Photoelectric distance sensor
OGD25x OGD55x
25
11 Parameter setting
Internally, the device remains in the operating mode during parameter setting. It continues its
monitoring function with the existing parameters until the change has been completed.
For [SPx], [nSPx], [FSPx], [dSPx], [bSPx], [ASP], [AEP], the current and yet unconfirmed value
is used for the evaluation. This way, the result of parameter setting can be assessed directly. If
the parameter setting is cancelled, the previous value is restored.
11.1 General parameter setting
Timeout: If no button is pressed for 30 s during the setting procedure, the device returns to Run
mode with unchanged values.
11.1.1 Setting a parameter value
Select Parameter
u
Press the [●] button to access menu level 1.
u
Press the [▲/▼] button until the required parameter is displayed.
Set parameter value
u
Briefly press the [●] button.
w
The current parameter value is displayed.
u
Keep the [▲/▼] button pressed.
w
The current parameter value flashes for 3 s.
u
Increase / decrease the parameter value step by step by pressing the button once or continuously
by holding it down.
As soon as the minimum / maximum parameter value is reached, the display changes to [bAck]
and then back to the minimum / maximum parameter value.
Acknowledge parameter value
u
Briefly press the [●] button.
w
The display changes back to menu level 1 and is thus effective.
Cancelling parameter setting
u
Wait for 30 s or press either [bAck] or the [▲] + [▼] button. If necessary, repeat the last abort
option several times to access menu level 0.
w
The display changes back to run mode and shows the current measured value.
11.1.2 Changing from menu level 1 to the menu level 2
u
Repeatedly press the [▲/▼] button until [EF] is displayed.
u
Confirm [EF] with [●].
w
The display changes to menu level 2.
11.1.3 Locking / unlocking the device
The device can be locked electronically to prevent unauthorised setting. On delivery the device is not
locked.