance with legal and normative requirements 

to be provided to the operator and user of the system� This documentation 

must contain all necessary information and safety instructions for the operator, 

the user and, if applicable, for any service personnel authorised by the 

manufacturer of the system�

•  Read this document before setting up the product and keep it during the entire 

service life�

•  The product must be suitable for the corresponding applications and 

environmental conditions without any restrictions�

• 

Only use the product for its intended purpose (→ Functions and features).

•  If the operating instructions or the technical data are not adhered to, personal 

injury and/or damage to property may occur�  

•  The manufacturer assumes no liability or warranty for any consequences 

caused by tampering with the product or incorrect use by the operator�

•  Installation, electrical connection, set-up, operation and maintenance of the unit 

must be carried out by qualified personnel authorised by the machine operator�

•  Protect units and cables against damage�

3  Functions and features

In connection with a temperature probe the unit monitors the system temperature 

in machines and plants�

Connectable temperature probes:

•  Temperature sensors TM, TS, TT�

• 

Resistance thermometer RTD (Pt 100 or Pt 1000).

The unit detects the connected sensor type and configures itself accordingly� 

Summary of Contents for TP323 Series

Page 1: ...Operating instructions Measured signal converter for temperature sensors TP323x 704899 00 07 2019 UK ...

Page 2: ...Link 4 5 Installation 4 6 Electrical connection 5 7 Parameter setting 6 7 1 Adjustable parameters 6 8 Operation 7 9 Technical data and scale drawing 7 10 Factory setting 7 1 Preliminary note 1 1 Symbols used Instruction Reaction result Cross reference Important note Non compliance can result in malfunction or interference ...

Page 3: ...ng applications and environmental conditions without any restrictions Only use the product for its intended purpose Functions and features If the operating instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operat...

Page 4: ...set the parameters of the unit while it is in operation Operation of the unit via an IO Link interface requires an IO Link master With a PC suitable IO Link software and an IO Link adapter cable communication is possible when the system is not in operation The IODDs necessary for the configuration of the unit detailed information about process data structure diagnostic information parameter addres...

Page 5: ... 3 2 L L L IO Link 2 L L 1 2 1 1 4 3 2 4 3 2 1 3 1 2 4 4 2 1 3 3 4 LED1 LED2 1 2 Connection Ub and output signals Pin 1 L Pin 3 L Pin 4 OUT1 IO Link Pin 2 OUT2 Analogue signal for temperature 3 Connection of a 2 wire measuring probe links between 1 2 and 3 4 A wire fault can be corrected in the menu COF 4 Connection of a 4 wire measuring probe LED 1 lit in case of operation as 3 wire unit IO Link ...

Page 6: ...mperature Measured value at which the output signal is 4 mA 20 mA at OU2 Ineg AEP Analogue end value for temperature Measured value at which the output signal is 20 mA 4 mA at OU2 Ineg Minimum distance between ASP analogue start point and AEP analogue end point 5 C or 9 F COF Zero point calibration Setting range 10 C in steps of 0 1 C The internal measured value 0 is shifted by this value FOU2 Beh...

Page 7: ...set measuring range The output signal rises to max 20 5 mA at OU2 I falls to min 3 8 mA at OU2 Ineg Value below or above the detection zone of the sensor Analogue signal acc to setting FOU2 9 Technical data and scale drawing Technical data and scale drawing at www ifm com 10 Factory setting Factory setting User setting TP3231 TP3232 TP3233 TP3237 OU2 I I I I ASP 50 50 0 0 AEP 150 300 300 100 COF 0...