3

UK

3  Functions and features

With this unit angular movements and positions of the valve between 0°...179.9° 
and -180°...0° can be determined. The unit generates output signals according to 
the operating mode and the parameter setting.

4   Installation

 

► Disconnect power before installation.

 

► Ensure that the machine stands still.

 

► Do not start the drive during installation.

 

► Keep potential interfering sources (magnets, heat sources) at a distance.
This product complies with the standard EN 61000-6-4. The unit may cause radio 
interference in domestic areas. The user must take appropriate measures to avoid 
this interference, if necessary. 

1

2

3

1:  Use the two notches at the bottom of 

the target puck as a mounting aid for a 
precise positioning on the shaft. Align 
target puck. The yellow indicator can 
be rotated to show the desired open 
position.
Fix the target puck to the valve head 
using the supplied screw, tightening 
torque 1.2 Nm. 

2:  Put the unit over the target puck.
3:  Fix the unit to the actuator housing 

using the supplied screws, tightening 
torque 1.5 Nm. Use an optional 
mounting plate, depending on the 
mechanical interface.

Summary of Contents for MVQ101

Page 1: ...Device manual Valve sensor MVQ101 80270936 00 04 2018 UK...

Page 2: ...y may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator Installation electrical connection set up opera...

Page 3: ...h the standard EN 61000 6 4 The unit may cause radio interference in domestic areas The user must take appropriate measures to avoid this interference if necessary 1 2 3 1 Use the two notches at the b...

Page 4: ...pin 4 Communication IO Link Switching output valve position open in SIO mode OUT 2 pin 2 Switching output valve position closed OUT 3 pin 5 Programmable Switching output valve position open Switching...

Page 5: ...ctory red flashing fault in the unit no pulse pick up available teach error switch points SSC1 and SSC2 overlap end position not reached after set time has elapsed unit faulty The LED colours in the t...

Page 6: ...ble Reading current process values Reading changing and saving current parameter settings and transmitting them to other units of the same type Connect the unit via the IO Link interface to a PC or PL...

Page 7: ...lerance and hysteresis can be set separately for each switch point with an additional seal monitoring for SSC2 9 3 2 Parameter setting via inductive teach button The sensor is adjusted using a metal o...

Page 8: ...ch button approx 20 s until the LED ring briefly flashes once 10 Settings 2 2 1 Settings tolerance Set a tolerance range between 0 1 and 15 around the taught set switch point 1 Teach point 2 Tolerance...

Page 9: ...Tolerance width 10 1 Timeout Timeout indicates the maximum duration for closing or opening before the sensor signals a blockage Adjustable time between 0 1 30 s factory setting 30 s In parallel the p...

Page 10: ...Defect of the unit Puck not used Limit value for the timeout exceeded 10 4 Opening closing duration The minimum maximum closing opening duration of the drive can be freely set and monitored The sensor...

Reviews: