22
9.3.10 Setting of the error behaviour of the outputs
►
Select [FOU1] and set the value:
-[On] = output 1 switches ON in case of an error�
-[OFF] = output 1 switches OFF in case of an error�
-[OU] = output 1 switches irrespective of the fault as defined with the
parameters�
►
Select [FOU2] and set the value:
-[On] = output 2 switches ON in case of an error, the analogue signal
goes to the upper error value�
-[OFF] = output 2 switches OFF in case of an error, the analogue signal
goes to the lower error value�
-[OU] = output 2 switches irrespective of the fault as defined with the
parameters� The analogue signal corresponds to the measured value�
Menu CFG:
[FOU1]
[FOU2]
9.4 Service functions
9.4.1 Read the min/max values for the temperature
►
Select [Hi�T] or [Lo�T] and read the value�
[HI�T] = max� value, [LO�T] = min� value�
Delete memory:
►
Select [Hi�T] or [Lo�T]�
► Briefly press [●].
► Keep [▲] or [▼] pressed.
> [----] is displayed�
► Briefly press [●].
It makes sense to delete the memories as soon as the unit operates
under normal operating conditions for the first time�
Menu MEM:
[Hi�T]
[Lo�T]
9.4.2 Resetting all parameters to factory setting
►
Select [rES]�
► Press [●].
► Press [▲] or [▼] and keep pressed until [----] is displayed.
► Briefly press [●].
It is recommended to take down your own settings in the table before
�
Menu EF:
[rES]