Air gap sensor
SDP110
23
10 Parameter setting
The parameters can be set via the IO-Link interface or via the keys on the unit.
CAUTION
If the medium temperature is above 50 °C (122 °F), parts of the housing can increase in
temperature to over 65 °C (149 °F).
w
Risk of burns
u
Do not touch the device with your hands.
u
Use another object (e.g. a ballpoint pen) to carry out settings on the unit.
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
10.1 Parameter setting via IO-Link
For parameter setting via the IO-Link interface, you need suitable parameter setting software and the
IO Device Description (IODD) for the unit.
•
IODD, parameter setting software and information on IO-Link at
.
•
Notes on parameter setting
Ò
Manual of the parameter setting software.
•
List of all available parameters in the PDF "IO-Link interface description" at
Via IO-Link, all parameters can be set that are also accessible via the keys on the unit. In addition, the
functions described below are available.
10.1.1 System commands
10.1.1.1 Flashing On / flashing off
The command is used to visually locate the unit in the installation. When activated, the switching
status LEDs flash and "IO-L" is displayed.
10.1.1.2 Distance teach
The command is used to teach a switch point SP1 or SP2 for the current object distance. See also
Distance teach (
10.1.2 Identification
Information about the unit is provided via the IODD. In addition, customer-specific descriptions
for identification can be assigned to the unit via IO-Link.
10.1.2.1 Application Specific Tag
•
Customer-specific application description.
•
Maximum length 32 characters and freely definable.