Operating instructions 

Flow meter compressed air

SD6020

80282583 / 01   03 / 2023

UK

Summary of Contents for SD6020

Page 1: ...Operating instructions Flow meter compressed air SD6020 80282583 01 03 2023 UK...

Page 2: ...ring via pulse signals 12 4 4 4 Consumed quantity monitoring via preset counter 12 4 5 Measured value damping 13 4 6 Low flow cut off 13 4 7 Simulation 13 4 8 Colour of the characters in the display 1...

Page 3: ...monitoring by pulse signal OUT1 or OUT2 37 10 3 2 Quantity monitoring by preset counter OUT1 or OUT2 37 10 3 3 Manual counter reset 37 10 3 4 Time controlled counter reset 37 10 3 5 Deactivation of t...

Page 4: ...ce repair and disposal 46 14 Factory setting 47 1 Preliminary note Detailed instructions technical data approvals and other information via the QR code on the unit on the packaging or at www ifm com 1...

Page 5: ...ore setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environ mental conditions without any restrictions Only use th...

Page 6: ...O 2533 i e volume flow at 1013 mbar 15 C and 0 relative air humidity The unit can be set to different standard conditions 10 5 7 This is a class A product This product may cause radio interference in...

Page 7: ...The unit generates 2 output signals according to the parameter setting OUT1 6 selection options switching signal for volumetric flow quantity limit switching signal for temperature limit switching si...

Page 8: ...FL lower limit FE window Hnc Fnc NC normally closed When the hysteresis function is set the set point SP is defined first and then the reset point rP which must have a lower value If only the set poi...

Page 9: ...suring range If the measured value is outside the measuring range or in the event of an internal error the current signal indicated in Fig 1 is provided For measured values outside the display range o...

Page 10: ...isplay range 5 measuring range 6 scaled measuring range Q flow T temperature MAW initial value of the measuring range for non scaled measuring range With setting of a low flow cut for Q signal output...

Page 11: ...etric flow quantity every 10 minutes After a power failure this value is available as the current meter reading If a time controlled reset is set the elapsed time of the set reset interval is also sav...

Page 12: ...3 5 The output switches when the volumetric flow quantity set with ImPS has been reached The output remains switched until the counter reset The preset counter is only reset when a manual reset is mad...

Page 13: ...nction the process values flow temperature and meter reading of the totaliser are simulated and their signal chain is reviewed When the parameters cr UL UL OL und cr OL are set the process values that...

Page 14: ...to green or vice versa Fig 2 r cF red display colour between the limits cFL cFH G cF green display colour between the limits cFL cFH cFL cFH MAW MEW cFL lower limit cFH upper limit MAW initial value...

Page 15: ...are and software can be found at www ifm com 4 9 1 Additional functions via IO Link The following functions are only available via the IO Link interface by means of a parameter setting software Flash...

Page 16: ...of the unit Adhere to the distances between sensor and interference Interference Distance to the sensor changes to the pipe diameter 10 x pipe diameter 90 elbow 10 x pipe diameter two 90 elbows one pl...

Page 17: ...gth horizontal unit vertical 3 pipe length right unit on side 4 avoid pipe length left unit on side 5 3 Installation in pipes Fit the unit in the pipe in accordance with the flow direction arrow on th...

Page 18: ...BU blue WH white Pin Connection 4 OUT1 switching signal for volumetric flow switching signal for temperature switching signal for preset counter pulse signal for quantity meter IO Link OFF 2 OUT2 InD...

Page 19: ...ples 2 x positive switching 2 x negative switching L L 3 BU 4 BK 2 WH 1 BN L L 3 BU 4 BK 2 WH 1 BN 1 x positive switching 1 x analogue 1 x negative switching 1 x analogue L L 3 BU 4 BK 2 WH 1 BN L L 3...

Page 20: ...lay of the parameters and parameter values 4 and buttons Select parameter Change parameter value hold button pressed Change of the display unit in the normal operating mode RUN mode Lock Unlock button...

Page 21: ...hanges between the standard indication and two other views After 30 s the device returns to the standard display Running 20 0 l min 1 Totalizer Running 100 l Last Totalizer 0 00 l Time since reset 3 R...

Page 22: ...EF rES rTo Info OUT1 OUT2 CFG MEM DIS COLR SIM ImPS1 ImPR1 AEP2 ASP2 SP2 rP2 FH2 FL2 ImPS2 ImPR2 DIn2 Explanation of the parameters 8 4 Submenu OUT1 and 8 5 Submenu OUT2 The displayed parameters chang...

Page 23: ...on and setting options rES restore factory setting rTo reset of the totaliser Info display device information OUT1 configuration output 1 OUT2 configuration output 2 CGF configuration basic settings M...

Page 24: ...24 8 4 Submenu OUT1 Main menu rES rTo Info OUT1 OUT2 CFG MEM DIS COLR SIM EF SEL1 ou1 dS1 dr1 FOU1 OUT1 OU On OFF Hno Hnc Fno Fnc ImP OFF TEMP FLOW rP1 SP1 FH1 FL1 ImPS1 ImPR1...

Page 25: ...rmally closed ImP consumed quantity monitoring totaliser function OFF output OFF of high impedance SP1 set point for OUT1 rP1 reset point for OUT1 FH1 upper limit value for OUT1 FL1 lower limit for OU...

Page 26: ...26 8 5 Submenu OUT2 Main menu rES rTo Info OUT1 OUT2 CFG MEM DIS COLR SIM EF SEL2 ou2 FOU2 OUT2 OU On OFF Hno Hnc Fno Fnc In D ImP I OFF TEMP FLOW AEP2 ASP2 SP2 rP2 FH2 FL2 ImPS2 ImPR2 DIn2 dS2 dr2...

Page 27: ...put for external counter reset signal OFF output OFF of high impedance ASP2 analogue start point for OUT2 AEP2 analogue end point for OUT2 SP2 set point for OUT2 rP2 reset point for OUT2 FH2 upper lim...

Page 28: ...28 8 6 Submenu CFG Main menu rES rTo Info OUT1 OUT2 CFG MEM DIS COLR SIM EF CFG uni T C F LFC rEF P rEF T SySP dAP F uni F l min m s ft3 h ft3 min ft s m3 h P n PnP nPn...

Page 29: ...unit of measurement for temperature dAP F measured value damping for volumetric flow P n output logic LFC low flow cut off rEF P standard pressure to which the measured and display values for volumet...

Page 30: ...30 8 7 Submenus MEM DIS Main menu rES rTo Info OUT1 OUT2 CFG MEM DIS COLR SIM EF DIS diS L L2 Temp L2 Totl L1 L3 diS U d1 d2 d3 diS R 0 90 180 270 diS B 25 50 75 100 OFF Lo T Hi F Hi T Lo F MEM...

Page 31: ...u DIS Parameter Explanation and setting options diS L standard process value display L1 current process value for volumetric flow L2 Temp current process value for flow and temperature L2 Totl current...

Page 32: ...o OUT1 OUT2 CFG MEM DIS COLR SIM EF COLR cFH T cFH F cFL F cFL T coL F bk wh red green yellow r cF G cF bk wh red green yellow r cF G cF coL T coL V bk wh red green yellow SIM S TMP OL cr OL cr UL UL...

Page 33: ...nge for temperature measurement coL V colour of the characters in the display for the totaliser value bk wh permanently black white yellow permanently yellow green permanently green red permanently re...

Page 34: ...ower on delay time 10 Parameter setting CAUTION The housing can heat up considerably Risk of burns Do not touch the device with your hands Use another object e g a ballpoint pen to carry out settings...

Page 35: ...ia software This locking can only be removed with a parameter setting software 10 1 1 Select submenu 1 Press to change from the process value display to the main menu 2 Press to select the menu EF and...

Page 36: ...ally closed Select SPx and set the value at which the output is set Select rPx and set the value at which the output is reset Menu OUTx SELx oux SPx rPx 10 2 2 Limit monitoring OUT1 or OUT2 window fun...

Page 37: ...oux ImPSx ImPRx 10 3 2 Quantity monitoring by preset counter OUT1 or OUT2 Select uni F and set the unit of measurement Select SELx and set FLOW Select oux and adjust the pulse output ImP Select ImPSx...

Page 38: ...at which the output is set Select rPx and set the value at which the output is reset Menu OUTx SELx oux SPx rPx 10 4 2 Limit monitoring OUT1 or OUT2 window function Select uni T and set the unit of me...

Page 39: ...switched off in the operating mode Error messages are displayed even if the display is deactivated Display activation by pressing any key Menu DIS diS L diS U diS R diS B 10 5 2 Standard unit of meas...

Page 40: ...t LFC and set limit below which a current is evaluated as standstill Menu CFG LFC 10 5 7 Standard conditions Select rEF P and set the standard pressure Select rEF T and set the standard temperature Me...

Page 41: ...cFH outside colour change to red Select cFH x and cFL x and set the limits for the colour window cFH F upper limit for volumetric flow cFL F lower limit value for volumetric flow cFH T upper limit val...

Page 42: ...spective of the error as defined with the parameters Analogue output On the analogue signal goes to the upper error value 4 3 OFF the analogue value goes to the lower error value 4 3 OU the analogue s...

Page 43: ...x or Hi x Keep and pressed is displayed Briefly press It is recommended to delete the memories as soon as the unit oper ates under normal operating conditions for the first time Menu MEM Lo x Hi x 10...

Page 44: ...s signals are classified according to NAMUR recommendation NE107 If several diagnostic events occur simultaneously only the diagnostic message of the result with the highest priority is displayed If o...

Page 45: ...circuit or excessive current Short circuit OUT1 OUT1 Short circuit OUT1 Check switching output OUT1 for short circuit or exces sive current Short circuit OUT2 OUT2 Short circuit OUT2 Check switching o...

Page 46: ...activate IO Link function Detection zone 4 3 Figure 1 Error In the event of an error the outputs react according to the setting under FOU1 and FOU2 10 5 11 Warning LED flashes LED flashes quickly 13 M...

Page 47: ...tory setting User setting EF rTo OFF OUT1 SEL1 FLOW ou1 Hno SP1 FH1 20 rP1 FL1 19 ImPS1 0 0001 m3 ImPR1 YES dS1 0 dr1 0 FOU1 OFF OUT2 SEL2 FLOW ou2 I ASP2 0 AEP2 100 SP2 FH2 40 rP2 FL2 39 ImPS2 0 0001...

Page 48: ...r setting CFG uni F m3 h uni T C dAP F 0 6 s P n PnP LFC 0 1 m3 h rEF T 15 C SySP 6 bar DIS diS L L3 diS U d3 diS R 0 diS B 75 COLR coL F bk wh coL T bk wh coL V bk wh The percentage values refer to t...