background image

Air gap sensor

SDP110

23

10 Parameter setting

The parameters can be set via the IO-Link interface or via the keys on the unit.

CAUTION

If the medium temperature is above 50 °C (122 °F), parts of the housing can increase in
temperature to over 65 °C (149 °F).

w

Risk of burns

u

Do not touch the device with your hands.

u

Use another object (e.g. a ballpoint pen) to carry out settings on the unit.

Parameters can be set before installation or during operation.

If you change parameters during operation, this will influence the function of the plant.

u

Ensure that there will be no malfunctions in your plant.

During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.

10.1 Parameter setting via IO-Link

For parameter setting via the IO-Link interface, you need suitable parameter setting software and the
IO Device Description (IODD) for the unit.

IODD, parameter setting software and information on IO-Link at 

io-link.ifm

.

Notes on parameter setting 

Ò

 Manual of the parameter setting software.

List of all available parameters in the PDF "IO-Link interface description" at

documentation.ifm.com

.

Via IO-Link, all parameters can be set that are also accessible via the keys on the unit. In addition, the
functions described below are available.

10.1.1 System commands

10.1.1.1 Flashing On / flashing off

The command is used to visually locate the unit in the installation. When activated, the switching
status LEDs flash and "IO-L" is displayed.

10.1.1.2 Distance teach

The command is used to teach a switch point SP1 or SP2 for the current object distance. See also
Distance teach (

Ò

 

/

 26).

10.1.2 Identification

Information about the unit is provided via the IODD. In addition, customer-specific descriptions
for identification can be assigned to the unit via IO-Link.

10.1.2.1 Application Specific Tag

Customer-specific application description.

Maximum length 32 characters and freely definable.

Summary of Contents for SDP110

Page 1: ...Operating instructions Air gap sensor SDP110 80300121 00 04 2021 GB...

Page 2: ...8 2 Main menu and submenus 18 9 Set up 22 10 Parameter setting 23 10 1 Parameter setting via IO Link 23 10 1 1 System commands 23 10 1 1 1 Flashing On flashing off 23 10 1 1 2 Distance teach 23 10 1...

Page 3: ...ero point calibration pressure 28 10 2 5 11 Switch on switch off delay 28 10 2 5 12 Error behaviour of the outputs 28 10 2 5 13 Lock unlock 28 10 2 5 14 Factory reset 29 10 2 6 Diagnostic functions 29...

Page 4: ...nit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunc...

Page 5: ...this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrict...

Page 6: ...013 mbar 101 3 kPa 15 C and 0 relative air humidity The unit can be set to different standard conditions Electromagnetic compatibility EMC This is a class A product This product may cause radio interf...

Page 7: ...gue signal flow Analogue signal pressure Input for external distance teach OFF output switched to high impedance 4 3 Distance measurement The unit measures the volume flow flow rate time and thus dete...

Page 8: ...general the following applies Dmax measuring nozzle at the exit measuring nozzle in mm Dmax in m Dmax none 1 0 250 500 1 1 275 550 1 2 300 600 1 3 325 650 1 4 350 700 1 5 375 750 1 6 400 800 1 7 425 8...

Page 9: ...imum distance Distance measurement 7 and the final value of the measuring range Technical data must be observed when setting SP rP FL and FH The switching signal in case of a fault is adjustable FOU O...

Page 10: ...e signal goes to 3 5 mA distance measurement and flow measurement 4 6 Measured value damping Use the damping time dAP to set after how many seconds the output signal has reached 63 of the final value...

Page 11: ...FH MAW MEW Fig 5 Colour change in the window section cFL Lower limit value cFH Upper limit value MAW Initial value of the measuring range MEW Final value of the measuring range The limits can be freel...

Page 12: ...rameters to identify the units in the plant Additional parameter and diagnostic functions events compared to the SIO mode Data storage Automatic transfer of parameters when a unit is replaced Logging...

Page 13: ...ntact u Apply the supplied warning label to the sensor cable u Ensure that the system is free of pressure during installation u The rules and regulations for the installation and operation of compress...

Page 14: ...u Avoid cracks or tapering between the sensor and the push in fitting u Do not use threads with hexagon socket mounting They can have a negative impact on the flow profile of the sensor and lead to an...

Page 15: ...its diameter at the outlet The access bore hole of the measuring nozzle has 2 5 x the diameter of the measuring nozzle at the outlet Expanding the access bore hole to an angle of 120 The outlet of the...

Page 16: ...e Pin Connection 1 L 3 L 4 OUT1 Switching signal distance Switching signal flow Switching signal pressure IO Link OFF output switched to high impedance 2 OUT2 Switching signal distance Switching signa...

Page 17: ...and display elements 1 Switching status LED for OUT1 2 Switching status LED for OUT2 3 TFT display 4 Keys for changing views and parameter setting Display illumination Unit temperature 70 C brightnes...

Page 18: ...vigate from the process value display to the main menu and from there to the submenus Process value display 1 Main menu 2 Extended functions EF 6 Min max memory MEM 7 Display settings DIS 3 Output 1 O...

Page 19: ...UT1 OUT2 CFG MEM DIS COLR SIM rP1 SP1 t SP1 FH1 FL1 AEP2 ASP2 rP2 SP2 t SP2 FH2 FL2 Process value display Fig 13 Main menu EF rES Info OUT1 OUT2 CFG MEM DIS COLR SIM OUT1 OUT2 CFG MEM DIS COLR SIM Mai...

Page 20: ...g 15 Output 1 OUT1 menu SEL2 ou2 FOU2 OUT2 OU On OFF Hno Hnc Fno Fnc tch I OFF FLOW DIST PRES AEP2 ASP2 SP2 rP2 FH2 FL2 dS2 dr2 EF Fig 16 Output 2 OUT2 menu EF CFG rEF T NOZ diA LFC rEF P coF dAP F dA...

Page 21: ...0 OFF L2 Flow L2 Pres L1 L3 EF Fig 19 Display settings DIS menu COLR cFH F cFH D cFL D cFL F coL D bk wh red green yellow r cF G cF cFH P cFL P coL P bk wh red green yellow r cF G cF bk wh red green y...

Page 22: ...signals according to the set parameters During the power on delay time the outputs are switched as programmed ON with normally open function Hno Fno OFF with normally closed function Hnc Fnc If outpu...

Page 23: ...ftware and the IO Device Description IODD for the unit IODD parameter setting software and information on IO Link at io link ifm Notes on parameter setting Manual of the parameter setting software Lis...

Page 24: ...in general Intention Action Change from the process value display to the main menu Change to the submenu Use to navigate to the sub menu e g EF then Select the requested parameter or Change to the set...

Page 25: ...10 2 3 1 Limit monitoring OUTx hysteresis function u Select the OUTx menu u Select oux and set the switching signal Hno hysteresis function normally open Hnc hysteresis function normally closed u Sel...

Page 26: ...t u Select the OUTx menu u Select SELx and set DIST u Select oux and set the switching signal Hno hysteresis function normally open Hnc hysteresis function normally closed u Select the main menu u Sel...

Page 27: ...d set the brightness of the display 25 50 75 100 OFF The process value display is switched off in the operating mode energy saving mode Error messages are displayed even if the display is deactivated...

Page 28: ...nu u Select LFC and set the limit below which a flow is evaluated as standstill 10 2 5 9 Standard conditions u Select the CFG menu u Select rEF P and set the standard pressure u Select rEF T and set t...

Page 29: ...Lo D Minimum value of the distance measured in the process Hi D Maximum value of the distance measured in the process Lo F Minimum value of the flow value measured in the process flow volume or flow...

Page 30: ...SDP110 Air gap sensor 30 On The simulation starts The values are simulated for the time set under S Tim Abort by pressing any key OFF The simulation is not active...

Page 31: ...set standard unit of measurement and other views w After 30 s the unit returns to the standard display 2 1 Running 20 m Running 20 m 0 0 m h 0 00 bar 1 Standard display as set under dis L 2 Overview...

Page 32: ...etting if necessary Title line Running Process value line NoData Process value invalid u Check process conditions Title line Parameter Error Process value line PARA Parameter setting outside the valid...

Page 33: ...ock via system Setting keys locked via parameter setting software parameter change rejected u Unlock the unit via IO Link interface using the parameter setting software Title line IO Link flash Proces...

Page 34: ...pair Only the manufacturer is allowed to repair the unit u Flush the unit at regular intervals with higher pressure maximum 16 bar to remove any soiling in the measuring channel 13 3 Disposal u After...

Page 35: ...r1 0 FOU1 On OUT2 SEL2 DIST ou2 I ASP2 0 m AEP2 250 m FOU2 On CFG uni F m3 h uni D m uni P bar dAP F 0 6 s dAP P 0 06 s P n PnP NOZ 1 diA 1 00 mm LFC 0 05 m h rEF P 1013 mbar rEF T 15 C coF 0 00 bar D...

Reviews: