background image

18

 

> Return to the next higher menu level� The changed parameter settings are not 

accepted�

9.1.3  Change to the process value display (RUN mode)

There are 3 possibilities:
1�  Wait for 30 seconds 

(→ 9.1.5 Timeout)

2�  Change from the submenu to the main menu, from the main menu to the pro-

cess value display with [▲] or [▼].

3�  Press [

] + [

] simultaneously until the RUN mode is reached�

9.1.4  Locking / Unlocking

The unit can be locked electronically to prevent unintentional settings� On delivery: 

not locked�
Locking:

 

Make sure that the unit is in the normal operating mode�

 

► Press [▲] and [▼] simultaneously for 10 s until [Loc] is displayed.

During operation: [LOC] is briefly displayed if you try to change parameter 

values�

Unlocking:

 

Make sure that the unit is in the normal operating mode�

 

► Press [▲] and [▼] simultaneously for 10 s until [uLoc] is displayed.

9.1.5  Timeout

If no button is pressed for 30 s during parameter setting, the unit returns to the 

operating mode with unchanged values�

9.2  Settings for consumed quantity monitoring
9.2.1  Limit value monitoring with OUT1 / hysteresis function

 

Select [SEL1] and set [FLOW]�

 

Select [ou1] and set the switching function: 

 -[Hno] = hysteresis function/normally open

 -[Hnc] = hysteresis function/normally closed

 

Select [SP1] and set the value at which the output is set�

 

Select [rP1] and set the value at which the output is reset�

Menu CFG:

[SEL1]

[ou1]
Main menu: 

[SP1] 

[rP1]

Summary of Contents for SBG2 Series

Page 1: ...Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx 80008231 00 04 2015 UK...

Page 2: ...ion main menu 13 8 2 Extended functions Basic settings 14 8 2 1 Explanation basic settings CFG 15 8 3 Extended functions Min max memory Display 16 8 3 1 Explanation min max memory MEM 16 8 3 2 Explana...

Page 3: ...lumetric flow 20 9 3 6 Configuration of the standard display 20 9 3 7 Configure colour change display 21 9 3 8 Set the damping for the switching output 21 9 3 9 Set damping for the analogue output 21...

Page 4: ...the unit must only be carried out by qualified personnel authorised by the machine operator In order to guarantee the correct condition of the device for the operating time it is necessary to use the...

Page 5: ...nication The unit displays the current volumetric flow quantity or temperature It gener ates 2 output signals according to the parameter setting OUT1 IO Link 4 selection options Parameter setting Swit...

Page 6: ...switching status of the output stable if the volumetric flow varies slightly 4 2 Analogue function The unit provides an analogue current signal that is proportional to the volumetric flow quantity an...

Page 7: ...7 UK A Volumetric flow monitoring MEW 0 100 mA 5 7 2 8 4 1 6 B Temperature monitoring C F 20 10 100 110 5 7 8 4 6 3 mA 1...

Page 8: ...cation is possible via a point to point connection with a USB adapter cable You will find more detailed information about IO Link at www ifm com gb io link 4 3 2 Device specific information You will f...

Page 9: ...re not necessary The sensor has the function of a non return valve The sensor head can be rotated by 360 Do not install the unit on ferromagnetic materials Ferromagnetic materials are all metals exert...

Page 10: ...llows 4 3 2 1 BK black BN brown BU blue WH white BN WH BK BU 4 1 3 2 OUT2 L L OUT1 Colours to DIN EN 60947 5 2 Sample circuits 1 x positive switching 1 x analogue 1 x negative switching 1 x analogue L...

Page 11: ...4 digits Display of current process values volumetric flow quantity temperature Display of the parameters and parameter values 4 Button Enter Change from the RUN mode to the main menu Change to the se...

Page 12: ...et parameters have a white background The parame ters with a grey background do not become visible before change to the preset values 8 1 Process value display RUN and main menu RUN EF_ m3 h l min C r...

Page 13: ...mit value at which OUT1 switches rP1 Reset point 1 lower limit value at which OUT1 is reset Switching output with window function FH1 Set point 1 upper limit value at which OUT1 switches FL1 Reset poi...

Page 14: ...1 SEL2 EF RUN CFG CFG_ rES MEM_ DIS_ FLOW TEMP FLOW TEMP nPn PnP 0 1 0 uni m3h Lmin GPH GPm FOU1 FOU2 OFF On OU OFF On OU MEdi OIL H2O OIL 2 gpm gph for SBN2xx units rES Restoring the factory settings...

Page 15: ...put logic pnp npn dAP Measured value damping for switching output in seconds dAA Measured value damping for analogue output in seconds MEDI Medium selection for volumetric flow FOU1 Behaviour of outpu...

Page 16: ...ocess Hi T Max value of the temperature measured in the process 8 3 2 Explanation display settings DIS coLr Assignment of the display colours red and green within the measuring range rEd Display alway...

Page 17: ...setting in general 1 Change from the RUN mode to the main menu 2 Select the requested parameter or 3 Change to the setting mode 4 Modification of the parameter value or 1 s 5 Acknowledge the set param...

Page 18: ...10 s until Loc is displayed During operation LOC is briefly displayed if you try to change parameter values Unlocking Make sure that the unit is in the normal operating mode Press and simultaneously...

Page 19: ...nction Select SEL1 and set TEMP Select ou1 and set the switching function Hno hysteresis function normally open Hnc hysteresis function normally closed Select SP1 and set the value at which the output...

Page 20: ...value in the standard unit of measurement is displayed TEMP the current medium temperature in C is displayed SBN2xx F Select diS and set the update rate and orientation of the display d1 update of the...

Page 21: ...itching output OUT1 with window function FL1 FH1 FL1 FH1 r1ou G1ou Menu DIS coLr MAW initial value of the measuring range MEW final value of the measuring range Red Green 9 3 8 Set the damping for the...

Page 22: ...defined with the parameters The analogue signal corresponds to the measured value Menu CFG FOU1 FOU2 9 4 Service functions 9 4 1 Read the min max values for the temperature Select Hi T or Lo T and rea...

Page 23: ...lumetric flow quantity l min or m3 h for SBN2xx gpm or gph 9 3 5 In RUN mode further process values can be read in addition to the preset stand ard display Press the buttons or The LED of the selected...

Page 24: ...OL Detection zone of volumetric flow or temperature exceeded Measured value between 120 and 130 of the final value of the measuring range UL Below the detection zone of temperature Measured value betw...

Page 25: ...54 F rP1 FL1 TEMP 11 C 52 F ou1 Hno SEL1 FLOW SEL2 FLOW SELd FLOW FOU1 ou FOU2 ou uni FLOW L min gal min P n PnP dAP FLOW 0 1 dAA FLOW 0 MEdI H2O coLr rEd diS d2 The percentage values refer to the fin...

Reviews: