Temperature sensor

4

3 Intended use

The unit detects the medium temperature of liquid and gaseous media.

4 Installation

CAUTION

During installation or in case of mechanical failure, high pressure or hot media can leak
from the system.

w

Risk of injury caused by pressure or burns.

u

Ensure that the system is free of pressure during installation.

u

Ensure that no media can leak at the mounting location during installation.

Sensors with process connection Clamp:

u

Secure the device with a bracket (Clamp counterpart).

4.1 Use in hygienic areas according to EHEDG

In case welded adapters are used, the food contact surface must be smooth (surface roughness
Ra < 0.8 µm) and the welding has to be done according to EHEDG Guideline 9 and 35.

The sensor is suited for CIP (clean in place) when installed correctly.

u

Observe the application limits (temperature and material resistance) according to the data
sheet.

u

Ensure that the installation of the unit in the system complies with EHEDG.

u

Use self-draining installation.

u

Only use process adapters permitted according to EHEDG with special seals required by the
EHEDG position paper.

u

For any structures in a tank, direct water jet cleaning must be possible. Cleaning of dead spaces
must be possible.

4.2 Using the welding adapter / welding thermowell

General notes on the welding operation:

u

The welding operation is to be carried out by qualified personnel according to state-of-the-art
technology.

u

Use materials and welding operations that are suitable for the housing material.

u

Keep the surfaces free from any contamination.

u

Ensure the careful preparation of the components.